Komfovent C3.1 Operating instructions

EN Electrical installation and Operation Manual
C3.1


UAB KOMFOVENT we reserve the right to make changes without prior notice
3
C3.1-16-01
This symbol indicates that this product is not to be disposed of with your household waste, according to the
WEEE Directive (2002/96/EC) and your national law. This product should be handed over to a designated
collection point, or to an authorised collection site for recycling waste electrical and electronic equipment (EEE).
Improper handling of this type of waste could have a possible negative impact on the environment and human
health due to potentially hazardous substances that are generally associated with EEE. At the same time, your
cooperation in the correct disposal of this product will contribute to the effective usage of natural resources. For
more information about where you can drop off your waste equipment for recycling, please contact your local city
ofce, waste authority, approved WEEE scheme or your household waste disposal service.
Content
1. ELECTRICAL INSTALLATION MANUAL..................................................................................................... 4
1.1. Air Handling Units Sections Connection..................................................................................................... 4
1.2. Electric Power Supply Connection............................................................................................................. 4
1.3. External Elements Connection................................................................................................................... 5
1.4. Temperature Sensors Installation............................................................................................................... 8
1.5. Requirements for the installation of the control panel................................................................................ 8
1.6. Control panel connection ........................................................................................................................... 8
2. OPERATION MANUAL................................................................................................................................... 9
2.1. Unit Control ................................................................................................................................................ 9
2.2. Control panel indication.............................................................................................................................. 9
2.3. Parameters overview ............................................................................................................................... 10
2.4. Operation modes selection ...................................................................................................................... 10
2.5. Menu ........................................................................................................................................................ 10
2.5.1. Overview .........................................................................................................................................11
2.5.1.1. Alarms................................................................................................................................11
2.5.1.2. Detailed information...........................................................................................................11
2.5.2. Functions.........................................................................................................................................11
2.5.2.1. Air quality control .............................................................................................................. 12
2.5.2.2. Exhaust air ow correction .............................................................................................. 12
2.5.2.3. Summer night cooling ...................................................................................................... 12
2.5.2.4. Minimum temperature control .......................................................................................... 13
2.5.2.5. Override function ............................................................................................................. 13
2.5.3. Scheduling ..................................................................................................................................... 13
2.5.4. Settings .......................................................................................................................................... 13
2.5.4.1. Air handling unit settings .................................................................................................. 14
2.5.4.2. Personalization ................................................................................................................. 14
2.6. Other Control Functions........................................................................................................................... 15
2.6.1. Remote unit switching on or off...................................................................................................... 15
2.6.2. Pump control .................................................................................................................................. 15
2.6.3. Cooling energy recovery ................................................................................................................ 15
2.6.4. Remote unit operation and failure indication.................................................................................. 15
2.7. Unit PC control......................................................................................................................................... 15
2.8. Troubleshooting........................................................................................................................................ 15
3. SAFETY REQUIREMENTS .......................................................................................................................... 17

EN
UAB KOMFOVENT we reserve the right to make changes without prior notice
4
C3.1-16-01
1. ELECTRICAL INSTALLATION MANUAL
Installation works can be performed only by the specialists that have required qualication. During installation
following requirements must be fullled.
It is recommended to lay control cables separately from power cables, or
use shielded cables. In such case it is necessary to earth cable shield-
ing!
1.1. Air Handling Units Sections Connection
After unit parts have been connected together (see unit installation instruction), unit sections connecting
cables and wires are connected.
Connector connection is performed strictly according to numeration giv-
en in wiring diagram, or adequate markings (see unit electric scheme).
When disconnecting unit sections, do not pull by connecting wires and
cables!
1.2. Electric Power Supply Connection
If the air handling unit voltage is ~230 V; 50 Hz it is necessary to install the socket with grounding of correspond-
ing capacity (see electric diagram unit). If the voltage is ~400 V; 50 Hz, the cable of electrical power supply is
connected to the main switch, which is located on the unit’s outside wall. It is necessary to connect earthing!
Types of cables of connection of electrical power supply are specied in 1.2 Table:
1.2 Table. Electrical Power Supply Cable Types
Air Handling Unit Type Cable type
DOMEKT P 400 H(V)
DOMEKT P 700 H(V)
DOMEKT P 900 H(V)
DOMEKT P 900 H(V)
VERSO P 1200 H**
VERSO P 1600 H**
VERSO P 2000 H**
VERSO S 1200 F**
VERSO S 2000 F**
3 x 1,5 mm2(Cu)
DOMEKT S 700 F 3 x 2,5 mm2(Cu)
DOMEKT P 900 H(V)
DOMEKT P 900 H(V)
VERSO P 3000 H**
VERSO P 4000 H**
VERSO P 4500 H**
VERSO P 7000 H**
DOMEKT S 700 F
VERSO S 3000 F
VERSO S 4000 F
5 x 1,5 mm2(Cu)
VERSO P 1200 H**
DOMEKT S 700 F
VERSO S 1200 F**
5 x 2,5 mm2(Cu)
VERSO P 1600 H(V)**
VERSO S 1200 F**
VERSO S 2000 F**
5 x 4,0 mm2(Cu)
VERSO P 3000 H** 5 x 6,0 mm2(Cu)
VERSO P 2000 H**
VERSO P 4000 H**
VERSO P 4500 H**
VERSO S 2000 F**
5 x 10,0 mm2(Cu)
** does not conform to the Ecodesign directive 2016.

