Kitchen Brains Modularm 75LC Troubleshooting guide

®
Kitchen Brains © 2014 | www.KitchenBrains.com | 229-40072 D Page 1 of 12
This document contains confidential information. The dissemination, publication, copying, or duplication of this document or the software described herein without prior written authorization is strictly prohibited.
24/7 Toll-Free Technical Support
1-800-243-9271
(from the U.S., Canada and the Caribbean)
Save the instructions
for future reference.
www.KitchenBrains.com
INSTALLATION &
OPERATING GUIDE
MODULARM 75LC Multi-Monitor

Kitchen Brains © 2014 | www.KitchenBrains.com | 229-40072 D
This document contains confidential information. The dissemination, publication, copying, or duplication of this document or the software described herein without prior written authorization is strictly prohibited.
Page 2 of 12
MODULARM 75LC Multi-Monitor Installation & Operating
NOTICES
Before you start, please read these instructions
thoroughly in order to obtain maximum benefit from
the capabilities that this product offers.
Thank you for purchasing the 75LC multi-monitor. The 75LC
integrates sophisticated function with easy operation.
Patented Autoset*Technology, combined with common
pre-programmed default settings eliminates the need for
manual programming in most applications. PAS-PRO™
password programming allows for easy and secure custom
configuration. All product functions and accessories may be
used simultaneously or you may use only those required for
your application. A simple, 3 button user interface combined
with prioritized intuitive visual alarm display makes the 75LC
extremely user friendly.
OVERVIEW
75LC FUNCTIONS:
The 75LC offers the following functions: (Patented
Operation, other Patents Pending.)
1. HI & LO Temperature Alarm with Patented Autoset
Technology.
2. AC Failure Alarm with built-in rechargeable battery
and built in recharging circuitry.
3. Door Ajar Alarm. (Requires magnetic contacts. See
pg. 3)
4. Panic (Entrapment) Alarm (Requires optional IP-1
Illuminated Button See pg. 3)
5. Manual and patented timed light control.
6. HACCP monitoring. (additional equipment required)
7. Remote notification. (additional equipment required)
8. Built in audible alarm.
*What is Autoset?
Patented Autoset Technology selects the right alarm temp
setpoints for monitoring a cooler or a freezer automatically,
virtually eliminating the need for manual programming.
Common cooler and freezer setpoints are pre-loaded into
the 75LC. Autoset Setpoints are:
COOLER FREEZER
HI 42F (6C) HI 10F (-12C)
LO 30F (-1C) LO -20F (-29C)
Cooler setpoints are the default settings, used for cooler
monitoring. If the compartment is a freezer, Autoset
detects the lower compartment temperature and
automatically changes to the freezer setpoints. (Freezer
defaults won’t revert to cooler defaults if temperature rises.
Cooler defaults can be easily manually restored when
necessary.) Manually changing setpoints in the program
menu automatically disables Autoset.
THREE BUTTON USER INTERFACE:
Test (Up):
Lights (Prog):
Silence (Down):
WHILE IN RUN OR ALARM MODE
Test: Press to test and to view alarm
parameter settings.
Lights: Press to manually activate and
deactivate compartment
Silence: Press to acknowledge an
alarm.
WHILE IN PROGRAM MODE
Up: Press to increase and alarm
parameter values.
Lights: Press to select PAS-PRO™
preset and program menu options.
Down: Press to decrease alarm
parameter values.
VISUAL ALARM ANNUNCIATION:
NOTE the following:
1. During normal operation the monitored temp
displays constantly.
2. Any abnormal or alarm condition (except Panic
Alarm) alternates between monitored condition
display and monitored temp as follows: (In order
of priority.)
ALARM TYPE ABNORMAL
CONDITION
ALARM
CONDITION
PANIC ALARM [Non applicable] “HLP” + “HLP”
DOOR AJAR Door Light On “Dor” +
Temperature
TEMP OUT OF
RANGE
“HI” or “LO” +
Temperature
“HI” or “LO”
+ “AL” +
Temperature
AC POWER
FAILURE
“PF” +
Temperature
A single dot will
display
Panic Alarm Operation: Two types of Panic Alarm are
available:
• Manual Panic Alarm – (Requires optional IP-1).
The alarm can be cleared by either pressing the
Silence button on the 75LC or by opening and
closing the door. (This requires door contacts).
• Auto Panic Alarm – (Requires magnetic contacts,
and either or both of the following IP-1 & MD -1).
Auto Panic offers protection for persons who may
be hurt or disabled and cannot activate a Manual
Panic Alarm.

