manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Johnson Controls
  6. •
  7. Switch
  8. •
  9. Johnson Controls S-224 User manual

Johnson Controls S-224 User manual

Pneumatic Control Manual 717.1
Selector Switches Section
Reference Bulletin # 1
Issue Date 37JC3
©Johnson Controls, Inc. 1
Code No. LIT-7171390X
Limited Adjustment and Stops
for S-224 Remote Set Point Gradual Switches
Since the introduction of the T-9000 series receiver-
controllers, setting the upper and lower pressure
limits of the S-224 and S-223 gradual switches for
remote set point applications has become very
important. The following adjusting instructions are
centered around a typical T-9000 remote set point
application. The 6 psi span gradual switch is
recommended for use with 25°F and 50°F span
transmitters. The 2 psi span gradual switch is
recommended for use with 100°F and 200°F span
transmitters.
Adjusting Procedure
With either 15 or 20 psi supply air:
1. Insert a test gage into the output line of the
gradual switch.
2. Turn on supply air pressure.
3. Remove knob and turn adjusting shaft clockwise
against stop.
4. Loosen locknut.
Example (Using 6 psi Gradual Switch)
To reset over a small range (± 10°F for a 100°F span
transmitter), the output change the gradual switch
must produce is 2.4 psi (0 to 100°span transmitter
sensitivity x 20°F remote reset change, or ± 1.2 psi
output change from set point).
Assume a 0 to 100°F transmitter is to be used and
the required set point is 75°F. This is equal to a
transmitter output of 12 psi. Therefore, with the
± 10°F set point change, the remote gradual switch
will be set to produce an output signal from 10.8 to
13.2 psi.
5. Adjust the calibrating set screw until the required
maximum output pressure is obtained (example,
13.2 psi). Retighten locknut.
6. Turn adjusting shaft until midpoint of pressure
range is indicated on gage (example, 12 psi or
75°F required set point).
7. Replace knob with pointer on midpoint of dial
scale.
Low Pressure Stops
If fixed lower stops are required, they must be
supplied in the field. Suggested method:
1. Rotate the adjusting knob to the minimum
pressure (10.8 psi).
2. Mark the dial just to the left of the pointer.
3. Remove the knob and drill a small hole for a set
screw, or remove the dial and use a small nail
for the stop. The head of the nail will act as a
holding device when the dial is reattached. This
type of stop can also be located under the knob.
Dials
Table 1 lists the dials recommended for remote
adjustment applications. Also listed are three
pressure spans and degrees per graduation for each
transmitter span.
2 psi Span Gradual Switch
Only the S-224 gradual switch can be changed to a
2 psi span. To accomplish this, order Conversion Kit
S-224-100 (Standard Equipment Book).
6 psi Span Gradual Switch
To change an S-223 or S-224 gradual switch with a
20 psi span to a 6 psi span, a new spring and an
adjusting screw are required. Order on Form 1634
(Part # 20-38096 and 69-17415-79, respectively).
2S-224 Reference Bulletin
Pulsations
Instruments having pneumatic feedback, such as the
S-224 gradual switch, may have a tendency to
pulsate when there is not enough capacity in the
control air line. The pulsations often occur (and are
objectionable) when an S-224 is used to readjust a
controller.
Note: Small 2-inch air gages are not very
sensitive to small pressure variation, so the
pulsations producing instability may not be
detectable unless a larger gage is installed.
To correct the pulsating condition, coil approximately
15 feet of 1/4-inch tubing and install it in the control
air line at the gradual switch, or add an in-line
restrictor to the output line. If the pulsations are not
eliminated, replace the tubing or restrictor with a
pulsation chamber (A-4000-114, listed in the
Standard Equipment Book under "Air Compressor
Accessories"). The pulsation chamber has a
sufficient volumetric capacity to eliminate any
pulsations. If a pulsation chamber is not available,
install more tubing in the control air line.
Table 1: Recommended Dials for Remote
Adjustment Applications
Deg. Readjusted/Grad.
S-224 Transmitter 2 psi 6 psi 20 psi
Dial Span (° F) Span Span Span
25 .05 .15 .5
S-224-52 50 .1 .30 1.0
S-224-50 100 .2 .60 2.0
200 .4 1.20 4.0
25 .06 .20 .6
S-224-56 50 .1 .40 1.2
S-224-53 100 .2 .80 2.5
200 .5 1.60 5.0
25 .08 .25 .8
S-224-58 50 .16 .50 1.6
S-224-61 100 .35 1.00 3.5
200 .68 2.00 6.8
25 .24 .75 2.25
S-224-62 50 .4 1.50 4.50
(Cooler- 100 1.0 3.00 9.00
Warmer) 200 2.0 6.00 18.00
Controls Group
507 E. Michigan Street
P.O. Box 423 Printed in U.S.A.
Milwaukee, WI 53202