UAB KOMFOVENT we reserve the right to make changes without prior notice
5
C3.1-16-01
Air handling units designed for 400V AC supply voltage must be con-
nected to the stationary installation by solid cable. All units must be con-
nected through circuit breaker with 300 mA current leakage protection
(type B or B+).
Before connecting unit to the electrical power supply, it is necessary to
check whether earthing has been installed properly.
1.3. External Elements Connection
In the air handling unit it is provided connection board 1.3 a picture or 1.3 b picture (depending on the unit type),
all external elements are connected to connection board. External elements connection diagram is given in the
1.3 c picture or 1.3 d picture.
Connection Board P3
1.3 a Picture
Connection Board C3-P1
1.3 b Picture

EN
UAB KOMFOVENT we reserve the right to make changes without prior notice
6
C3.1-16-01
P3 Control System External Elements Connection Diagram
1.3 c Picture
1Used only in the units with water heater.
2Only in units with EC fans, additional accessories required.
3In DOMEKT S, VERSO S unit is not used.
4In units with AC fans is not used.
Control contact.
Do not connect voltage!
Normally closed contact.
Do not connect voltage!

UAB KOMFOVENT we reserve the right to make changes without prior notice
7
C3.1-16-01
C3-P1 Control System External Elements Connection Diagram
1.3 d Picture
1Used only in the units with water heater.
2Only in units with EC fans, additional accessories required.
3used only in VERSO P 7000 H units.
Normally closed contact.
Do not connect voltage!
Control contact.
Do not connect voltage!

EN
UAB KOMFOVENT we reserve the right to make changes without prior notice
8
C3.1-16-01
1.4. Temperature Sensors Installation
The supply air temperature sensor B1 (1.4 a Picture) is mounted in the air duct in a projected place for it; after
cooler section (if provided). The minimal distance from the duct connection of the unit up to the sensor should
be not less than double diameter of the circular connection or a diagonal of rectangular connection.
The water temperature sensor B5 (1.4 b Picture) is mounted on the water pipe by screwing it into the pro-
vided hole. The sensor must be thermo insulated!
Supply air temperature sensor B1 Water temperature sensor B5
1.4 a Picture 1.4 b Picture
1.5. Requirements for the installation of the control panel
1. The control console should be installed in a room where the following conditions are ensured:
1.1. ambient temperature: 0 ºC ... 40 ºC;
1.2. relative humidity range: 20 % ... 80 %;
1.3. protection against dripping of water (IP X0).
2. Control panel connection is provided through a hole in the back or bottom side.
3. The panel can be mounted on a ush mounting box or in any other place just screwing two holes on the
fastening surface.
Do not use any other type or size screws but those that are packed toget-
her for control panel mounting. Wrong screws may damage electronics
board.
1.6. Control panel connection
The control panel is connected to the connection terminals (see Picture 1.3 a or Picture 1.3 b). The length of the
cable for connecting the panel with the unit may not exceed 150 m.
Yellow (A) () White
(+) RedGreen (B)
Yellow (A)
(+) Red
Green (B)
() White Yellow (A) () White
(+) RedGreen (B)
Yellow (A)
(+) Red
Green (B)
() White
1.6 Picture. Control panel connection
Control panel connection and other cable thicknesses are specied in
the wiring diagram!
Remove protective screen tape, before mounting front cover on the con-
trol panel!

