1.4 Special conditions for safe use
1.4.1 General
For information on the flameproof joints please contact your KROHNE representative. No repairs
are permitted to the flameproof joints.
To avoid the risk of ignition as a result of electrostatic charging, the equipment can not be used
in locations that have:
•High charge generating processes,
•Mechanical friction and separation processes,
•Electron emission (e.g. near electrostatic coating equipment) may occur.
1.4.2 Additional notes for safe operation
Connection conditions
1. When the terminal compartment of the OPTISONIC 7300 C/…-Ex compact ultrasonic gas flow-
meter and the connection box of the OPTISONIC 7000...-Ex ultrasonic gas flow sensor is de-
signed as flameproof enclosure "Ex db”, the following must be complied with:
•The device shall be connected with suitable cable glands or conduit systems that meet the
requirements stipulated in IEC/EN 60079-1, sections 13.1 and 13.2, and for which a separate
test certificate has been issued. If the device is connected to conduit systems, the required
sealing device shall be provided immediately at the cable entrance(s) of the enclosure
•Cable glands and blanking plugs of simple design must not be used
•Openings that are not used shall be sealed in compliance with the specifications in IEC/EN
60079-1, section 11.9.
•If the electrical connection is made in a potentially explosive area, the connecting cable
(unconnected cable end) of the remote ultrasonic gas flow sensor OPTISONIC 7000 …-Ex,
shall be connected in an enclosure that meets the requirements of an approved type of
protection in accordance with IEC/EN 60079-0, section 1.
2. The connecting cable(s) delivered with the ultrasonic gas flow meter system, shall be fixed and
routed so that it will be adequately protected against damage. The cable is rated for a continu-
ous operating temperature of maximum 100°C. The maximum temperatures listed in the tem-
perature classification tables in the next Chapter are limited based on the maximum operating
temperature of the connecting cable(s), cable gland(s) and/or blind plug (only in case of a sin-
gle-beam sensor).
3. The OPTISONIC 7300 C/…-Ex and OPTISONIC 7000…-Ex shall be included in the local equipo-
tential bonding system of the potentially explosive area.
Components attached or installed (i.e. terminal compartments, bushings, Ex-type cable glands,
connectors, etc.) shall be of a technical standard that comply with the specifications on the cover
sheet and shall have a separate examination certificate. The operating conditions specified in the
component certificates must be complied with.