4
Pulse output – Passive (STANDARD) 66-99-607
PULSE DIVIDER – Passive
ype: Open collector. 2- or 3-wire connection via the integrated
pull-up resistance of 33 k
Ω
Cable length,
flow meter: Max. 10 m
Cable length,
PULSE DIVIDER: Dependent on the calculator
Pulse length: 100 ms (standard)
Interval between
pulses: Dependent on the actual pulse frequency
2-wire connection: Voltage range 3...6 VDC
Max. leak current 1
µ A
Min. R
load
30 k
Ω
Max. R
load
1 M
Ω
3-wire connection: Supply (9A) 3...10 VDC
l
max
0.2 mA
Pulse output – Active (re-configured) 66-99-606
he PULSE DIVIDER can be re-configured to an active output.
Supplies from
the PULSE
DIVIDER (9A)
and calculator
must not
be coupled
together
ype: Active
Cable length, flow
meter for calculator: Max. 10 m
Pulse length: 100 ms (standard)
Intervals between pulses: Dependent on the actual pulse
frequency
Voltage V
OH
: 3.6 V ± 0.1 V