UAB KOMFOVENT we reserve the right to make changes without prior notice
9
C3.1-16-01
2.1 Picture. Control panel
2.2. Control panel indication
MODE 1
21,9 °C
21,3 °C
Temperature
16:30
Selection of
operation modes
Menu
Indication of unit operation
modes and functions
Main parameters
overview window
Switching between
overview windows
Time
Explanation of the displayed symbols
Supply air temperature
Extract air temperature
Supply air volume
Extract air volume
Extract air humidity
Extract (room) air quality
Fan operation
Energy recovery operation
Air heater operation
Air cooler operation
Weekly operation mode
Unit control activation by external contacts (see Chapter 2.5.2.5)
Alarm signal
2. OPERATION MANUAL
2.1. Unit Control
Air handling units control system ensures control of the physical pro-
cesses that are taking place inside the air handling unit.
Control system consists of:
• main controller module;
• circuit breakers and main switch;
• control panel, which can be installed in the convenient place for the
user;
• pressure and temperature sensors.
Control panel (2.1 Picture) is designed for remote air handling unit
control, setting and display of controller parameters.

EN
UAB KOMFOVENT we reserve the right to make changes without prior notice
10
C3.1-16-01
2.3. Parameters overview
The main parameters of the unit are indicated in three main windows of the panel: temperatures indication, air
ow, air quality (humidity) and energy saving.
All other unit parameters are presented in the menu “Overview” (see 11 page).
MODE 1
1250 m3/h
1310 m3/h
Air ow
16:30
MODE 1
21,9 °C
21,3 °C
Temperature
16:30
MODE 1
800 ppm
Air quality
16:30
Note: In supply air units (OTK) only supply air ow and temperature is indicated.
2.4. Operation modes selection
Three operation modes are possible, one of them user can select directly from control panel main window:
• MODE 1, 2, 3 – for each of them the user can set air ow and temperature.
• OFF mode completely turns off the unit.
Reset settings
MODE 2
Supply air ow
1250 m3/h
Extract air ow
1250 m3/h
Setpoint
20 °C
MODE 1
21,9 °C
21,3 °C
Temperature
16:30 Operation modes
MODE 1
MODE 2
MODE 3
OFF
Note: In supply air units (OTK) only supply air ow and temperature is indicated.
2.5. Menu
Menu of panel consists of the four points:
Functions Settings
Overview Scheduling
Menu
MODE 1
21,9 °C
21,3 °C
Temperature
16:30

UAB KOMFOVENT we reserve the right to make changes without prior notice
11
C3.1-16-01
2.5.1. Overview
Main air handling unit parameters are presented in
the main windows (Chapter 2.3). All other informa-
tion, relating to the operation of the unit and alarms is
detailed in overview menu.
Functions Settings
Overview Scheduling
Menu
2.5.2. Functions
In this menu item, the user can activate and set ad-
ditional unit functions.
blank box: function is not activated
gray box: function is activated
Functions Settings
Overview Scheduling
Menu
2.5.1.1. Alarms
This menu displays the notication of existing faults.
After failure elimination (see chapter 2.8), messages are deleted by selecting
“Delete”. By clicking on „History“ can be viewed up to 50 registered alarms.
2.5.1.2. Detailed information
All temperature sensor readings, functioning of separate air handling unit ele-
ments and other detailed information is available in this menu.
Detailed information
Supply air ow
350 m3/h
1 / 3
Supply air temperature
21,9 °C
Extract air temperature
22,1 °C
Outdoor air temperature
16,6 °C
Water temperature
25,3 °C
Alarms
Detailed information
Overview
04A
Electric heater overheating
16B
Extract air lter impurity
Alarms
Delete History
Functions
Air quality
control
Exhaust air ow
correction
Summer night
cooling
Min. temperature
control
Overide function