Kitchen Brains © 2014 | www.KitchenBrains.com | 229-40072 D
This document contains confidential information. The dissemination, publication, copying, or duplication of this document or the software described herein without prior written authorization is strictly prohibited.
Page 3 of 12
MODULARM 75LC Multi-Monitor Installation & Operating
Using AutoPanic with an IP-1:
• If Autopanic is enabled, pressing the IP-1 at
any time while the door is closed starts the 20
minute Auto Panic Timer. When the Auto Panic
timer runs out, the IP-1 starts to beep and blink
for 40 seconds. Repressing IP-1 during a beep
and blink resets the Auto Panic Timer for 20
minutes.
• If not pressed, A Panic Alarm (HLP) automatically
annunciates on the 75LC to let others know that
someone may be injured or disabled inside the
walk-in. Auto Panic Alarm is cleared in the same
way as a Manual Panic Alarm.
Using AutoPanic with an MD-1:
• The MD-1 makes Autopanic easier to use. Each
time motion is detected, the MD-1 restarts the 20
minute Auto Panic Timer. If no motion is detected
for 20 minutes the IP-1 (if present) starts to beep
and blink for 40 seconds.
• If no motion is detected a Panic Alarm (HLP)
automatically annunciates on the 75LC to let
others know that someone may be injured or
disable inside the walk-in. Auto Panic Alarm is
cleared the same way as a Manual Panic Alarm.
AC Power Failure Operation:
• When power failure occurs: The 75LC will
alternate PF and the Monitored temperature
for 1 minute as shown above under “Abnormal
Condition”.
• For power failures under 1 minute: Normal
operation restores automatically and the incident
is ignored.
• For power failures beyond 1 minute: The
Alarm relay activates, and the horn will chirp
intermittently with a blinking decimal point.
Pressing Silence at any time during a power
failure silences the horn for 1 minute, and briefly
displays the monitored condition.
ACCESSORIES:
Three accessories expand 75LC operation:
1. IP-1 Illuminated Push Button
2. MD-1 Motion Detector
3. MC-1 Magnetic Contacts.
These accessories are low voltage devices, connected
directly to and powered by the 75LC. Accessories may
be used individually or in combination. To help eliminate
programming when common settings are desired, the 75LC
comes equipped with Autodetect.
What is Autodetect?
The Autodetect function in the 75LC senses if and when
an accessory is connected to the 75LC and automatically
integrates the connected accessory into device
operation. No special programming is required. The 75LC
ships with Autodetect enabled for the accessory inputs.
(Ex: If magnetic contacts are not connected, the 75LC
operates as if there are no magnetic contacts. Once
magnetic contacts are connected, Autodetect senses this
and automatically provides door ajar alarm function and
automatic lights on function when the door is open.)
Accessories Information:
• IP-1 Illuminated Push Button – The low voltage
IP-1 mounts inside of the walk-in and provides
both a lights control switch and a panic alarm
switch. (Press to control lights, press and hold
for 2 seconds to activate Panic Alarm “HLP”).
A buzzer and lights built into the IP-1 provide
warning to personnel in the walk-in that lights
may turn off if the IP-1 isn’t pressed.
• MD-1 Motion Detector – (Not recommended
for freezers) The low voltage MD-1 mounts
inside of the walk-in and duplicates the light ON
control function of the IP-1 button when activated
by movement of personnel inside of the walk-in.
• MC-1 Magnetic Contacts – Low voltage
magnetic contacts sense door status and
provide both a door ajar alarm switch and a
lights on switch relative to the status of the
door. One set of magnetic contacts come with
each 75LC, various styles are available.
OPERATION
LIGHT CONTROL OPERATION: The 75LC offers three ways
to control lights:
1. Regular timed lighting
2. Patented timed lighting with Auto Panic (default),
3. Untimed, manual on-off light control (replaces light
switches.)
Password selectable presets are used to easily change or
select the desired mode of operation for your configuration
(See pg. 6)
NOTE: The DOOR light blinks whenever lights are on.
1. Regular Timed Lighting Operation – When lights
turn on, the lights-off timer is activated. Lights will
turn off when the lights-off timer expires. Operation
is as follows:
• Without Accessories: Press the Lights Button
on the 75LC to turn lights on and start lights-off

Kitchen Brains © 2014 | www.KitchenBrains.com | 229-40072 D
This document contains confidential information. The dissemination, publication, copying, or duplication of this document or the software described herein without prior written authorization is strictly prohibited.
Page 4 of 12
MODULARM 75LC Multi-Monitor Installation & Operating
timer. Press the Lights Button again to manually
turn lights off before the lights-off timer expires.
• With IP-1 installed: Press Lights Button or IP-1
to turn lights on and start lights off timer. Press
Lights Button or IP-1 Switch again to manually
turn lights off before the lights-off timer expires.
The IP-1 blinks and beeps for 40 seconds before
lights-off timer expires to warn personnel that
lights will be turning off. Pressing the IP-1 when it
is blinking/beeping resets the lights-off timer and
keeps lights on. If no action is taken the lights will
turn off when lights-off timer expires.
• With Magnetic Contacts installed: Open the
door to turn lights on. 75LC light button and
installed IP-1 will turn lights on & off with
door open. Once the door is closed the lights-off
timer will begin.
• With MD-1 motion detector installed: (Coolers
only) Activation of the MD-1 by movement of
personnel inside the walk-in turns lights on. When
personnel are no longer detected inside the walk-
in the lights turn off.
Any combination of accessories may be used.
Accessories operate together as described
individually.
2. Patented Timed Lighting with Auto Panic (Default) –
(Magnetic contacts required. IP-1 and/or MD-1
required in a cooler. IP-1 required in a freezer.)
Operation is as follows:
When the door opens, Lights turn on.Press the
75LC light button or installed IP-1 to turn
lights on & off while door is open. When the
Door is closed the Lights-off timer starts and the
IP-1 starts to beep and blink to prompt a button
press.
Pressing the IP-1 does the following:
1. Stops the lights-off timer and makes lights
stay on indefinitely for as long as the door
remains closed.
2. Starts a built-in 20 minute Auto Panic timer.
3. “Locks out” Light Switch on 75LC so that
someone outside of walk-in can’t turn off
lights while the box is occupied.
4. After 20 minutes, IP-1 starts to beep and blink
again for 40 seconds to prompt a “check in”
button press. Pressing the IP-1 resets and
restarts Auto Panic timer. This repeats for as
long as someone remains in the box with the
door closed. If IP-1 isn’t pressed within 40
seconds, the 75LC automatically generates
a panic alarm, “HLP” appears on the 75LC
display to let personnel outside the box know
that someone may be injured or disabled
inside of the walk-in.
5. Opening and closing door resets all functions.
If no one is in the box to press the IP-1 after
door is closed, lights turn off when lights-off
timer expires.
NOTE 1: With both Magnetic contacts and IP-1
installed, IP-1 is a Lights ON only switch when the
door is closed, and is a Lights ON/OFF switch when
the door is open.
NOTE 2: With the door closed, the IP-1 blinks and beeps
initially for 40 seconds and again for 40 seconds before
the lights-off timer expires. Pressing the IP-1 at any
time always activates the 20 minute Auto Panic timer.
NOTE 3: If door is closed and lights are off, the IP-1
always works as a “lights on” switch inside of the
walk-in and always activates the 20 minute Auto Panic
timer when pressed.
NOTE 4: In coolers, The MD-1 motion detector may
be used instead of or in addition to the IP-1. MD-1
activation duplicates an IP-1 press and automates the
process.
3. Untimed Manual On-Off Light Control – Replaces
standard light switches. Operation is as follows:
• Without accessories – Press lights button on
75LC to turn lights on. Press again to turn lights off.
• With IP-1 installed – IP-1 is a “lights ON/OFF”
switch inside of the walk-in. (Plus Manual
Panic Alarm)
• With Magnetic Contacts installed – Lights turn
on when the door is open. (Plus Door Ajar Alarm)
• With MD-1 installed – (Coolers only): Activation
of MD-1 by movement of personnel in walk-in
turns on lights.
Any combination of accessories may be used.
Accessories operate together as described
individually.
NOTE: Manual ON-OFF Light Control with Auto Panic is
a password selectable option. (See table, pg. 6).
ALARM OPERATION:
The 75LC has four modes of operation: Sleep, Run,Test,
and Program.
Sleep Mode: The 75LC ships from the factory in
Sleep Mode. (The rechargeable battery is connected
physically but is not connected electrically until AC
power is applied.) To restore Sleep Mode if the alarm
has been powered up:

