manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Juniper
  6. •
  7. Switch
  8. •
  9. Juniper QFX5110-48S User manual

Juniper QFX5110-48S User manual

QFX5110-48S Quick Start Guide
See the complete QFX Series documentation at
http://www.juniper.net/techpubs/ .
To mount, connect power to, and perform the initial configuration of a
Juniper Networks QFX5110-48S, you need:
zElectrostatic discharge (ESD) grounding strap (not provided)
zOne pair of side-mounting rails (provided)
zOne pair of rear-mounting blades (provided)
zTwelve screws to secure the mounting rails and mounting blades to the chassis
(provided)
zEight screws to secure the chassis and mounting blades to the rack (not provided)
zScrewdriver appropriate for your rack mounting screws (not provided)
zTwo power cords with plugs appropriate for your geographical location (provided)
zRJ-45 cable and RJ-45 to DB-9 serial port adapter (provided)
zManagement host, such as a PC laptop, with a serial port (not provided)
Part 1: Mount the Switch
The QFX5110-48S can only be mounted in a four-post 19 inch rack configuration.
To mount the switch:
1. Attach the ESD grounding strap to your bare wrist and to a site ESD point.
NOTE: If you are mounting multiple units in the rack, mount the heaviest unit at the
bottom and mount the others from bottom to top in order of decreasing weight. The
switch weighs approximately 23 lb (10.4kg). Installing the QFX5110-48S in a rack or
cabinet requires two persons to lift the switch and secure it to the rack.
2. Place the rack in its permanent location, allowing adequate clearance for airflow and
maintenance, and secure it to the building structure.
3. Determine whether the end with field replaceable units (FRUs) or the ports must be
placed at the front of the rack.
4. Align the holes in the side-mounting rail with the holes on the side of the chassis.
5. Attach the side-mounting rail to the switch using six mounting screws.
6. Repeat Step 4 and Step 5 on the opposite side of the device.
7. Have one person grasp both sides of the switch, lift it, and position it in the rack so
that the front bracket is aligned with the rack holes.
8. Have the second person secure the front of the switch to the rack by using four
mounting screws (and cage nuts and washers if your rack requires them). Tighten the
screws.
9. Continue to support the switch while sliding the rear-mounting blades into the
channel of the side-mounting rails and securing the blades to the rack. Use the four
mounting screws (and cage nuts and washers if your rack requires them) to attach
each blade to the rack. Tighten the screws.
10. Ensure that the switch chassis is level by verifying that all the screws on the front of
the rack are aligned with the screws at the back of the rack
11. Attach a grounding cable to earth ground and then attach it to the chassis grounding
points.
Part 2: Connect Power to the Switch
The switch is supplied with two factory-installed power supplies.
To connect power to an AC-powered switch:
1. If the AC power source outlet has a power switch, set it to the off (0) position.
2. Insert the coupler end of the power cord into the AC power cord inlet on the AC
power supply faceplate.
3. Push the power cord retainer onto the power cord.
4. Insert the power cord plug into the power source outlet.
5. If the AC power source outlet has a power switch, set it to the on (|) position.
6. Verify that the AC and the DC LEDs are lit green and on steadily.
Part 3: Perform the Initial Configuration
You must perform the initial configuration of the switch through the console port. Before
you begin, set the following parameter values in the console server or PC:
zBaud Rate—9600
zFlow Control—None
zData—8
zParity—None
Attach mounting brackets artwork goes here
g050478
GM
g050480
GM
Copyright © 2016 Juniper Networks, Inc. All rights reserved. Juniper Networks, Junos, Steel-Belted Radius, NetScreen, and ScreenOS are registered trademarks of Juniper Networks, Inc. in the United
States and other countries. The Juniper Networks Logo, the Junos logo, and JunosE are trademarks of Juniper Networks, Inc. All other trademarks, service marks, registered trademarks, or registered
service marks are the property of their respective owners. Juniper Networks assumes no responsibility for any inaccuracies in this document. Juniper Networks reserves the right to change, modify, transfer,
or otherwise revise this publication without notice. Part Number: 530-069174 Revision 01, 18 February 2016.
zStop Bits—1
zDCD State—Disregard
To connect and configure the switch from the console:
1. Connect the console port to a laptop or PC by using the provided RJ-45 cable and
RJ-45 to DB-9 serial port adapter. The console (CON) port is located on the
management panel of the switch.
2. Log in as root. There is no password. If the software booted before you connected
to the console port, you might need to press the Enter key for the prompt to appear.
login: root
3. Start the CLI.
root@% cli
4. Enter configuration mode.
root> configure
5. Add a password to the root administration user account.
[edit]
root@# set system root-authentication plain-text-password
New password: password
Retype new password: password
6. (Optional) Configure the name of the switch. If the name includes spaces, enclose
the name in quotation marks (“ ”).
[edit]
root@# set system host-name host-name
7. Configure the default gateway.
[edit]
root@# set routing-options static route default next-hop
address
8. Configure the IP address and prefix length for the switch management interface.
[edit]
root@# set interfaces em0 unit 0 family inet address
address/prefix-length
NOTE: The management ports, em0 (C0) and em1 (C1), are located on the FRU end of
the QFX5110-48S.
9. (Optional) Configure the static routes to remote prefixes with access to the
management port.
[edit]
root@# set routing-options static route remote-prefix next-hop
destination-ip retain no-readvertise
10. Enable Telnet service.
[edit]
root@# set system services telnet
11. Enable SSH service.
[edit]
root@# set system services SSH
12. Commit the configuration to activate it on the switch.
[edit]
root@# commit
Safety Warnings Summary
This is a summary of safety warnings. For a complete list of warnings, including
translations, see the QFX5110 switch documentation at
http://www.juniper.net/techpubs/ .
WARNING: Failure to observe these safety warnings can result in personal injury
or death.
zPermit only trained and qualified personnel to install or replace switch components.
zPerform only the procedures described in this quick start and the QFX5110 switch
documentation. Other services must be performed only by authorized service
personnel.
zBefore installing the switch, read the planning instructions in the QFX5110 switch
documentation to make sure that the site meets power, environmental, and clearance
requirements for the switch.
zBefore connecting the switch to a power source, read the installation instructions in the
QFX5110 switch documentation.
zThe QFX5110-48S switch weighs approximately 23 lb (10.4 kg). Manually installing the
QFX5110-48S switch in a rack or cabinet at a height above 60 in. (152.4 cm) requires
two persons to lift the switch and install mounting screws. To prevent injury, keep your
back straight and lift with your legs, not your back.
zIf the rack or cabinet has stabilizing devices, install them in the rack before mounting or
servicing the switch in the rack or cabinet.
zBefore installing or after removing an electrical component, always place it
component-side up on a flat antistatic mat or in an antistatic bag.
zDo not work on the switch or connect or disconnect cables during electrical storms.
zBefore working on equipment that is connected to power lines, remove jewelry,
including rings, necklaces, and watches. Metal objects heat up when connected to
power and ground and can cause serious burns or become welded to the terminals.
CAUTION: Do not place a copper transceiver in an access port directly above or
below another copper transceiver. Damage to the access ports will occur.
Power Cable Warning (Japanese)
The attached power cable is only for
this product. Do not use this cable for
another product.
Contacting Juniper Networks
For technical support, see
http://www.juniper.net/support/requesting-support.html .
G