EN
UAB KOMFOVENT we reserve the right to make changes without prior notice
12
C3.1-16-01
2.5.2.1. Air quality control
Air quality control is designed according to:
• CO2sensor [0...2000 ppm];
• air quality sensor VOCq [0...100 %];
• air pollution sensor VOCp [0...100 %];
• relative humidity sensor [0...100 %];
Depending on the type of the selected sensor, the value of the air quality
function to be maintained is set, and the air handling unit intensity will be adjusted
according to that value. Ventilation intensity will be increased automatically in the
case of deviation from the set value and decreased again when it is approached.
For example, if the unit is designed with the CO2maintenance function and is
equipped with a CO2sensor, after setting value 800 ppm, this set CO2level will
be maintained by adjusting ventilation intensity, i.e. ventilation intensity will be
increased if the CO2level grows and will be decreased when it returns to the
previous condition.
This function is provided only in units with EC fans.
2.5.2.2. Exhaust air ow correction
Set air ow intensity (or maintained air volume) for 1–99 minutes period can be
corrected from -50 % till +50 % from set value. Example, after reducing exhaust
air ow intensity, for some time overpressure will be caused (sometimes needed
to start the replace or such).
Note: After this function has been activated unit will work for the set time period
with present exhaust correction. After time period is over this function turns off
automatically.
This function is provided only in units with EC fans. This function is not
available in supply air units (OTK).
2.5.2.3. Summer night cooling
If the room temperature (exhaust air) in summertime is 5 °C higher than the set-
point and outside temperature is between 12 °C and the setpoint, the ventilation
level is automatically switched to the third intensity level at 00:15 am. The unit
will operate in the third intensity level until 06:00 am or when outside air cools
down (warms up) too much or the room temperature equals the setpoint. The air
is being cooled only by fans, without heat or coolness recovery and additional air
heating or cooling. When function is switched off the unit continues operating in
the previous mode.
Function starts operating automatically if only the unit operates in the
rst or second operation mode. Function stops operating, when the
mode is being changed.
Summer night cooling and minimum temperature control functions can
not be activated at the same time. When one is selected, another’s
function operation is blocked.
Enable
Setpoint
1000 ppm
Sensor
CO2
Air quality control
Enable
Extract ow
-50%
Time
1 min.
Exhaust air ow correction
Enable
Summer night cooling

UAB KOMFOVENT we reserve the right to make changes without prior notice
13
C3.1-16-01
2.5.2.4. Minimum temperature control
In wintertime (outside temperature < 5°C), when heating power is not enough and
supply air temperature is 4°C below setting value, ventilation intensity automati-
cally is decreasing in one level. If there is not enough, one more level (up to mini-
mum) till set supply air temperature will be maintained.
Summer night cooling and minimum temperature control functions can
not be activated at the same time. When one is selected, another’s
function operation is blocked.
2.5.2.5. Override function
Unit is provided with remote control possibility using external device (button, timer,
other sensor) which is connected to the contacts 17, 18 (see chapter 1.3c Picture)
or 27, 28 (see chapter 1.3 d Picture). External signal (short-circuit on contacts 17-
18, 1.3 c Pic. or 27-28, 1.3 d. Pic.) activates “Override” function and air handling
unit starts to operate by the preset parameters.
If “Override” function is deactivated then mentioned contacts can be
used for remote on/off control of the unit (see Chapter 2.6.1.)
Enable
Min. temperature control
Enable
Supply ow
1250 m3/h
Extract ow
1250 m3/h
Setpoint
20 °C
Override funcion
2.5.3. Scheduling
Menu for planning of the air handling unit operation according to the weekly program. For each day of the week
there is a possibility to set up to 3 operation programs.
Functions Settings
Overview Scheduling
Meniu Scheduling
Monday
Tuesday
Wednesday
Thursday
Friday
Enable
1 / 2
Monday
Operation mode
MODE 1
Start time
00:00
Stop time
00:00
Program 1
1 / 3
Note: Every program start and end time is set from 0:00 to 23:59 h.
2.5.4. Settings
This menu is for air handling unit and the user param-
eter setting.
Air handling unit
Personalization
Settings
Functions Settings
Overview Scheduling
Menu