Kitchen Brains © 2014 | www.KitchenBrains.com | 229-40072 D
This document contains confidential information. The dissemination, publication, copying, or duplication of this document or the software described herein without prior written authorization is strictly prohibited.
Page 5 of 12
MODULARM 75LC Multi-Monitor Installation & Operating
1. Disconnect from AC power. Press and hold
Lights (Prog) button for 3 seconds. Display reads
“con” (confirm).
2. Press Test (Up). Display reads “bye”, all
functions shut off and the alarm goes into Sleep
Mode. (Ready to ship.)
3. The battery automatically reconnects electrically
the next time AC Power is applied.
Run Mode: All 75LC monitoring functions take place in
Run Mode
Note the following:
1. You must press Silence to clear a Temp Alarm or
a Power Failure alarm even if the condition has
corrected itself! This informs the operator if
these alarm conditions happened, even if no
one was present during the alarm.
2. If door is being monitored, close the door to clear
a door ajar alarm.
3. Open and close the door or press Silence to clear
a Panic Alarm.
Test Mode: Press Test to perform simple test
procedures and to view alarm parameter settings. The
following occurs:
1. All visual indicators light. (LEDS)
2. Software version rE (revision) is displayed.
3. Program Menu parameters and settings are
sequentially displayed. (See Parameter List
below)
4. Horn sounds and alarm relay activates.
5. Pressing Silence at any time during the Test
procedure restores Run Mode (normal operation)
6. Run Mode is automatically restored 10 seconds
after Test is complete if Silence isn’t pressed.
Program Mode: Use PAS-PRO™password
programming to select or customize a factory preset
mode of operation (See pg. 6). The 10 available program
parameters with symbols and ranges are:
PARAMETER LIST
Password PARAMETER SYMBOL RANGE
50 Scale SCL F or C
51 Probe Calibration (1) Prb + CAL -5 to +5
52 HI Alarm Temp Setpt HI + ALr -40F to 125F
53 LO Alarm Temp Setpt LO +ALr -40F to 125F
54 Temp Alarm Delay Alr + dLy 0 to 150 Min.
55 Door Ajar Delay dor + dLy 0 to 60 Min.
56 Ringback Delay (2) rng + dLy 0 to 60 Min.
57 Lights Off Delay (3) LtS + dLy 0 to 150 Min.
58 Lights Operation (4) LtS + OPr Aut or tL
59 Alarm Relay (5) Alr + rLy Unlatch (UnL)
or Latch (LCH)
1. Probe Calibration – The 75LC comes pre-
calibrated to read proper temperature with
Automatic Scale Conversion from F to C. CAL
parameter provides a means for offsetting the
displayed temperature by +/-5 if so desired.
(NOTE: CAL offset doesn’t offset setpoints.)
2. Ringback Delay – Ringback provides a way to
generate timed repeat audible alarms during an
ongoing temperature alarm or power failure alarm
condition. Select the time interval you wish for
this to occur.
3. Lights Off Delay- The lights will turn off in the
indicated number of minutes. If the Lights Off
Delay is not to be used, increase the delay past
150 minutes and the time delay reads TOG for
Toggle.
4. Lights Operation – “Aut” operation provides
Timed Lighting with Auto panic (See pg. 3). “tL”
operation provides regular timed lighting (See pg. 3).
5. Alarm Relay – Normally Open (N/O) and Normally
Closed (N/C) dry contacts are provided. The two
relay modes are:
a. Unlatched (UnL) – Default Setting. Relay
activates when alarm occurs and deactivates
when Silence is pressed. Typical Application:
Controlling a remote buzzer or light.
b. Latched (Lch) – Relay activates when alarm
occurs and deactivates when both alarm
condition has cleared and Silence has been
pressed. Typical Application: Connection to
a building management system where relay
remains activated until alarm condition clears
and is acknowledged.

