KNX 70662 Guide

Intra-Sewi KNX TH-Pr
Ambient Climate Sensor with Presence Detector
Item numbers 70662 (white), 70667 (black)
EN
Installation and Adjustment


1 Contents
Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany
Sensor Intra-Sewi KNX TH-Pr • from version 1.0
Version: 11.06.2018 • Technical changes and errors excepted.
1. Description ........................................................................................... 5
1.0.1. Scope of delivery .......................................................................................... 5
1.1. Technical data ........................................................................................................... 6
1.1.1. *Measuring accuracy .................................................................................... 7
2. Installation and start-up ....................................................................... 7
2.1. Installation notes ...................................................................................................... 7
2.2. Installation location .................................................................................................. 7
2.2.1. Coverage area of the motion detector ........................................................ 8
2.3. Installation of the sensor ......................................................................................... 9
2.3.1. Installation in false ceiling ............................................................................ 9
2.3.2. Installation in connector socket ................................................................. 10
2.3.3. Back view: connection ................................................................................ 11
2.3.4. Front view: programming and addressing ............................................... 12
2.4. Notes on mounting and commissioning .............................................................. 12
3. Maintenance ....................................................................................... 12
4. Transfer protocol ............................................................................... 13
4.1. List of all communication objects ......................................................................... 13
5. Parameter setting .............................................................................. 24
5.1. Behaviour on power failure/ restoration of power .............................................. 24
5.2. General settings ..................................................................................................... 24
5.3. Motion detector ...................................................................................................... 24
5.3.1. Master 1/2/3/4 .............................................................................................. 26
5.3.2. Align communication between master and slave .................................... 29
5.3.2.1. Sending cycle slave - switch-off delay master ........................... 29
5.3.2.2. Slave cycle reset ........................................................................... 29
5.4. Temperature Measurement ................................................................................... 30
5.5. Temperature PI control .......................................................................................... 31
5.5.0.1. General control ............................................................................. 31
5.5.0.2. General setpoint values ............................................................... 33
5.5.0.3. Comfort Setpoint .......................................................................... 33
5.5.0.4. Standby setpoint ........................................................................... 34
5.5.0.5. Eco setpoint ................................................................................... 34
5.5.0.6. Setpoint values for frost/heat protection (building protection) 35
5.5.0.7. General control variables ............................................................. 35
5.6. Temperature threshold values .............................................................................. 36
5.6.1. Threshold value 1, 2, 3, 4 ........................................................................... 36
5.6.1.1. Threshold value ............................................................................ 36
5.6.1.2. Switching output .......................................................................... 37
5.6.1.3. Block .............................................................................................. 38
5.6.2. Heating control level 1/2 ............................................................................. 38
5.6.3. Cooling control level 1/2 ............................................................................. 41
5.7. Humidity Measurement ......................................................................................... 43

2 Contents
Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany
Sensor Intra-Sewi KNX TH-Pr • from version 1.0
Version: 11.06.2018 • Technical changes and errors excepted.
5.8. Humidity threshold values .................................................................................... 43
5.8.1. Threshold value 1, 2, 3, 4 ........................................................................... 44
5.8.1.1. Threshold value ............................................................................ 44
5.8.1.2. Switching output .......................................................................... 45
5.8.1.3. Block .............................................................................................. 45
5.9. Humidity PI control ................................................................................................ 46
5.9.0.1. General control ............................................................................. 46
5.9.0.2. Controller setpoint ........................................................................ 47
5.9.0.3. Dehumidification and/or humidification ..................................... 48
5.10.Dewpoint measurement ........................................................................................ 49
5.10.1. Cooling medium temp. monitoring ........................................................... 49
5.10.1.1.Threshold value ............................................................................ 49
5.10.1.2.Switching output .......................................................................... 50
5.10.1.3.Blocking ......................................................................................... 51
5.11.Absolute humidity ................................................................................................. 51
5.12.Comfort field .......................................................................................................... 52
5.13.Variable comparator .............................................................................................. 52
5.13.1. Control variable comparator 1/2 ................................................................ 53
5.14.Logic ........................................................................................................................ 53
5.14.0.1.AND logic ....................................................................................... 54
5.14.0.2.OR logic ......................................................................................... 54
5.14.1. AND logic 1-4 and OR logic outputs 1-4 ................................................... 54
5.14.1.1.Block .............................................................................................. 55
5.14.1.2.Monitoring ..................................................................................... 56
5.15.AND logic connection inputs ................................................................................ 56
5.15.1. Connection inputs of the OR logic ............................................................. 58