EN
UAB KOMFOVENT we reserve the right to make changes without prior notice
14
C3.1-16-01
2.5.4.1. Air handling unit settings
Temperature control
The air handling unit provides for several temperature control modes:
• Supply. The unit supplies air according to the temperature preset by the user.
• Extract. Unit automatically supplies air of such temperature to maintain preset
exhaust air temperature.
• Auto. When cooling is needed, unit will work in the extract air temperature
maintenance mode. If the outside temperature will be few degrees lower than
set value, control automatically will switch to supply air maintenance mode.
Note. This setting is not intended in supply air units (OTK).
Air volume control
Supply and exhaust air volumes control modes have been provided in the unit:
• CAV – constant air volume control mode. The unit will supply and extract a constant air ow which is preset
by the user, irrespective of any changes occurring in the ventilation system;
• VAV – variable air volume control mode. The unit will supply and extract an air ow with regard to the
ventilation needs in different rooms. In case of frequently changing ventilation demands this air volumes
maintenance mode signally reduces unit exploitation costs.
Menu window for air ow control is intended only in units with EC fans.
It is possible to use a simplied VAV control function, “single-ow VAV control”. It means that the perfor-
mance of this function requires only a single air ow pressure sensor, which is installed in a variable air duct
system (e. g. in supply air). This variable system is called the master ventilation system, according to which
control is performed, while the other air ow (in this case, discharged air) operates as the slave ventilation sys-
tem and always follows the master one. If the supply air requirement in the ventilation system which is assigned
as the master system decreases, the intensity of discharged air in the slave system is reduced correspondingly
by the same percentage.
If the variable air volume control function is mode is selected, the initial
calibration of the control mode must be performed; otherwise, the unit
will not operate if the VAV mode is selected.
Variable air volume control mode calibration:
1. Before start of calibration the air distribution and exhaust devices in ventilation system should be adjusted,
all valves for variable air ow in a way enabling air supply to all ventilated premises should be opened.
2. After switch on of the unit the VAV mode should be selected and calibration procedure should be conrmed.
After the end of the calibration, depending on the conguration of pressure sensors, VAV mode status will
change to Supply, Extract, Double.
3. After calibration the air handling unit further will operate in the previous mode.
Time / Date
Time and date is required for air handling unit operation planning.
Season
For the air handling unit operating in most economical mode, summer and winter seasons have been provided.
• By setting “Winter” season, unit cooling function is blocked.
• By setting “Summer” season, unit heating function is blocked.
• By setting “Auto”, automatic season selection will take place. Depending on
the heating and cooling demand, the season is selected automatically.
2.5.4.2. Personalization
In this item for the user are presented menu language, measurement units and
other control panel settings.
Reset settings
Air handling unit
Temperature control
Flow control
Time/Date
Season
Personalization
Language
English
Flow units
m3/h
Screen saver
On
Panel lock
O
Touch sound
Click

UAB KOMFOVENT we reserve the right to make changes without prior notice
15
C3.1-16-01
2.6. Other Control Functions
2.6.1. Remote unit switching on or off
If the unit is not operating according to programmed week schedule, by connecting (short-circuit) contacts 17,
18 (see chapter 1.3 c Picture) or 27, 28 (see chapter 1.3 d Picture) unit will be switched on and will operate in
mode, which is set in the panel main window (see Chapter 2.4); by disconnecting contacts unit operation will
return to standby mode.
If unit is operating in auto mode with chosen intensity, to switch it off by remote switch contacts 17, 18 (see
chapter 1.3 c Picture) or 27, 28 (see chapter 1.3 d Picture) must be connected (short-circuit).
Remote unit switching on and off is available only after activation of the
weekly program (Chapter 2.5.3.) and deactivation of “Override” function
(Chapter 2.5.2.5.)
2.6.2. Pump control
Units with water heater are designed with water circulation pump control. In winter pump operates continually,
in summer season it is off. When outdoor temperature is lower than 5 °C, pump is automatically turned on.
Pump is connected to the connection box contacts (see 1.3. chapter).
2.6.3. Cooling energy recovery
In summer when room temperature is lower than temperature outside, units with either plate heat exchanger or
rotary heat exchanger automatically operate with activated function of cooling energy recovery. This function
is not intended in supply air units (OTK).
2.6.4. Remote unit operation and failure indication
If the information about unit operation mode is requested (when unit is operating and when is not) indication
device (for ex. bulb) must be connected to the contacts 33, 35 (see chapter 1.3 c Picture). In the connection
board (see chapter 1.3.) are provided contacts 33, 34 (see chapter 1.3 c Picture) or 29, 30 (see chapter 1.3 d
Picture), which are intended for connection of unit’s emergency stop indicating device.
2.7. Unit PC control
This is additionally ordered function and for it implementation special network module “Ping2” is provided.
Connection diagrams and installation requirements of network module are given in the “Ping2” module instal-
lation manual.
After connecting units through special network modules to computer network or Internet and given an IP
address, integrated web server allows the operator from his computer not only to monitor, but also to control
air handling units operation: to turn on/off, change ventilation intensity and etc. It also allows indicating failures.
2.8. Troubleshooting
If the unit is not working:
• Make sure if the unit is connected to the electrical power supply.
• Check if the unit main switch is on (if designed).
• Check all control block fuses. If needed, change failed fuses with the new ones that are the same electrical
parameters as old ones (fuses types are shown in wiring diagrams).
• Check if there is not failure indication on the control panel. If there is indication, it needs to be eliminated
rst. To eliminate failure use 2.8 Table, which describes failures.
• If nothing is indicating on control panel, check whether cable connecting control panel with the unit is not
damaged.