Kitchen Brains © 2014 | www.KitchenBrains.com | 229-40072 D
This document contains confidential information. The dissemination, publication, copying, or duplication of this document or the software described herein without prior written authorization is strictly prohibited.
Page 6 of 12
MODULARM 75LC Multi-Monitor Installation & Operating
PAS-PRO™PASSWORD PROGRAMMING
INSTRUCTIONS
STEP ONE: Use Operation passwords [20 →29] to choose desired
light control operation in either ºF or ºC scale. (Default
Password is “20”)
STEP TWO: If desired, use Parameter passwords [50 →59] to
customize your selected operation.
Using PAS-PRO™To select an OPERATION PASSWORD [20 →29]:
1. While pressing and holding Silence, press Test . Display reads “???”,
then “0”.
2. Press and hold Test (Up) to scroll to the desired operation password.
Silence (Down) may be used to lower the number if you overshoot.
3. Press Lights (Prog). Display reads “Set”, then the password of the
selected operation.
4. 75LC returns to Run Mode, operating in accordance with selected
operation password.
Using PAS-PRO™To select a parameter password [50 →59]:
(See passwords and corresponding program menu parameters in tables
above and on previous page.)
NOTE: Parameter passwords “50” thru “59” are “entry points” into the
programming menu. The programming menu is an “endless loop” and
the entire menu can be accessed from any entry point.
1. While pressing and holding Silence, press Test. Display
reads “???”, then “0”.
2. Press Test (Up) to scroll to the password for the desired
parameter you wish to change. Silence (Down) may be used
to lower the number if you overshoot.
3. Press Lights (Prog). Display reads “Prg”, then the selected
parameter symbol, then the present parameter setting.
(Example: HI SETPT SYMBOL = “HI” + “ALr”, default setting
= “42º”).
4. Use the Test (Up) switch or the Silence (Down) to change
parameter setting if necessary.
5. Once the desired parameter setting is selected, momentarily
press Lights (Prog) to advance to the next parameter and
continue in the same manner for each setting you wish to
change.
6. Exit from Program Mode occurs automatically if no
buttons are pressed for 5 seconds. (Display reads “SEt”,
75LC returns to Run Mode, operating in accordance
with new settings.)To manually exit, HOLD Lights
(Prog) Switch for 2 seconds until Display reads “SEt”.
(75LC returns to run mode, operating in accordance
with new settings.) It is not necessary to complete the
menu to change selected parameters. ANY CHANGES
MADE PRIOR TO EXITING WILL BE STORED AS NEW
OPERATING PARAMETERS! If desired, once programming
is complete, press “TEST” switch to verify new parameter
settings.
SEE PAGE 4 FOR PUTTING ALARM TO SLEEP FOR SHIPPING.

Kitchen Brains © 2014 | www.KitchenBrains.com | 229-40072 D
This document contains confidential information. The dissemination, publication, copying, or duplication of this document or the software described herein without prior written authorization is strictly prohibited.
Page 7 of 12
MODULARM 75LC Multi-Monitor Installation & Operating
INSTALLATION
GENERAL SAFETY MEASURES AND PRODUCT LIMITATIONS
• This product (“Product”) must be installed by a licensed electrician experienced in working in the types of environments for which this
Product is intended to be utilized; specifically, commercial walk-in coolers and freezers (“Equipment”).
• Personnel installing the Product must carefully and completely read the Operating and Installation Instructions (“Instructions”), and
instructions and specifications of the Equipment manufacturers, before attempting to operate and install the Product. Failure to comply
with the Instructions, and the instructions and specifications of the Equipment manufacturers, may result in personal injury and/or
property damage and may void the warranty of the Product. Retain the Instructions for future reference.
• The Product shall only be used for the purposes described in the Instructions.
• During installation of the Product, all applicable laws, regulations and industry rules, including local electrical and safety codes, the
National Electric Code (NEC) and the Occupational Safety and Health Act (OSHA), must be strictly followed. Consistent therewith,
follow applicable electrical codes regarding running of low voltage wiring and high voltage wiring in separate conduits and use
appropriately rated wire (insulation type, voltage rating and wire gauge) for all connections. Supply connection wiring must be rated at
least 90°C. Use copper conductors only.
• The enclosure used for mounting the Product must be properly grounded according to electrical code.
• Confirm that the power source conforms to the requirements of the Product before connecting.
• Do not exceed the rated limits of the Product. Refer to the Product specifications for suitability of the Product to the application.
• The Product is not suitable for use in wet locations. Do not expose the Product to water, moisture or condensation. In no event should
the Product be exposed to environments where sudden temperature changes with high humidity may result in the formation of
condensation.
• Any openings in the walls, ceiling or floor of the Equipment for wiring or other reason must be sealed (made airtight and
watertight) with appropriate materials (e.g., silicone, caulk or foam), both on the outside and inside of the Equipment, to
prevent moisture or condensation from entering the compartment of the Equipment and forming and accumulating on the
interior walls of the compartment and the contents of the compartment, including the Product. Failure to properly seal such
openings may (i) result in damage to the Equipment and contents of the compartment (ii) pose a safety hazard and (iii) void
the warranty of the Product.
• To prevent moisture or condensation from entering or forming in the enclosure used for the Product, any openings in this
enclosure (for wiring access or other purpose) must be appropriately sealed with materials such as silicone, caulk or foam.
• Installation of the Product should be inspected and the Product tested by qualified personnel to ensure the Product performs safely
and in accordance with the Product specifications. Periodic testing of the Product should be performed on an ongoing basis (at least
quarterly) to ensure the Product continues to perform properly.
• All personnel operating, maintaining, repairing or interfacing with the Product must be instructed in the use of the Product and provided
with the Instructions. The Instructions must be kept in an accessible location for easy reference.
• WARNING: Hazard of electric shock! Power sources must be turned off or otherwise disconnected prior to installation or servicing of
the Product. Lock and tag power disconnects to prevent an unexpected application of power.
Mounting the enclosure for the 75LC:
Any enclosure used for 75LC mounting must provide
multiple wire access hubs for running line voltage wiring
and low voltage wiring in separate conduits. Determine the
wire access hubs to be utilized for the installation and plug
and seal any remaining unused openings with hardware
and/or sealant. The 75LC will fit into a typical outdoor, single
gang outlet box.
Surface Mount – A typical outdoor, single gang outlet box
may be used for surface mounting. Mount the enclosure
vertically onto the desired surface. If fastening the
enclosure with screws directly through the back wall of the
enclosure, use two screws, centered vertically above and
below the opening in the rear of the enclosure.
Flush Mount – (See flush mount cutout template, pg 9).
Make the cutout and the mounting holes into the
compartment door frame or compartment wall as shown
on the cutout template. Once the cutout and mounting
holes have been made, screws in the mounting holes may
be used to hold the selected enclosure in place during the
foaming process.
Mounting the IP-1:
The IP-1 may be flush mounted into a standard J-Box. A
typical outdoor type single gang outlet box may be used for
surface mounting. (NOTE: The IP-1 is a low voltage device.
Wiring to the IP-1 must not be installed in the same conduit
as line voltage wiring. An 8’ length of color coded wiring for
connecting the IP-1 is provided.) Typical mounting location
for the IP-1 is inside of the walk-in adjacent to the door. Any
wire pathways or other openings leading into the enclosure