3 Clarification of signs
This manual is amended periodically and will be brought into line with new software
releases. The change status (software version and date) can be found in the contents footer.
If you have a device with a later software version, please check
www.elsner-elektronik.de in the menu area "Service" to find out whether a more up-to-
date version of the manual is available.
Clarification of signs used in this manual
Installation, inspection, commissioning and troubleshooting of the device
must only be carried out by a competent electrician.
Safety advice.
Safety advice for working on electrical connections, components,
etc.
DANGER! ... indicates an immediately hazardous situation which will lead to
death or severe injuries if it is not avoided.
WARNING! ... indicates a potentially hazardous situation which may lead to
death or severe injuries if it is not avoided.
CAUTION! ... indicates a potentially hazardous situation which may lead to
trivial or minor injuries if it is not avoided.
ATTENTION! ... indicates a situation which may lead to damage to property if it is
not avoided.
ETS In the ETS tables, the parameter default settings are marked by
underlining.

4 Clarification of signs

5 Description
Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
1. Description
The Sensor Intra-Sewi KNX TH-Pr for the KNX building bus system detects motion.
It measures the temperature and the air humidity and calculates the dew-point. Via the
bus, the indoor sensor can receive external values of temperature and humidity and
process them further with its own data to a total value (mixed value, e.g. room aver-
age).
All measurement values can be used for the control of limit-dependent switching out-
puts. States can be linked via AND logic gates and OR logic gates. In addition, an inte-
grated actuating variable comparator can compare and output variables that were re-
ceived via communication objects.
Integrated PI-controllers control ventilation (humidification/dehumidification accord-
ing to humidity) and heating/cooling (according to temperature). The Intra-Sewi KNX
TH-Pr can output a warning to the bus as soon as the comfort field, as per DIN 1946,
is left.
Functions:
•Motion detection
• Measuring the temperature and air humidity (relative, absolute), each with
mixed value calculation. The share of internal measurement value and
external value can be set as a percentage
• Bus message, whether the values for temperature and air humidity are within
the comfort field (DIN 1946). Dew point calculation
•Threshold values can be adjusted per parameter or via communication
objects
•PI-controller for heating (one or two-stage) and cooling (one or two-stage)
according to temperature. Regulation according to separate setpoints or basic
setpoint temperature
•PI controller for humidity according to humidity: Ventilate/Air (one-stage) or
Ventilate (one or two-stage)
•4 AND and 4 OR logic gates, each with 4 inputs. All switching events as well
as 16 logic inputs (in the form of communications objects) can be used as
inputs for the logic gates. The output of each gate can be configured optionally
as 1-bit or 2 x 8-bit
•2 actuation variable comparators to output minimum, maximum or
average values. 5 inputs each for values received via communication objects
Configuration is made using the KNX software ETS. The product file can be down-
loaded from the Elsner Elektronik website on www.elsner-elektronik.de in the “Ser-
vice” menu.
1.0.1. Scope of delivery
•Sensor
• Pre-assembled clamps for false ceiling installation
• Support ring for connector socket installation