EN
UAB KOMFOVENT we reserve the right to make changes without prior notice
16
C3.1-16-01
2.8 Table. Failures indicated on the control panel, possible reasons and it elimination
Message Possible Failure Cause Failure Elimination
Change supply air lter Supply air lter is clogged. After unit is off, it is necessary to change lter.
Change exhaust air lter Exhaust air lter is clogged. After unit is off, it is necessary to change lter.
Low supply air
temperature
Supply air temperature dropped lower allow-
able level.
Check program settings, unit heat
exchanger and heater operation.
Supply air
overheating
Supply air temperature is higher allowable
level.
Check program settings, unit heat
exchanger and heater operation.
Supply air fan overheat-
ing
Supply air fan motor
overheated due to excessive load.
Check if air lters are inserted, if the unit doors
are closed, if unit ventilation system has been
installed correctly.
Exhaust air fan
overheating
Exhaust air fan overheated due to excessive
load.
Check if air lters are inserted, if the unit doors
are closed, if unit ventilation system has been
installed correctly.
Heater off Heater is disconnected due to low air ow.
When heater cools down, protection restores
automatically. It is recommended to increase
ventilation intensity level.
Electric heater
overheating
Electric heater overheating
protection is on.
To restore protection, it is possible only after
pressing “RESET” button, which is located on
the heater.
Return water low
temperature
Return water temperature in water heater
dropped lower allowable level.
Check circulation pump and heating system con-
dition, heating valve actuator performance.
Frost
possibility
Temperature of the air passing through plate
heat exchanger, dropped lower allowable level.
Check by-pass damper condition and actuator
performance. It is recommended to decrease
ventilation level.
Rotor
stopping The belt is broken, or failure of the rotor motor. Check rotor drive and rotation
sensor condition.
Fire
alarm
Received re alarm signal from the building
re system.
When re alarm signal disappears, unit needs
to be restarted from control panel.
B1 sensor
failure
Supply air temperature sensor is not con-
nected or broken down.
It is necessary to check sensor
connections or change the sensor.
B2 sensor
failure
Exhaust air temperature sensor is not con-
nected or broken down.
It is necessary to check sensor
connections or change the sensor.
B3 sensor
failure
Outdoor temperature sensor is not connected
or broken down.
It is necessary to check sensor
connections or change the sensor.
B4 sensor
failure
Plate heat exchanger temperature sensor is not
connected or broken down.
It is necessary to check sensor
connections or change the sensor.
VAV calibration fail Pressure sensors are not connected or broken. Check connections of the sensor or replace
the sensor.

UAB KOMFOVENT we reserve the right to make changes without prior notice
17
C3.1-16-01
It is possible to restore emergency overheating protection with button
“RESET”, only if before heater overheating cause has been claried and
eliminated.
If the unit is shut down and a failure text message is shown on the control
panel, the fault must be eliminated!
After failure has been eliminated and power supply connected the error messages should be deleted. How
ever if the failure has not been eliminated, unit either starts operating and after some time it stops again, or it
does not operate and failure message is indicated.
3. SAFETY REQUIREMENTS
• To avoid accidents and/or unit damage, only a trained technician must
carry out the connection.
• The appropriate Personal Protective Equipment (PPE) attire is worn
relative to the operation being carried out.
• Electrical equipment is rated, connected and earthed in accordance
with CE regulations.
Before performing any jobs inside the unit make sure that the unit is
stopped and disconnected from the electrical power supply.
• Earth must be installed according EN61557, BS 7671.
• The unit should be installed according to Installation and Maintenance
Manual.
• Before starting the unit, check correct position of air lters.
• Service maintenance should be carried out only in conformity with the
instructions specied herein below.



