Jung 52921 ST User manual

Operating instructions
Universal push-button module, 1-gang
Art. no. 52911 ST
Universal push-button module, 3-gang
Art. no. 52921 ST
Universal push-button module, 3-gang
Art. no. 52931 ST
Universal push-button module, 4-gang
Art. no. 52941 ST
16.05.2023
32408003 j0082408003
ALBRECHT JUNG GMBH & CO. KG
Volmestraße 1
58579 Schalksmühle
GERMANY
Telefon: +49 2355 806-0
Telefax: +49 2355 806-204
www.jung.de

Table of contents
1 Safety instructions ............................................................................................................ 3
2 Device components .......................................................................................................... 3
3 System information........................................................................................................... 3
4 Intended use..................................................................................................................... 4
5 Product characteristics ..................................................................................................... 4
6 Operation.......................................................................................................................... 5
7 Information for electrically skilled persons........................................................................ 5
7.1 Commissioning ...................................................................................................... 7
7.1.1 Safe-state mode........................................................................................ 7
7.1.2 Master reset .............................................................................................. 8
8 Flashing frequencies of the LEDs..................................................................................... 9
9 Technical data .................................................................................................................. 9
10 Accessories .................................................................................................................... 10
11 Warranty ......................................................................................................................... 10
2 / 10
32408003 16.05.2023
j0082408003
Universal push-button module

1 Safety instructions
Electrical devices may be mounted and connected only by electrically skilled
persons.
Serious injuries, fire or property damage are possible. Please read and follow the
manual fully.
Use only the enclosed plastic screws for fastening to the supporting frame! Otherwise
safe operation cannot be ensured. Electrostatic discharges can cause defects in the
device.
This manual is an integral part of the product, and must remain with the customer.
2 Device components
Image1: Push button modules Universal – front view
(1) Status LED
(2) Operation LED
3 System information
This device is a product of the KNX system and complies with the KNX directives.
Detailed technical knowledge obtained in KNX training courses is a prerequisite to
proper understanding.
The function of this device depends upon the software. Detailed information on load-
able software and attainable functionality as well as the software itself can be ob-
tained from the manufacturer´s product database.
Universal push-button module
3 / 10
32408003 16.05.2023
j0082408003

The device can be updated. Firmware can be easily updated with the Jung ETS Ser-
vice App (additional software).
The device is KNX Data Secure capable. KNX Data Secure offers protection against
manipulation in building automation and can be configured in the ETS project. De-
tailed technical knowledge is required. A device certificate, which is attached to the
device, is required for safe commissioning. During mounting, the device certificate
must be removed from the device and stored securely.
Planning, installation and commissioning of the device are carried out with the aid of
the ETS, version 5.7.7 and higher or 6.0.6.
4 Intended use
Intended use
– Operation of loads, e.g. light on/off, dimming, blinds up/down, brightness val-
ues, temperatures, calling up and saving light scenes, etc.
– Mounting in appliance box with dimensions according to DIN 49073
5 Product characteristics
– The push-button sensor functions switching, dimming, controlling blinds, value
transmitter, calling up moods, etc.
– One or two functions per button
– Completion with set of buttons (Accessory)
– Illuminable inscription panel
– One status LED per button – red, green or blue adjustable
– One operation LED as an orientation light and to indicate the programming
status – red, green or blue adjustable
– Brightness of status LED, operation LED and labelling field adjustable; switch-
able while in operation, e.g. during the night
– Measurement of the room temperature
– Extension for room temperature controller
– Disabling function: Disable or function switch-over of all or of individual push-
button functions
– Alarm function, optionally with confirmation by pressing any button
– Energy saving mode
– Integrated bus coupling unit
– Connection for a push-button sensor extension module, for expansion with up
to four additional buttons
Universal push-button module
4 / 10
32408003 16.05.2023
j0082408003