6 Description
Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
For socket installation you will need in addition (not supplied):
• Socket Ø 60 mm, 42 mm deep
1.1. Technical data
The product is compliant with the provisions of the EU guidelines.
Housing Plastic, glass
Colour • similar to signal white RAL 9003
• similar to jet black RAL 9005
Assembly built-in, in false ceiling or connector socket
Protection category IP 30
Dimensions Ø approx. 80 mm
height above wall approx. 5 mm
height in wall (installation) approx. 31 mm (incl. clamps)
Total weight approx. 50 g
Ambient temperature Operation -20…+60°C, storage -20…+70°C
Ambient humidity max. 95% RH, avoid condensation
Operating voltage KNX bus voltage
Bus current max. 10 mA
Data output KNX +/- bus plug-in terminal
BCU type Integrated microcontroller
PEI type 0
Group addresses max. 254
Assignments max. 254
Communication objects 232
Temperature sensor:
Measurement range -20°C … +60°C
Resolution 0.1°C
Accuracy* ±0.7°C at -20°C...-10°C
±0.5°C at -10°C...+60°C
Humidity sensor:
Measurement range 0% rH … 100% rH
Resolution 0.1% rH
Accuracy ± 7,5% rH at 0% … 10% rH
± 4,5% rH at 10% … 90% rH
± 7,5% rH at 90% … 100% rH
Motion sensor:
Coverage angle approx. 100° × 82° (see also Coverage area of the motion
detector)
Range approx. 5 m

7 Installation and start-up
Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
1.1.1. *Measuring accuracy
Deviations in measured values due to interfering sources (see chapter installation lo-
cation) must be corrected in the ETS in order to achieve the specified accuracy of the
sensor (offset).
During the Temperature measurement, the self-heating of the device is taken into
consideration by the electronics. It is compensated by the software, therefore the dis-
played/output indoor temperature measuring value is correct.
2. Installation and start-up
2.1. Installation notes
Installation, testing, operational start-up and troubleshooting should
only be performed by an electrician.
CAUTION!
Live voltage!
There are unprotected live components inside the device.
• National legal regulations are to be followed.
• Ensure that all lines to be assembled are free of voltage and take
precautions against accidental switching on.
• Do not use the device if it is damaged.
• Take the device or system out of service and secure it against
unintentional use, if it can be assumed, that risk-free operation is no
longer guaranteed.
The device is only to be used for its intended purpose. Any improper modification or
failure to follow the operating instructions voids any and all warranty and guarantee
claims.
After unpacking the device, check it immediately for possible mechanical damage. If it
has been damaged in transport, inform the supplier immediately.
The device may only be used as a fixed-site installation; that means only when assem-
bled and after conclusion of all installation and operational start-up tasks and only in
the surroundings designated for it.
Elsner Elektronik is not liable for any changes in norms and standards which may occur
after publication of these operating instructions.
2.2. Installation location
Install and use only in dry interior rooms! Avoid condensation.

8 Installation and start-up
Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
The Sensor Intra-Sewi KNX TH-Pr is installed in a false ceiling or a standard con-
nection socket (Ø 60 mm, 42 mm deep).
The device must be installed on the ceiling, so that the movement capturing takes
place from above. Make sure that the desired area is covered by the sensor's coverage
angle and that no obstacles obstruct the recording.
When selecting an installation location, please ensure that the measurement results of
temperature and humidity are affected as little as possible by external influences.
Possible sources of interference include:
• Direct sunlight
• Drafts from windows and doors
• Draughts from ducts coming from other rooms or the outdoors
• Warming or cooling of the building structure on which the sensor is mounted,
e.g. due to sunlight, heating or cold water pipes
• Connection lines and empty ducts which lead from warmer or colder areas to
the sensor
Measurement variations from such sources of interference must be corrected in the
ETS in order to ensure the specified accuracy of the sensor (offset).
2.2.1. Coverage area of the motion detector
Angle of coverage: approx. 100° × 82°
Range: approx. 5 m
Segmentation of the coverage area
Fig. 1
Distance 2.50 m
5.66 m
7.42 m
Orientation of the sup-
port ring for socket ins-
tallation

9 Installation and start-up
Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
Size of the coverage area
2.3. Installation of the sensor
2.3.1. Installation in false ceiling
Connect the bus line to the KNX terminal (red/black).
Place the device in the installation opening in the ceiling. For this, fold the clamps up-
wards and guide the device through the installation opening with the clamps first.
Intra-Sewi KNX TH-Pr is automatically fixed by the clamps.
Distance Length Width
2.50 m approx. 7.42 m approx. 5.66 m
3.50 m approx. 10.38 m approx. 7.92 m
Fig. 2
Distance 3.50 m
7.92 m
10.38 m
Orientation of the sup-
port ring for socket ins-
tallation