C3.1-16-01
UAB KOMFOVENT
VILNIUS Ozo g. 10, LT-08200
Tel. +370 (5) 2779 701
Mob. tel. 8-685 44658
KAUNAS Taikos pr. 149, LT-52119
Tel.: (8-37) 473 153, 373 587
Mob. tel. 8 685 63962
KLAIPĖDA Dubysos g. 25, LT-91181
Mob. tel.: 8 685 93706, 8 685 93707
ŠIAULIAI Metalistų g. 6H, LT-78107
Tel. (8-41) 500090,
mob. tel. +370 685 93700
PANEVĖŽYS Beržų g. 44, LT-36144
Mob. tel. 8 640 55988
EXPORT & SALES DEPARTMENT
Ph.: +370 (5) 205 1579, 231 6574
Fax +370 (5) 230 0588
GARANTINIO APTARNAVIMO SK. /
SERVICE AND SUPPORT
Tel. / Ph. +370 (5) 200 8000,
mob. tel. / mob. ph.: +370 652 03180
www.komfovent.com
PARTNERS
AT J. PICHLER Gesellschaft m. b. H. www.pichlerluft.at
AU Pacic HVAC www.pacichvac.com
BE Ventilair group www.ventilairgroup.com
ACB Airconditioning www.acbairco.be
CZ REKUVENT s.r.o. www.rekuvent.cz
CH
WESCO AG www.wesco.ch
SUDCLIMATAIR SA www.sudclimatair.ch
CLIMAIR GmbH www.komfovent.com/en/business/
more/contact-us/
DK UNIQ COMFORT ApS www.uniqcomfort.dk
AIR2TRUST www.air2trust.com
EE BVT Partners www.bvtpartners.ee
FR AERIA www.aeria-france.fr
GB ELTA FANS www.eltafans.com
HR Microclima www.microclima.hr
HU
AIRVENT Légtechnikai Zrt. www.airvent.hu
Gevent Magyarország Kft. www.gevent.hu
Merkapt www.merkapt.hu
IR Fantech Ventilation Ltd www.fantech.ie
IS Blikk & Tækniþjónustan ehf www.bogt.is
Hitataekni ehf www.hitataekni.is
NL Ventilair group www.ventilairgroup.com
DECIPOL-Vortvent www.vortvent.nl
NO Ventistål AS www.ventistal.no
Thermo Control AS www.thermocontrol.no
PL Ventia Sp. z o.o. www.ventia.pl
SE Nordisk Ventilator AB www.nordiskventilator.se
SI Agregat d.o.o www.agregat.si
SK TZB produkt, s.r.o. www.tzbprodukt.sk
ООО «АМАЛВА-Р»
Россия, Москва
ул. Выборгская д. 16,
стр. 1, 2 этаж, 206 офис
тел./факс +7 495 640 6065,
www.komfovent.ru
ООО «АМАЛВА-ОКА»
390017 г. Рязань
Ряжское шоссе, 20 литера Е, пом Н6
тел. +7 4912 950575, +7 4912 950672,
+7 4912 950648
www.komfovent.ru
ИООО «Комфовент»
Республика Беларусь, 220125 г. Минск,
ул. Уручская 21 – 423
Тел. +375 17 266 5297, 266 6327
www.komfovent.by
Komfovent AB
Ögärdesvägen 12B
433 30 Partille, Sverige
Phone +46 31 487752
www.komfovent.se
Komfovent Oy
Muuntotie 1 C1
FI-01 510 VANTAA
+358 (0) 40 8263 500
info_@komfovent.com
www.komfovent.com
Komfovent GmbH
Konrad-Zuse-Str. 2a, 42551 Velbert,
Deutschland
Mob. ph. +49 (0) 2051/6051180
www.komfovent.de
Komfovent SIA
Katlakalna iela 9,
LV-1073 Riga
Tel. +371 67 20 1572
Fakss +371 67 20 1570
www.komfovent.lv
Table of contents
Popular Control System manuals by other brands

NELSEN WATER
NELSEN WATER NRO ROC2HE-UL manual

Nordson
Nordson Eclipse EPC-30 Series instruction sheet

ATEN
ATEN VK112EU quick start guide

Varimixer
Varimixer Cinnabon 40 user manual

MojoDesk
MojoDesk Hand Control 2020 Operation instructions

quiko
quiko QK-CT219500 Instructions for installation, use and maintenance