Energy saving mode
The device switches to the energy saving mode after a preset time or by an external
telegram. In energy saving mode all LED functions are switched off. The device
leaves the energy saving mode – depending on programming – on operation or by an
external telegram.
Operations from the energy saving mode are executed immediately.
6 Operation
The operation of functions or electrical consumers can be set individual for each
device. Two operating modes are used:
– Single-area operation (button function):
Switching on or off, e.g. of lighting, takes place alternately when the button is
pressed repeatedly.
– Dual-area operation (rocker function):
Two buttons next to each other form a function pair. Pressing the left button,
for example, switches or dims lighting on or brighter, pressing the right one
switches it off or makes it darker.
Operating a function or load
■ Switch: Short press on button.
■ Dim: Long press on button.
■ Move Venetian blind: Long press on button.
■ Stop or adjust Venetian blind: Short press on button.
■ Call up light scene: Short press on button.
■ Save light scene: Long press on button.
■ Set value, e.g. brightness or temperature setpoint: Short press on button.
■ Adjusting value: Press button for a long time.
Depending on programming, a button triggers several functions after a longer
press or triggers another function if opposite buttons are pressed simultan-
eously.
7 Information for electrically skilled persons
DANGER!
Electric shock when live parts are touched.
Electric shocks can be fatal.
Cover up live parts in the installation environment.
Universal push-button module
5 / 10
32408003 16.05.2023
j0082408003

Mounting and connecting the device
Image2: Installation of Universal push-button sensor module
(3) Supporting frame
(4) Frame
(5) Push-button sensor module
(6) Fastening screws, plastic
(7) Buttons
(8) Connection of the extension module (optional)
(9) KNX device connection terminal
(10) Box screws
DANGER!
Danger of electrical shock!
When mounting with 230 V socket outlets under a common cover there is a danger of
electrical shocks in the event of a fault!
Use only the enclosed plastic screws for fastening to the supporting frame!
■ Mount supporting frame (3) in the right orientation on an appliance box. Note
marking TOP. Use only the enclosed box screws (10).
■ Push frame (4) onto supporting frame.
■ Connect the push-button sensor module (5) to the KNX with the KNX device
connection terminal (9) and push onto the supporting frame.
■ Fix push-button sensor module to supporting frame using the enclosed plastic
screws (6). Tighten the plastic screws only lightly.
■ Before mounting the buttons (7), load the physical address into the device.
Universal push-button module
6 / 10
32408003 16.05.2023
j0082408003

7.1 Commissioning
Preconditions in secure operation
– Secure commissioning is activated in the ETS.
– Device certificate entered/scanned or added to the ETS project. A high resolu-
tion camera should be used to scan the QR code.
– Document all passwords and keep them safe.
Programming the physical address and application program
Project design and commissioning with ETS version 5.7.7 and higher or 6.0.6.
The device is connected and ready for operation.
If the device contains no – or an incorrect – application program, the labelling field
and the operation LED flash slowly.
Image3: Activating programming mode
■ Activate programming mode: Press and hold push-button at the upper left
(11). Then press push-button at the lower right (12).
The operation LED flashes quickly.
■ Programming the physical address.
The operation LED returns to its previous state – off, on, or flashing slowly.
■ Programming the application program.
Installing the buttons
The buttons are available as a complete set of buttons (see accessories).
■ Place the buttons on the device in the correct orientation and snap in with a
short push.
7.1.1 Safe-state mode
The safe-state mode stops the execution of the loaded application program.
Universal push-button module
7 / 10
32408003 16.05.2023
j0082408003