10 Installation and start-up
Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
2.3.2. Installation in connector socket
Before socket installation, remove the clamps for the false ceiling installation.
Screw the support ring onto the socket. Pay attention to the orientation as shown in the
chapter Coverage area of the motion detector.
Connect the bus line to the KNX terminal (red/black).
Clamp the device in the support ring so that the springs on the device snap over the
tabs of the support ring.
A
Fig. 3
1 Clamps for installation in false ceiling
A Height in wall (built-in): approx. 31 mm
B Space behind the false ceiling, necessary for insertion (clear dimension):
approx. 31 mm
C Maximum wall thickness: 20 mm
D Hole size for installation: 50...65 mm
B
C
D
1
Fig. 4: Tragring
1Tabs
1
1

11 Installation and start-up
Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
2.3.3. Back view: connection
The connection is made with the KNX terminal (red/black) to KNX TP.
Fig. 5
Connector socket with Ø 60 mm, 42 mm deep.
1 Support ring, screwed to the socket
2 Springs hold the device firmly on the support ring
2
1
2
Fig. 6
1 Clamps for installation in false
ceiling
2 Springs for installation in sup-
port ring
3 KNX terminal
1
3
2
1

12 Maintenance
Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
2.3.4. Front view: programming and addressing
The equipment is delivered with the bus address 15.15.255. You can program a differ-
ent address in the ETS by overwriting the address or by teaching the device via the pro-
gramming button.
The programming button is located between the airing lamella (Fig. 7: No. 4).
2.4. Notes on mounting and commissioning
Never expose the device to water (e.g. rain) or dust. This can damage the electronics.
You must not exceed a relative humidity of 95%. Avoid condensation.
The airing lamella must not be closed or covered. The device must not be painted over.
After the bus voltage has been applied, the device will enter an initialisation phase last-
ing a few seconds. During this phase no information can be received or sent via the
bus.
The motion sensor has a start-up phase of approx. 15 seconds during which no motion
detection takes place.
3. Maintenance
The movement sensor and the airing lamella must not get dirty or covered. As a rule,
it is sufficient to wipe the device with a soft, dry cloth twice a year.
1Fig. 7
1 Clamps for installation in false
ceiling
2 Airing lamella
3 Motion sensor
4 Programming button
(recessed, larger opening)
5 Programming LED
(recessed, smaller opening)
2
3
1
4
5

13 Transfer protocol
Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
4. Transfer protocol
Units:
Temperatures in degrees Celsius
Brightness in Lux
Air humidity in %
Absolute air humidity in g/kg and/or g/m3
Variables in %
4.1. List of all communication objects
Abbreviation flags:
C Communication
R Read
WWrite
T Transfer
UUpdate
No. Text Function Flags Data Point Type Size
0 Software version Output R-CT [217.1]
DPT_Version
2 Bytes
5 Motion sensor: Test object Output R-CT [14]
14.xxx
4 Bytes
6 Motion sensor: Test object
release (1 = release)
Input -WC- [1.1]
DPT_Switch
1 Bit
7 Motion sensor: Slave: Block (1 =
Blocking)
Input -WC- [1.1]
DPT_Switch
1 Bit
8 Motion sensor: Slave: Message Output R-CT [1.1]
DPT_Switch
1 Bit
9 Motion sensor: Slave: Cycle
reset
Input -WC- [5.1]
DPT_Scaling
1 Byte
10 Motion sensor: Master 1: bright-
ness
Input -WCT [9.4]
DPT_Value_Lux
2 Bytes
11 Motion sensor: Master 1:
Brightn. thresh. val. On
Input /
Output
-WCT [9.4]
DPT_Value_Lux
2 Bytes
12 Motion sensor: Master 1: Bright-
ness hysteresis
Input /
Output
-WCT [9.4]
DPT_Value_Lux
2 Bytes
13 Motion sensor: Master 1: Bright-
ness waiting time
Input RWC- [7.5]
DPT_TimePeriodSec
2 Bytes
14 Motion sensor: Master 1: Out-
put
Output R-CT Depending on setting 1 Bit -
4 Bytes
15 Motion sensor: Master 1: Switch
on delay
Input RWC- [7.5]
DPT_TimePeriodSec
2 Bytes
16 Motion sensor: Master 1: Switch
off delay
Input RWC- [7.5]
DPT_TimePeriodSec
2 Bytes