Kitchen Brains © 2014 | www.KitchenBrains.com | 229-40072 D
This document contains confidential information. The dissemination, publication, copying, or duplication of this document or the software described herein without prior written authorization is strictly prohibited.
Page 8 of 12
MODULARM 75LC Multi-Monitor Installation & Operating
for the IP-1 from outside of the walk-in must be sealed both
on the outside and on the inside of the walk-in to prevent a
pathway for condensation.
Mounting the MD-1:
(Install in Coolers only). The MD-1 may be flush mounted
into a standard J-Box rotated 90°. A typical outdoor type
single gang outlet box may be used for surface mounting.
(NOTE: The MD-1 is a low voltage device. Wiring to the
MD-1 must not be installed in the same conduit as line
voltage wiring. A 6’ length of color coded installation wiring
is pre-connected to the MD-1). Typical mounting location for
the MD-1 is inside of the walk-in above the door. There is no
need to open or access the motion detector itself. Mount
the MD-1 horizontally with the white oval lens facing down.
The red light inside of the MD-1 will illuminate whenever
the MD-1 is activated.
WIRING: See Wiring Diagrams, page 10 & 11. Keep wiring
relatively short inside of the enclosure for the 75LC. Make
sure that wiring openings into all enclosures are sealed
properly to prevent a pathway for condensation.
Line Voltage Wiring:
The line voltage terminal block will accept up to 12AWG
wire. Wire the 3 line voltage connections in accordance
with the accompanying 75LC Connections diagram.
Connections are also marked on the 75LC.The stripped
end of the line voltage wire connections should be kept
short, approximately ¼” long. Insert the wire ends into
the appropriate terminal block openings and tighten the
screws securely to clamp the wires into place. With
stranded wire, make sure that all strands are captured
in the terminal block openings. Tug on wire to make
sure connections are secure. MAKE SURE THE SCREWS
ARE TIGHT! Supply connection wiring must be rated at
least 90°C. Use copper conductors only. Make sure that
the green wire from the 75LC faceplate is properly
grounded. If a metal enclosure is used for mounting
the 75LC, make sure that the enclosure is also properly
grounded.
Low Voltage Wiring:
The low voltage terminal blocks will accept wire from
24-16AWG. Accessories and sensors are typically provided
with 24-22AWG wire. General Accessories and sensor
connections are shown on the accompanying 75LC
Connections diagram. Connections are also marked on
the 75LC. See the diagrams labeled “IP-1 Connections”,
“MD-1 Connections”, and “IP-1 & MD-1 Connections”
for wiring specific to your application. The stripped end of
the low voltage wire connections should be kept short,
approximately ¼” long. To connect wires, press down on
the respective plunger on the top of the terminal block,
insert the wire into the respective hole and release the
plunger. Tug on wires to make sure connections are
secure and that they are grabbing bare wire and not
insulation. (NOTE: If the IP-1 and the MD-1 are both being
used, use the enclosure for the IP-1 as a junction box for
connecting the MD-1 in accordance with the “IP-1 & MD-1
Connections” diagram. Connect the green wires together
in the IP-1 enclosure with a wire nut or other connector.
Strip the 2 black wires approximately 3/8”, twist together
and insert both into the IP-1 block in accordance with the
diagram. Do the same with the two red wires. Again, tug
gently on all wires to make sure connections are secure.)
Temperature Probe Mounting:
Run the probe into the monitored compartment and locate
the sensor in a spot which will typify the average ambient
temperature. Recommended location is in the center of
the ceiling. Fasten the sensor with the provided clamp.
Make sure sensor and sensor wire are positioned and/or
protected so as not to be damaged by products or items
in the monitored area. (Seal any openings made for
passage of the probe wire into the walk-in on the inside
and the outside of the walk-in to prevent a pathway for
condensation.)
Magnetic Contacts Mounting:
Mounting method will vary depending on the type of
contacts utilized. Make sure that the operating gap
between the magnet part and the switch part of the
contacts accurately detects a door open or a door closed
condition. (The DOOR light is on constantly when the door
is open. This light may be utilized to assist in proper switch
and magnet placement.) NOTE: For compartments with
more than one door, multiple sets of contacts, wired in
series, may be utilized to monitor multiple door’s status.
Mounting the 75LC onto the enclosure:
Mount the 75LC onto the enclosure with the provided
mounting screws. If the 75LC is mounted onto an outdoor
type single gang outlet box, route all wiring away from the
battery when the 75LC is inserted. Inspect the installation
for compliance with electrical code, safety, sealing
against moisture and condensation, and test to confirm
that the Product and installation are operating properly
in accordance with these instructions. Periodic testing is
recommended to ensure continued proper operation.
Locking the keypad:
Enter programming menu, select password “10” and press
Lights (Prog) switch. Display reads “Set” then returns to run
mode. The keypad is locked. To unlock, proceed as above
using password “105”. The keypad is unlocked.
Resetting the 75LC to factory defaults:
Enter programming menu, select password “20” and press
LIGHTS Button. Display reads “Set” then returns to run
mode. The 75LC is now in factory mode.

