GB-2
GB
Checking the usage
DL..H, DL..N
For monitoring increasing and decreasing air or flue
gas pressure.
DL..H switches and locks off with rising pressure,
DL..N switches and locks off with falling pressure.
They can be unlocked using the manual reset.
This function is only guaranteed when used within
the specified limits– see page6 (Technical data).
Any other use is considered as non-compliant.
Type code
Code Description
DL Air pressure switch
10 – 150 Max. setting in mbar
A
K
Rp ¼, tube connection and hand wheel
Tube connection and hand wheel
H
N
Locks off with rising pressure
Locks off with falling pressure
GWith gold-plated contacts
-
-4
-5
-6
-9
Electrical connection
via screw terminals
via screw terminals, IP65
4-pin plug, without socket
4-pin plug, with socket
4-pin plug, with socket, IP65
K
T
T
N
Red/green pilot LED for 24 V DC/AC
Blue pilot lamp for 230 V AC
Red/green pilot LED for 230 V AC
Blue pilot lamp for 120 V AC
AExternal adjustment
Part designations
Test
1
2
3
5
4
1Upper housing section with cover
Lower housing section
Hand wheel
4M16 cable gland
5DL..H, DL..N with manual reset
Type label
DL
CE – 0085AP0466
2
13
D-49018 Osnabrück, Germany
Max. inlet pressure pmax. = withstand pressure, mains
voltage, ambient temperature, enclosure: see type
label.
Installation
CAUTION
Please observe the following to ensure that the DL
is not damaged during installation and operation:
– Check max. ambient temperature – see
page6 (Technical data).
– When using silicone tubes, only use silicone
tubes which have been sufficiently cured.
– Vapours containing silicone must not be allowed
to get into the housing.
– Condensation must not be allowed to get into
the housing. At subzero temperatures, malfunc-
tions/failures due to icing can occur.
– The service life will be shorter if subject to ozone
concentrations exceeding 200μg/m3. When
installing outdoors, place the DL in a roofed
area and protect from direct sunlight (even IP65
version).
– Avoid subjecting the DL to strong or violent
vibrations.
– In case of highly fluctuating pressures, install
a restrictor orifice, see page 4 (Restrictor
orifice for DL..A).
▷Ensure that there is sufficient installation space.
▷Ensure unobstructed view of the hand wheel.
▷Installation position as required, preferably with
vertical diaphragm. Then the switching point pS
corresponds to the scale value SK set on the
hand wheel. In other installation positions, the
switching pointpSwill change and no longer
correspond to the scale valueSK set on the
hand wheel. Check the switching point.
pS= SK
pS= SK + 0.18 mbar pS= SK - 0.18 mbar