14 Transfer protocol
Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
17 Motion sensor: Master 1: Slave
message
Input -WC- [1.1]
DPT_Switch
1 Bit
18 Motion sensor: Master 1: Slave
cycle reset
Output --CT [5.1]
DPT_Scaling
1 Byte
19 Motion sensor: Master 1: Block
(1 = Blocking)
Input -WC- [1.1]
DPT_Switch
1 Bit
20 Motion sensor: Master 1: Cen-
tral Off
Input -WC- [1.1]
DPT_Switch
1 Bit
21 Motion sensor: Master 2: bright-
ness
Input -WCT [9.4]
DPT_Value_Lux
2 Bytes
22 Motion sensor: Master 2:
Brightn. thresh. val. On
Input /
Output
-WCT [9.4]
DPT_Value_Lux
2 Bytes
23 Motion sensor: Master 2: Bright-
ness hysteresis
Input /
Output
-WCT [9.4]
DPT_Value_Lux
2 Bytes
24 Motion sensor: Master 2: Bright-
ness waiting time
Input RWC- [7.5]
DPT_TimePeriodSec
2 Bytes
25 Motion sensor: Master 2: Out-
put
Output R-CT Depending on setting 1 Bit -
4 Bytes
26 Motion sensor: Master 2: Switch
on delay
Input RWC- [7.5]
DPT_TimePeriodSec
2 Bytes
27 Motion sensor: Master 2: Switch
off delay
Input RWC- [7.5]
DPT_TimePeriodSec
2 Bytes
28 Motion sensor: Master 2: Slave
message
Input -WC- [1.1]
DPT_Switch
1 Bit
29 Motion sensor: Master 2: Slave
cycle reset
Output --CT [5.1]
DPT_Scaling
1 Byte
30 Motion sensor: Master 2: Block
(1 = Blocking)
Input -WC- [1.1]
DPT_Switch
1 Bit
31 Motion sensor: Master 2: Cen-
tral Off
Input -WC- [1.1]
DPT_Switch
1 Bit
32 Motion sensor: Master 3: bright-
ness
Input -WCT [9.4]
DPT_Value_Lux
2 Bytes
33 Motion sensor: Master 3:
Brightn. thresh. val. On
Input /
Output
-WCT [9.4]
DPT_Value_Lux
2 Bytes
34 Motion sensor: Master 3: Bright-
ness hysteresis
Input /
Output
-WCT [9.4]
DPT_Value_Lux
2 Bytes
35 Motion sensor: Master 3: Bright-
ness waiting time
Input RWC- [7.5]
DPT_TimePeriodSec
2 Bytes
36 Motion sensor: Master 3: Out-
put
Output R-CT Depending on setting 1 Bit -
4 Bytes
37 Motion sensor: Master 3: Switch
on delay
Input RWC- [7.5]
DPT_TimePeriodSec
2 Bytes
38 Motion sensor: Master 3: Switch
off delay
Input RWC- [7.5]
DPT_TimePeriodSec
2 Bytes
No. Text Function Flags Data Point Type Size