3 1/4"
2 7/8"
2 1/2"
FLUSH MOUNT
CUTOUT TEMPLATE
1 5/8"
1 1/4"
EXPANSION
PORT
TX RX SHLD
DRY
CONTACTS
1A@120VAC
C NC NO
SUPPLY
POWER
120 VAC
LIGHTS
8.3A@120VAC
1000W
NEUTRAL
LINE
LIGHTS
N/C
CONTACTS
TEMP.
PROBE
MD-1
MOTION
DECTECTOR IP-1
PUSH
BUTTON
9V,NI-MH
RECHARGEABLE
BATTERY
MAGNETIC
IMPORTANT!!
MOUNT THE 75LC
ENCLOSURE WITH THE
GROUND LUG TO THE LEFT
SO THAT THE BATTERY
GROUND LUG WHEN THE
ALARM IS INSTALLED
GROUND
LUG TO
LEFT!!
75LC ENCLOSURE POSITION
DOES NOT CONTACT THE
(WHITE)*
(BLACK)*
(RED)*
*COLORS INDICATED ARE TYPICAL
75LC TERMINAL
BLOCK
LINE VOLTAGE CONNECTIONS
75LC CONNECTIONS
CONNECT THE GROUND WIRE
TO GROUND LUG BEFORE
INSERTING 75LC
Kitchen Brains © 2014 | www.KitchenBrains.com | 229-40072 D
This document contains confidential information. The dissemination, publication, copying, or duplication of this document or the software described herein without prior written authorization is strictly prohibited.
Page 9 of 12
MODULARM 75LC Multi-Monitor Installation & Operating
FLUSH MOUNT CUTOUT TEMPLATE

EXPANSION
PORT
TX RX SHLD
DRY
CONTACTS
C NC NO SUPPLY
POWER
120 VAC
LIGHTS
NEUTRAL
LINE
LIGHTS
N/C
CONTACTS
TEMP. PROBE
MD-1
MOTION
DECTECTOR
IP-1
PUSH
BUTTON
9V,NI-MH
RECHARGEABLE
BATTERY
MAGNETIC
(WHITE)*
(BLACK)*
(RED)*
*COLORS INDICATED ARE TYPICAL
BLOCK
LINE VOLTAGE CONNECTIONS
MODULARM 75LC WIRING DIAGRAM Rev 2
TEMP B R Y DOOR
MD W
G
B
R
(GREEN)
B
W
R
Y
1000W
8.3A@120VAC
*75LC MUST
BE GROUNDED
GREEN WIRE
75LC TERMINAL
75LC
FROM
BACK
PR
REVISION 2
REVISION 3
EXPANSION
PORT
TX RX SHLD
DRY
CONTACTS
C NC NO
SUPPLY
POWER
120 VAC
LIGHTS
LIGHTS
NEUTRAL
LINE
N/C
CONTACTS
TEMP. PROBE
MD-1
MOTION
DECTECTOR
IP-1
PUSH
BUTTON
9V,NI-MH
RECHARGEABLE
BATTERY
MAGNETIC
BW R Y
BW R Y
BW R Y
MD-1
CONNECTION
B=BLACK
R=RED
G=GREEN
LOW
VOLTAGE!!
IP-1
CONNECTION
B=BLACK
R=RED
LOW
VOLTAGE!!
W=WHITE
Y=YELLOW
IP-1
TERMINAL
BLOCK
BW RY
BW R Y
IP-1 / MD-1
CONNECTION
B=BLACK
R=RED
LOW
VOLTAGE!!
W=WHITE
Y=YELLOW
MD-1
MOTION
DETECTOR
G=GREEN
USE IP-1 ENCLOSURE
AS A JUNCTION BOX
FOR CONNECTING MD-1
WIRE NUT OR OTHER
APPROPRIATE SPLICING
75LC TERMINAL
BLOCK
DOOR
TEMP MD
TEMP DOOR
TEMP DOOR
(RED)*
(WHITE)*
(BLACK)*
*COLORS INDICATED ARE TYPICAL
BLOCK
LINE VOLTAGE CONNECTIONS
MODULARM 75LC WIRING DIAGRAM Rev 3
IP-1 CONNECTIONS
MD-1 CONNECTIONS
IP-1 & MD-1 CONNECTIONS
TEMP B R Y DOORMD W
G
B
R
(GREEN)
B
W
R
Y
1000W
8.3A@120VAC
MD
MD
GB R
METHOD
IP-1 ENCLOSURE
(GREEN)
GB R
(GREEN)
MD-1
MOTION
DETECTOR
IP-1
TERMINAL
BLOCK
75LC TERMINAL
BLOCK
75LC TERMINAL
BLOCK
*75LC MUST
BE GROUNDED
GREEN WIRE
75LC TERMINAL
75LC
FROM
BACK
PR
SALES@KITCHENBRAINS.COM
MODULARM
WWW.KITCHENBRAINS.COM
SALES@KITCHENBRAINS.COM
MODULARM
WWW.KITCHENBRAINS.COM
PLEASE FOLLOW THE
WIRE PLACEMENT AS
BOARD LABELS
INDICATED BY THE
BOARD LABELS
PLEASE FOLLOW THE
WIRE PLACEMENT AS
INDICATED BY THE
PLEASE FOLLOW THE
WIRE PLACEMENT AS
BOARD LABELS
INDICATED BY THE
PLEASE FOLLOW THE
WIRE PLACEMENT AS
BOARD LABELS
INDICATED BY THE
MD-1
MAGNETIC
CONTACT (MC-1)
TMP
MD
BWRY DOOR
TEMP
SENSOR
GREEN
B
W
R
Y
B
W
R
Y
75LC # 1 CONNECTIONS
DOOR # 1
ILLUMINATED PUSHBUTTON
DOOR # 2
DOOR # 3
MAGNETIC
CONTACT (MC-1)
MAGNETIC
CONTACT (MC-1)
(IP-1)
ILLUMINATED PUSHBUTTON
(IP-1)
ILLUMINATED PUSHBUTTON
*
(IP-1)
TMP
MD
BWRY DOOR
TEMP
SENSOR 75LC # 2 ONLY READS TEMP
TMP
MD
BWRYDOOR
TEMP
SENSOR 75LC # 3 ONLY READS TEMP
CONNECT ALL LIGHTS TO THIS ALARM'S TERMINAL
OF COMPARTMENT, DOOR AJAR,
MC-1 CONTACTS CAN CONNECT INSIDE IP-1
WIRING DIAGRAM
IP-1'S & MAGNETIC CONTACTS.
MOTION DETECTOR (MD-1)
FUNCTION: TO PROVIDE 3 AND 4 WAY
AND AUTOMATIC "LIGHTS-ON" AT
EACH DOOR.
*NOTE: ALL CONNECTIONS SHOWN ARE LOW
VOLTAGE USING RECOMMENDED INTER-CONNECT
WIRE: [22AWG,MULTI-CONDUCTOR,STRANDED]
PROVIDE SEPARATE CONDUIT FOR LOW VOLTAGE WIRING.
- 75LC WITH MULTIPLE
ALSO SHOWN
LIGHT SWITCHING INSIDE
Kitchen Brains © 2014 | www.KitchenBrains.com | 229-40072 D
This document contains confidential information. The dissemination, publication, copying, or duplication of this document or the software described herein without prior written authorization is strictly prohibited.
Page 10 of 12
MODULARM 75LC Multi-Monitor Installation & Operating

