GB-2
Checking the usage
DG
To monitor rising and falling pressure.
Positive
pressure
Negative pres-
sure
Differential
pressure
DG..S NH3, O2,
air – –
This function is only guaranteed when used within
the specified limits– see page4 (Technical data).
Any other use is considered as non-compliant.
Type code
Code Description
DG Gas pressure switch
6 – 500 Max. setting in mbar
SPositive pressure (NH3, O2)
GWith gold-plated contacts
-3
-4
-5
-6
-9
Electrical connection
via screw terminals
via screw terminals, IP 65
4-pin plug, without socket
4-pin plug, with socket
4-pin plug, with socket, IP 65
K2
T
T2
N
Red/green pilot LED for 24 V DC/AC
Blue pilot lamp for 230 V AC
Red/green pilot LED for 230 V AC
Blue pilot lamp for 120 V AC
AExternal adjustment
Part designations
1
2
3
4
1Upper housing section with cover
2Lower housing section
3Hand wheel
4M16 cable gland
Type label
Max. inlet pressure, mains voltage, ambient tem-
perature, enclosure: see type label.
DG
2
13
D-49018 Osnabrück, Germany
Installation
CAUTION
Please observe the following to ensure that the DG
is not damaged during installation and operation:
– As the temperature increases, the diffusion rate
of NH3through the diaphragm also increases
which can cause corrosion of the contacts. For
this reason, query the closed contacts for opening.
– The medium NH3must not condense as this can
lead to increased corrosion of the lower section
(pressure supply can become blocked) and de-
formation of the diaphragm (causing the switching
point to shift).
– Continuous operation at high temperatures accel-
erates the ageing of elastomer materials. In places
where a high thermal capacity is required, thermal
equipment trips must be installed upstream of
theDG.
– Use approved sealing material only.
– Check max. ambient temperature – see
page4 (Technical data).
– Condensation or vapours containing silicone must
not be allowed to get into the housing. At subzero
temperatures malfunctions/failures due to icing
can occur.
– The service life will be shorter if subject to ozone
concentrations exceeding 200μg/m3. When in-
stalling outdoors, place the DG in a roofed area
and protect from direct sunlight (even IP65 ver-
sion). To avoid condensation, the cover with pres-
sure equalization element can be used.
– Avoid subjecting the DG to strong or violent vibra-
tions.
▷Installation position as required, preferably with
vertical diaphragm. Then the switching pointpS
corresponds to the scale valueSK set on the
hand wheel. In other installation positions, the
switching pointpSwill change and no longer
correspond to the scale valueSK set on the
hand wheel. Check the switching point.
ps=SK
ps= SK + 0,18 mbar
ps= SK - 0,18 mbar
▷
The DG must not be in contact with masonry.
Minimum clearance 20mm.
▷Ensure that there is sufficient installation space.
▷Ensure unobstructed view of the hand wheel.
1 Disconnect the system from the electrical power
supply.
2 Shut off the medium supply.
3 Ensure that the pipeline is clean.