15 Transfer protocol
Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
39 Motion sensor: Master 3: Slave
message
Input -WC- [1.1]
DPT_Switch
1 Bit
40 Motion sensor: Master 3: Slave
cycle reset
Output --CT [5.1]
DPT_Scaling
1 Byte
41 Motion sensor: Master 3: Block
(1 = Blocking)
Input -WC- [1.1]
DPT_Switch
1 Bit
42 Motion sensor: Master 3: Cen-
tral Off
Input -WC- [1.1]
DPT_Switch
1 Bit
43 Motion sensor: Master 4: bright-
ness
Input -WCT [9.4]
DPT_Value_Lux
2 Bytes
44 Motion sensor: Master 4:
Brightn. thresh. val. On
Input /
Output
-WCT [9.4]
DPT_Value_Lux
2 Bytes
45 Motion sensor: Master 4: Bright-
ness hysteresis
Input /
Output
-WCT [9.4]
DPT_Value_Lux
2 Bytes
46 Motion sensor: Master 4: Bright-
ness waiting time
Input RWC- [7.5]
DPT_TimePeriodSec
2 Bytes
47 Motion sensor: Master 4: Out-
put
Output R-CT Depending on setting 1 Bit -
4 Bytes
48 Motion sensor: Master 4: Switch
on delay
Input RWC- [7.5]
DPT_TimePeriodSec
2 Bytes
49 Motion sensor: Master 4: Switch
off delay
Input RWC- [7.5]
DPT_TimePeriodSec
2 Bytes
50 Motion sensor: Master 4: Slave
message
Input -WC- [1.1]
DPT_Switch
1 Bit
51 Motion sensor: Master 4: Slave
cycle reset
Output --CT [5.1]
DPT_Scaling
1 Byte
52 Motion sensor: Master 4: Block
(1 = Blocking)
Input -WC- [1.1]
DPT_Switch
1 Bit
53 Motion sensor: Master 4: Cen-
tral Off
Input -WC- [1.1]
DPT_Switch
1 Bit
56 Temperature sensor: malfunc-
tion
Output R-CT [1.1]
DPT_Switch
1 Bit
57 Temperature sensor: measured
value external
Input -WCT [9.1]
DPT_Value_Temp
2 Bytes
58 Temperature sensor: measured
value
Output R-CT [9.1]
DPT_Value_Temp
2 Bytes
59 Temperature sensor: measured
value total
Output R-CT [9.1]
DPT_Value_Temp
2 Bytes
60 Temperature sensor: measured
value min./max. query
Input -WC- [1.17]
DPT_Trigger
1 Bit
61 Temperature sensor: measured
value minimum
Output R-CT [9.1]
DPT_Value_Temp
2 Bytes
62 Temperature sensor: measured
value maximum
Output R-CT [9.1]
DPT_Value_Temp
2 Bytes
No. Text Function Flags Data Point Type Size