Kitchen Brains © 2014 | www.KitchenBrains.com | 229-40072 D
This document contains confidential information. The dissemination, publication, copying, or duplication of this document or the software described herein without prior written authorization is strictly prohibited.
Page 11 of 12
MODULARM 75LC Multi-Monitor Installation & Operating
EXPANSION
PORT
TXRX SHLD
DRY
CONTACTS
C NC NO
SUPPLY
POWER
120 VAC
LIGHTS
N/C
CONTACTS
TEMP. PROBE
MD-1
MOTION
DECTECTOR
IP-1
PUSH
BUTTON
9V,NI-MH
RECHARGEABLE
BATTERY
MAGNETIC
*COLORS INDICATED ARE TYPICAL
BLOCK
LINE VOLTAGE CONNECTIONS
TEMP B R Y DOOR
MD W
G
B
R
(GREEN)
B
W
R
Y
1000W
8.3A@120VAC
*75LC MUST
BE GROUNDED
GREEN WIRE
75LC TERMINAL
PR
MODULARM 75LC WIRING DIAGRAM
75LC
FROM
BACK
C
B
A
VERSION 1 VERSION 2
LINE
LINE
NEUTRAL
NEUTRAL
LIGHTS
LIGHTS
LINE
NEUTRAL
LIGHTS
MODULARM
WWW.KITCHENBRAINS.COM
MESSAGE DISPLAYED POSSIBLE CAUSE CORRECTIVE ACTION
HI + ## + (AL) Temperature above HIGH set point for less time
than alarm delay (AL indicates longer than time
delay)
Wait for defrost cycle to end
Check HIGH set point ( & alarm delay)
Possibly adjust setting
Check location of temp probe Relocate if necessary
Lo + ## + (AL) Temperature below LOW set point for less time
than alarm delay (AL indicates longer than time
delay)
Check location of temp probe
Check LOW set point ( & alarm delay) & possibly adjust setting
Relocate if necessary
LO+OPN Open circuit or out of range value on temp probe Ensure proper electrical connection of temp probe.
Ensure proper sensing bulb.
Inspect run of wire
HI+ SHR Short circuit or out of range value on temp probe Ensure proper electrical connection of temp probe
Ensure proper sensing bulb.
Inspect run of wire
HI+ SHR
LO+OPN
Door sensor & temp probe are reversed Door sensor & temp probe are reversed
OCC Occupancy sensor is giving error Check connection to Motion Detector and Motion detector
device
PF Line voltage is not detected Check Line voltage.
Check for signs of physical damage
HLP (cannot silence) Fault from IP-1 Inspect wire connection points [B W R Y] on 75LC and IP-1
ERR + ## Fault from I-BOARD or 75LC WIRELESS Inspect wire connection points on 75LC [TX RX SHLD PR] and
Crossover device (I-BOARD or 75LC WIRELESS)
DOR (cannot silence) Fault on door contact Inspect wire connection points and physical contact alignment
Rapidly changing temperature Empty compartment,
Poor sensor location,
Wrong sensor
Fill compartment
Relocate sensor
Call for assistance in identification
TROUBLESHOOTING GUIDE

