
KBR multimess D6
V5.00
EDEBDA0224-3823-1_EN
10
Application/range of functions
4 Field of application/range of functions
multimess D6 is a compact, easy-to-use energy meter that records active as well
as reactive energy (for consumption and recovery).
This energy counting device was designed in accordance with the standards
DIN EN 61036 (IEC 1036), DIN EN 61268 (IEC 1268) and requirement specica-
tion 2.0 revision 12/97 by the German Electricity Association (VDEW).
Dual-tari counter function (HT/LT)
Consumption during high tari and low tari times is saved separately. Switch-
ing from high to low tari times and vice versa is either carried out by means of
a digital signal to be applied externally, e.g. from the energy supplier, or via an
internal clock. A display ashing on the front of the device indicates which tari
is active at the moment. When operated with the KBR Energy Bus, switching can
also be carried out centrally via the Multimaster or computer.
Convenient operation and display
The LCD serves to either display the measured values directly or enter the re-
spective parameters and conguration data. In addition, six LEDs serve to show
the status and monitor the functions. Four buttons facilitate clearly structured
navigation through the menus.
For 100 to 400 V networks
The multimess D6 can be applied in three-wire as well as four-wire networks.
If the measuring value displays in the three-wire network are incorrect, a ze-
ro-point creator should be used. The unit can be implemented in 100 V as well
as in 400 V networks for direct measurement. Using a transducer adaptor, up to
700 V can be connected to the meter. Higher voltages can only be connected
via external voltage transformers, whereby primary and secondary voltage can
be freely programmed. The measuring voltage inputs of the device measure
directly, i.e. they are not metallically separated by a voltage transformer!
For energy supply networks with outer conductor connected to the earth po-
tential, suitable control gear with electrical isolation (e.g. voltage transformer)
must be used.
x/5A or x/1A freely programmable
The measuring inputs for current must always be fed via current transformers,
while the transformer ratio is programmable. The primary current value as well
as the secondary current value can be selected.
Programmable pulse output
Active energy or reactive energy proportional pulses can be output via a
programmable output laid out as an S0interface. The pulse output type (in
proportion to active or reactive energy