16 Transfer protocol
Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
63 Temperature sensor: measured
value min./max. reset
Input -WC- [1.17]
DPT_Trigger
1 Bit
66 Temp. thresholdV 1: Absolute
value
Input /
Output
-WCT [9.1]
DPT_Value_Temp
2 Bytes
67 Temp. thresholdV 1: (1:+ | 0:-) Input -WC- [1.1]
DPT_Switch
1 Bit
68 Temp. thresholdV 1: Switching
delay from 0 to 1
Input -WC- [7.5]
DPT_TimePeriodSec
2 Bytes
69 Temp. thresholdV 1: Switching
delay from 1 to 0
Input -WC- [7.5]
DPT_TimePeriodSec
2 Bytes
70 Temp. thresholdV 1: Switching
output
Output R-CT [1.1]
DPT_Switch
1 Bit
71 Temp. thresholdV 1: Switching
output block
Input -WC- [1.1]
DPT_Switch
1 Bit
72 Temp. thresholdV 2: Absolute
value
Input /
Output
-WCT [9.1]
DPT_Value_Temp
2 Bytes
73 Temp. thresholdV 2: (1:+ | 0:-) Input -WC- [1.1]
DPT_Switch
1 Bit
74 Temp. thresholdV 2: Switching
delay from 0 to 1
Input -WC- [7.5]
DPT_TimePeriodSec
2 Bytes
75 Temp. thresholdV 2: Switching
delay from 1 to 0
Input -WC- [7.5]
DPT_TimePeriodSec
2 Bytes
76 Temp. thresholdV 2: Switching
output
Output R-CT [1.1]
DPT_Switch
1 Bit
77 Temp. thresholdV 2: Switching
output block
Input -WC- [1.1]
DPT_Switch
1 Bit
78 Temp. thresholdV 3: Absolute
value
Input /
Output
-WCT [9.1]
DPT_Value_Temp
2 Bytes
79 Temp. thresholdV 3: (1:+ | 0:-) Input -WC- [1.1]
DPT_Switch
1 Bit
80 Temp. thresholdV 3: Switching
delay from 0 to 1
Input -WC- [7.5]
DPT_TimePeriodSec
2 Bytes
81 Temp. thresholdV 3: Switching
delay from 1 to 0
Input -WC- [7.5]
DPT_TimePeriodSec
2 Bytes
82 Temp. thresholdV 3: Switching
output
Output R-CT [1.1]
DPT_Switch
1 Bit
83 Temp. thresholdV 3: Switching
output block
Input -WC- [1.1]
DPT_Switch
1 Bit
84 Temp. threshold value 4: Abso-
lute value
Input /
Output
-WCT [9.1]
DPT_Value_Temp
2 Bytes
85 Temp. threshold value 4: (1:+ |
0:-)
Input -WC- [1.1]
DPT_Switch
1 Bit
86 Temp. thresh. val. 4: Switching
delay from 0 to 1
Input -WC- [7.5]
DPT_TimePeriodSec
2 Bytes
No. Text Function Flags Data Point Type Size

17 Transfer protocol
Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
87 Temp. thresh. val. 4: Switching
delay from 1 to 0
Input -WC- [7.5]
DPT_TimePeriodSec
2 Bytes
88 Temp. threshold value 4: Swit-
ching output
Output R-CT [1.1]
DPT_Switch
1 Bit
89 Temp. threshold value 4: Swit-
ching output block
Input -WC- [1.1]
DPT_Switch
1 Bit
95 Temp.control: HVAC mode
(priority 1)
Input -WC- [20.102]
DPT_HVACMode
1 Byte
96 Temp.control: HVAC mode
(priority 2)
Input -WCT [20.102]
DPT_HVACMode
1 Byte
97 Temp.control: Mode frost/heat
protection activt.
Input -WCT [1.1]
DPT_Switch
1 Bit
98 Temp.control: Block (1 = Bloc-
king)
Input -WC- [1.1]
DPT_Switch
1 Bit
99 Temp.control: Current setpoint Output R-CT [9.1]
DPT_Value_Temp
2 Bytes
100 Temp.control: Switch. (0: Hea-
ting | 1: Cooling)
Input -WC- [1.1]
DPT_Switch
1 Bit
101 Temp.control: Setpoint Com-
fort heating
Input /
Output
-WCT [9.1]
DPT_Value_Temp
2 Bytes
102 Temp.control: Setpoint Com-
fort heat.(1:+ | 0:-)
Input -WC- [1.1]
DPT_Switch
1 Bit
103 Temp.control: Setpoint Com-
fort cooling
Input /
Output
-WCT [9.1]
DPT_Value_Temp
2 Bytes
104 Temp.control: Setpoint Com-
fort cool.(1:+ | 0:-)
Input -WC- [1.1]
DPT_Switch
1 Bit
105 Temp.control: Basic 16-bit set-
point shift
Input /
Output
-WCT [9.1]
DPT_Value_Temp
2 Bytes
106 Temp.control: Setpoint Standby
heating
Input /
Output
-WCT [9.1]
DPT_Value_Temp
2 Bytes
107 Temp.control: Setpoint Standby
heat.(1:+ | 0:-)
Input -WC- [1.1]
DPT_Switch
1 Bit
108 Temp.control: Setpoint Standby
cooling
Input /
Output
-WCT [9.1]
DPT_Value_Temp
2 Bytes
109 Temp.control: Setpoint Standby
cool. (1:+ | 0:-)
Input -WC- [1.1]
DPT_Switch
1 Bit
110 Temp.control: Setpoint Eco hea-
ting
Input /
Output
-WCT [9.1]
DPT_Value_Temp
2 Bytes
111 Temp.control: Setpoint Eco hea-
ting (1:+ | 0:-)
Input -WC- [1.1]
DPT_Switch
1 Bit
112 Temp.control: Setpoint Eco coo-
ling
Input /
Output
-WCT [9.1]
DPT_Value_Temp
2 Bytes
113 Temp.control: Setpoint Eco coo-
ling (1:+ | 0:-)
Input -WC- [1.1]
DPT_Switch
1 Bit
No. Text Function Flags Data Point Type Size