certifications apply to 75LC only
®
This document contains confidential information. The dissemination, publication, copying, or duplication of this document or the software described herein without prior written authorization is strictly prohibited.
SPECIFICATIONS- 75LC
DIMENSIONS
4.5” L x 2.75” W x 2.0” D (Dimensions include
outdoor type single gang outlet box.)
POwEr SuPPLy
120VAC +/- 10%
POwEr CONSuMPTION
3.6VA Max (30mA)
ALArM rELAy
N/O & N/C Dry contacts, 1A @ 28VDC
LIghT rELAy
8.3A @ 120VAC, 1000W tungsten
AMbIENT TEMP
0-40°C
huMIDITy
90% noncondensing
MEASurEMENT TEMPErATurE rANgE
-40°F to 125°F (-40°C to 52°C)
TEMPErATurE SENSOr
Standard 25’ sensor. (Other lengths available.)
rESOLuTION
1°F or °C
ACCurACy
+/- 1°F from -25°F to 70°F (-32°C to 21°C), +/-2°F
full range
MOuNTINg
Outdoor, single gang outlet box*
*Alternate enclosure for mounting must be UL listed
enclosure, providing multiple wire access hubs for
running line and low voltage.
Kitchen Brains © 2014 | www.KitchenBrains.com | 229-40072 D Page 12 of 12
MODULARM 75LC Multi-Monitor Installation & Operating
International offices are located in the
United Kingdom, China and Singapore:
Europe, Middle East, Africa
31 Saffron Court Southfields Business Park
Basildon, Essex SS15 6SS ENGLAND
Phone: +44 0 1268544000
China
1803, 18F, No 922 Hengshan Rd
Shanghai 200030, CHINA
Phone: +8613916 854 613
Asia Pacific
13A MacKenzie Road
228676
Singapore
Phone: +65 983159273
Food Automation - Service Techniques, Inc.
905 Honeyspot Road, Stratford, CT 06615-7147 USA
Phone: +1-203-377-4414
Sales: 1-800-327-8766
Fax: +1-203-377-8187
International Callers: +1-203-378-6860
www.KitchenBrains.com
Toll-free technical support 24/7 from the U.S.,
Canada, and Caribbean: 1-800-243-9271
WARRANTY
Kitchen Brains makes the following limited warranty to the original purchaser
only:
Hardware: Hardware products, other than replacement parts and probes are
warranted to be free from defects in material and/or workmanship for a period
of 1 year from the original date of purchase.
Replacement Parts and Probes: Are warranted to be free from defects in
material and/or workmanship for a period of ninety (90) days from the date of
purchase.
Information Services/Software: The Information Services or Software is
provided “as is” without warranty of any kind arising from its use or operation.
The warranty is valid in the United States only and covers only the repair or
replacement of the defective part (at the option of Kitchen Brains) and does
not include any labor changes associated with the repair or replacement.
Outside the US warranty may vary, contact the Authorized Distributor in your
country for specific warranty details.
This limited warranty does not apply to normal wear and tear or damage
resulting from accident, alteration, misuse, abuse or a problem due to
operation at voltages other than that specified on the product nameplate
and is void if the serial number is removed or defaced. No other warranty
is expressed or implied, including merchantability and fitness, and all other
warranties are excluded.
Additional terms and conditions may apply, for a complete copy of the
warranty consult www.kitchenbrains.com/warranty.
PATENTS
The products manufactured by Kitchen Brains are protected
under one or more of the following U.S. Patents:
5,711,060 5,723,846 5,875,430 6,142,666
5,711,606 5,723,846 5,875,430 6,142,666
6,339,930 6,401,466 6,401,467 6,581,391
7,015,433 7,650,833 7,877,291 8,060,408
8,712,851
Plus foreign patents and patents pending and licensed patent
5,973,297
SPECIFICATIONS- IP-1
DIMENSIONS
4.5” L x 2.75” W x 2.0” D (Dimensions include
outdoor type single gang outlet box.)
POWER SUPPLY
6V DC from 75LC
AMBIENT TEMP
-40-40°C
HUMIDITY
90% noncondensing
MOUNTING
Outdoor, single gang outlet box*
*Alternate enclosure for mounting must be UL listed
enclosure, providing multiple wire access hubs for
running low voltage.
SPECIFICATIONS- MD-1
DIMENSIONS
3.125” L x 4.5” W x 3.5” D (Dimensions include
outdoor type single gang outlet box.)
POWER SUPPLY
6V DC from 75LC
OPERATING TEMPERATURE
-10°C -50°C (14°F to 122°F)
MAX COVERAGE
12x12m (40x40ft) / 90°
MOUNTING HEIGHT
1.8m - 2.4m (6 - 8ft)
HUMIDITY
90% noncondensing
MOUNTING
Outdoor, single gang outlet box*
*Alternate enclosure for mounting must be UL listed
enclosure, providing multiple wire access hubs for
running low voltage.
Other manuals for Modularm 75LC
2
This manual suits for next models
1
Table of contents
Other Kitchen Brains Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

Krone
Krone OPTISOUND 3030 C operating instructions

Omega
Omega iServer 2 Series user guide

Panasonic
Panasonic DMR-HW220 operating instructions

Danaher
Danaher Hengstler tico 734 operating instructions

Masibus
Masibus 9000C user manual

PCB Piezotronics
PCB Piezotronics 356A31/NC Installation and operating manual