Other Juniper Switch manuals

Juniper EX Series User manual

Juniper

Juniper EX Series User manual

Juniper EX9208 Installation instructions

Juniper

Juniper EX9208 Installation instructions

Juniper QFX5220 Installation instructions

Juniper

Juniper QFX5220 Installation instructions

Juniper EX4100 Installation instructions

Juniper

Juniper EX4100 Installation instructions

Juniper Day One+ Installation instructions

Juniper

Juniper Day One+ Installation instructions

Juniper EX 3200 24T User manual

Juniper

Juniper EX 3200 24T User manual

Juniper EX3300 User manual

Juniper

Juniper EX3300 User manual

Juniper EX2300-24P User manual

Juniper

Juniper EX2300-24P User manual

Juniper EX Series User manual

Juniper

Juniper EX Series User manual

Juniper EX2200 Series User manual

Juniper

Juniper EX2200 Series User manual

Juniper EX4300 Installation instructions

Juniper

Juniper EX4300 Installation instructions

Juniper QFX5210 User manual

Juniper

Juniper QFX5210 User manual

Juniper QFX10008 User manual

Juniper

Juniper QFX10008 User manual

Juniper EX9251 Installation instructions

Juniper

Juniper EX9251 Installation instructions

Juniper EX 3200 User manual

Juniper

Juniper EX 3200 User manual

Juniper EX8208 User manual

Juniper

Juniper EX8208 User manual

Juniper EX3200 Series Quick start guide

Juniper

Juniper EX3200 Series Quick start guide

Juniper QFX10002 User manual

Juniper

Juniper QFX10002 User manual

Juniper EX2300 Series User manual

Juniper

Juniper EX2300 Series User manual

Juniper QFX5220-32CD User manual

Juniper

Juniper QFX5220-32CD User manual

Juniper EX Series User manual

Juniper

Juniper EX Series User manual

Juniper EX8208 User manual

Juniper

Juniper EX8208 User manual

Juniper QFX10016 User manual

Juniper

Juniper QFX10016 User manual

Juniper QFX5100 Installation instructions

Juniper

Juniper QFX5100 Installation instructions

Popular Switch manuals by other brands

BT Mini Hub Quick start quide

BT

BT Mini Hub Quick start quide

Edge-Core AS5916-54XKS quick start guide

Edge-Core

Edge-Core AS5916-54XKS quick start guide

Cisco Cisco Small Business Unmanaged Switch SD208 quick start guide

Cisco

Cisco Cisco Small Business Unmanaged Switch SD208 quick start guide

Philio PAN33 manual

Philio

Philio PAN33 manual

TANDBERG RJ45RJ11 Connecting

TANDBERG

TANDBERG RJ45RJ11 Connecting

ADDER AdderView Prism user guide

ADDER

ADDER AdderView Prism user guide

Flic Hub Mini user manual

Flic

Flic Hub Mini user manual

OSD NETWORKS OSD2254EP Operator's manual

OSD NETWORKS

OSD NETWORKS OSD2254EP Operator's manual

Gewiss RESTART RD 90 Series manual

Gewiss

Gewiss RESTART RD 90 Series manual

Cedrat Technologies CSA96 Instruction

Cedrat Technologies

Cedrat Technologies CSA96 Instruction

Sangamo CHOICE PR2 installation instructions

Sangamo

Sangamo CHOICE PR2 installation instructions

PKP FS13 instruction manual

PKP

PKP FS13 instruction manual

LQ GROUP 1145616-00000 instruction manual

LQ GROUP

LQ GROUP 1145616-00000 instruction manual

Cisco Linksys SGE2010 datasheet

Cisco

Cisco Linksys SGE2010 datasheet

Siemens 3KF2 F5 3KF3 F5 Series operating instructions

Siemens

Siemens 3KF2 F5 3KF3 F5 Series operating instructions

Cypress CDVI-31 Operation manual

Cypress

Cypress CDVI-31 Operation manual

Siemens SITRANS LPS200 operating instructions

Siemens

Siemens SITRANS LPS200 operating instructions

BABBITT LS7500 owner's manual

BABBITT

BABBITT LS7500 owner's manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.