If the device does not work properly - for instance as a result of errors in the project
design or during commissioning - the execution of the loaded application program
can be halted by activating the safe-state mode. The device remains passive in safe-
state mode, since the application program is not being executed (state of execution:
terminated).
Only the system software of the device is still functional. ETS diagnosis functions and
programming of the device are possible.
Activating safe-state mode
■ Switch off the bus voltage.
■ Press and hold down the top left and bottom right button.
■ Switch on the bus voltage.
The safe-state mode is activated. The operation LED flashes slowly (approx. 1
Hz).
Do not release the buttons until the operation LED flashes.
Deactivating safe-state mode
■ Switch off the voltage or carry out ETS programming.
7.1.2 Master reset
The master reset restores the basic device settings (physical address 15.15.255,
firmware remains in place). The device must then be recommissioned with the ETS.
In secure operation: A master reset deactivates device security. The device can then
be recommissioned with the device certificate.
If the device - for instance as a result of errors in the project design or during com-
missioning - does not work properly, the loaded application program can be deleted
from the device by performing a master reset. The master reset resets the device to
delivery state. Afterwards, the device can be put into operation again by program-
ming the physical address and application program.
Performing a master reset
Precondition: The safe-state mode is activated.
■ Press and hold the button at the top left and the button at the bottom right for
more than five seconds until the operation LED flashes quickly (approx. 4 Hz).
■ Release the buttons.
The device performs a master reset.
The device restarts. The operation LED flashes slowly.
Universal push-button module
8 / 10
32408003 16.05.2023
j0082408003

Resetting the device to its default settings
Devices can be reset to factory settings with the ETS Service App. This function uses
the firmware contained in the device that was active at the time of delivery (delivered
state). Restoring the factory settings causes the devices to lose their physical ad-
dress and configuration.
8 Flashing frequencies of the LEDs
State of operation Operation LED Status LED
Application discharged Approx. 0.75 Hz (blue) With On button pressed
(red, green, blue)
Safe-state mode Approx. 1 Hz (blue) ---
Flashing status *) Approx. 2 Hz Approx. 2 Hz
Alarm signal *) Approx. 2 Hz (red) Approx. 2 Hz (red)
Master reset Approx. 4 Hz (red) ---
Programming mode Approx. 8 Hz (blue) ---
Full-surface operation --- Approx. 8 Hz
*) The labelling field is also activated with approx. 2 Hz.
9 Technical data
KNX
KNX medium TP256
Safety KNX Data Secure (X-mode)
Commissioning mode S mode
Rated voltage KNX DC 21 ... 32 V SELV
Current consumption KNX
without TSEM Max. 12 mA
with TSEM Max. 20 mA
Connection mode KNX Device connection terminal
Ambient temperature -5 ... +45°C
Storage/transport temperature -25 ... +70°C
Protectionclass III
Connection of the extension module
Number 1
Cable length Max. 30 m
Cable type J-Y(St)Y 2×2×0.8
Universal push-button module
9 / 10
32408003 16.05.2023
j0082408003

10 Accessories
Cover kit 1-gang ..501 TSA..
Cover kit 2-gang ..502 TSA..
Cover kit 3-gang ..503 TSA..
Cover kit 4-gang ..504 TSA..
Push-button extension module, 1-gang ..5091TSEM
Push-button extension module, 2-gang ..5092TSEM
Push-button extension module, 3-gang ..5093TSEM
Push-button extension module, 4-gang ..5094TSEM
11 Warranty
The warranty is provided in accordance with statutory requirements via the specialist
trade.
ALBRECHT JUNG GMBH & CO. KG
Volmestraße 1
58579 Schalksmühle
GERMANY
Telefon: +49 2355 806-0
Telefax: +49 2355 806-204
www.jung.de
Universal push-button module
10 / 10
32408003 16.05.2023
j0082408003
Table of contents
Other Jung Switch manuals

Jung
Jung AS 1280-1 Series User manual

Jung
Jung FAS180 Series User manual

Jung
Jung 10911ST Series User manual

Jung
Jung 567 S Series User manual

Jung
Jung FA10EB User manual

Jung
Jung DAW 360 WW User manual

Jung
Jung 1254 TSE User manual

Jung
Jung KNX 4071.0 LED Series Operator's manual

Jung
Jung FMAS10ZS User manual

Jung
Jung FMAS816REG User manual

Jung
Jung 1701PSE User manual

Jung
Jung LB management User manual

Jung
Jung Home User manual

Jung
Jung 1701 SE User manual

Jung
Jung 1701SE User manual

Jung
Jung 1704ESE User manual

Jung
Jung KNX 3281-1 Series User manual

Jung
Jung 3181-1 Series User manual

Jung
Jung A3181-1-01 User manual

Jung
Jung 3281-1 Series User manual