Other Johnson Controls Switch manuals

Johnson Controls FS80-C User manual

Johnson Controls

Johnson Controls FS80-C User manual

Johnson Controls SBH300 User manual

Johnson Controls

Johnson Controls SBH300 User manual

Johnson Controls exacqVision G Series User manual

Johnson Controls

Johnson Controls exacqVision G Series User manual

Johnson Controls F59D Service manual

Johnson Controls

Johnson Controls F59D Service manual

Johnson Controls F61 series User manual

Johnson Controls

Johnson Controls F61 series User manual

Johnson Controls Penn F262 Series User manual

Johnson Controls

Johnson Controls Penn F262 Series User manual

Johnson Controls G Series User manual

Johnson Controls

Johnson Controls G Series User manual

Johnson Controls IQ4 User manual

Johnson Controls

Johnson Controls IQ4 User manual

Johnson Controls IQ Outlet User manual

Johnson Controls

Johnson Controls IQ Outlet User manual

Johnson Controls OLS-2000 Manual

Johnson Controls

Johnson Controls OLS-2000 Manual

Johnson Controls M9300 Series User manual

Johnson Controls

Johnson Controls M9300 Series User manual

Johnson Controls CSDECM-ADJ Series User manual

Johnson Controls

Johnson Controls CSDECM-ADJ Series User manual

Johnson Controls F61 Series User manual

Johnson Controls

Johnson Controls F61 Series User manual

Popular Switch manuals by other brands

Siemens SIMATIC NET RUGGEDCOM RSG2488F installation manual

Siemens

Siemens SIMATIC NET RUGGEDCOM RSG2488F installation manual

Cisco MDS 9000 Series Configuration guide

Cisco

Cisco MDS 9000 Series Configuration guide

Abtus HDBT-GAHD31T/AP3 User's operation guide

Abtus

Abtus HDBT-GAHD31T/AP3 User's operation guide

Siemens SCALANCE X-200 operating instructions

Siemens

Siemens SCALANCE X-200 operating instructions

Siemens 3WN1 operating instructions

Siemens

Siemens 3WN1 operating instructions

Pilz PSEN cs1.1p operating instructions

Pilz

Pilz PSEN cs1.1p operating instructions

NETGEAR ProSAFE FS526Tv2 Hardware installation guide

NETGEAR

NETGEAR ProSAFE FS526Tv2 Hardware installation guide

Hamlet XU2SATAIDE user manual

Hamlet

Hamlet XU2SATAIDE user manual

olympia electronics RF-52/A/D Installation instruction

olympia electronics

olympia electronics RF-52/A/D Installation instruction

TELUS PureFibre Internet installation guide

TELUS

TELUS PureFibre Internet installation guide

Intercoax HPS-1008 quick start guide

Intercoax

Intercoax HPS-1008 quick start guide

Gefen RMT-MATRIX-444 user manual

Gefen

Gefen RMT-MATRIX-444 user manual

ATEN KL1508AM specification

ATEN

ATEN KL1508AM specification

Bryston SWB6 Schematic diagram

Bryston

Bryston SWB6 Schematic diagram

HB Products HBSC2-SSR quick start guide

HB Products

HB Products HBSC2-SSR quick start guide

Huawei S6700 Series Configuration guide

Huawei

Huawei S6700 Series Configuration guide

Panasonic ZEQUO 6400 operating instructions

Panasonic

Panasonic ZEQUO 6400 operating instructions

Zonet KVM3008 user guide

Zonet

Zonet KVM3008 user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.