18 Transfer protocol
Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
114 Temp.control: Control variable
heating (level 1)
Output R-CT [5.1]
DPT_Scaling
1 Byte
115 Temp.control: Control variable
heating (level 2)
Output R-CT [5.1]
DPT_Scaling
1 Byte
116 Temp.control: Control variable
cooling (level 1)
Output R-CT [5.1]
DPT_Scaling
1 Byte
117 Temp.control: Control variable
cooling (level 2)
Output R-CT [5.1]
DPT_Scaling
1 Byte
118 Temperature control: Variable
for 4/6-way valve
Output R-CT [5.1]
DPT_Scaling
1 Byte
119 Temp.control: Status Heat. level
1 (1=ON|0=OFF)
Output R-CT [1.1]
DPT_Switch
1 Bit
120 Temp.control: Status Heat. level
2 (1=ON|0=OFF)
Output R-CT [1.1]
DPT_Switch
1 Bit
121 Temp.control: Status Cool. level
1 (1=ON|0=OFF)
Output R-CT [1.1]
DPT_Switch
1 Bit
122 Temp.control: Status Cool. level
2 (1=ON|0=OFF)
Output R-CT [1.1]
DPT_Switch
1 Bit
123 Temp.control: Comfort exten-
sion status
Input /
Output
-WCT [1.1]
DPT_Switch
1 Bit
124 Temp.control: Comfort Exten-
sion time
Input -WCT [7.5]
DPT_TimePeriodSec
2 Bytes
130 Humidity sensor: malfunction Output R-CT [1.1]
DPT_Switch
1 Bit
131 Humidity sensor: measured
value external
Input -WCT [9.7]
DPT_Value_Humidity
2 Bytes
132 Humidity sensor: measured
value
Output R-CT [9.7]
DPT_Value_Humidity
2 Bytes
133 Humidity sensor: measured
value total
Output R-CT [9.7]
DPT_Value_Humidity
2 Bytes
134 Humidity sensor: measured
value min./max. query
Input -WC- [1.17]
DPT_Trigger
1 Bit
135 Humidity sensor: measured
value minimum
Output R-CT [9.7]
DPT_Value_Humidity
2 Bytes
136 Humidity sensor: measured
value maximum
Output R-CT [9.7]
DPT_Value_Humidity
2 Bytes
137 Humidity sensor: measured
value min./max. reset
Input -WC- [1.17]
DPT_Trigger
1 Bit
138 Humidity thresholdV 1: Abso-
lute value
Input /
Output
-WCT [9.7]
DPT_Value_Humidity
2 Bytes
139 Humidity thresholdV 1: (1:+ | 0:-) Input -WC- [1.1]
DPT_Switch
1 Bit
140 Humidity thresholdV 1: Delay
from 0 to 1
Input -WC- [7.5]
DPT_TimePeriodSec
2 Bytes
No. Text Function Flags Data Point Type Size
This manual suits for next models
1
Table of contents
Popular Temperature Controllers manuals by other brands

Temperature Guard
Temperature Guard VM500-3 Operating manual and instructions

Bosch
Bosch YPRM66XB Operation handbook

iNels
iNels RFTC-150/G/ice manual

Audacy
Audacy AH-T Series installation instructions

Salus
Salus DT600 quick start guide

Mammoth Innovation
Mammoth Innovation Monkey Vision MOMETER PRO quick start guide