GB-3
For measuring negative pressure
▷Attach the tube to the negative pressure port (-).
The positive pressure port is left open to ventilate
the lower chamber of the diaphragm.
For measuring differential pressure
▷Attach the tube with the higher pressure to the
positive pressure port (+), attach the tube with the
lower pressure to the negative pressure port (-).
Adjusting the switching pressure pS
▷
The switching pressure can be adjusted using the
hand wheel with scale. The switching pressure
differs from the adjusted setpoint by a maximum
of ± 15%, when it has been set for increasing
pressure and with a vertical diaphragm.
1 Disconnect the system from the electrical power
supply.
2 Generate negative and/or positive pressure on
the CPS.
Remove the CPS cover.
4 Check the contact position with a measuring
instrument.
1
NC
2
NO
3
COM
NO
2
NC
1
COM
3
5 Set the switching pressure using the hand wheel.
Adjusting range
[Pa]
Switching hys-
teresis [Pa]
CPS 300 20 – 300 7 – 16
CPS 330 20 – 330 8 – 18
CPS 450 30 – 500 10 – 25
CPS 510 100 – 510 13 – 25
CPS 800 50 – 800 15 – 40
CPS 1000 100 – 1000 25 – 40
CPS 1100 100 – 1100 15 – 40
CPS 1600 400 – 1600 20 – 60
CPS 2400 200 – 2400 35 – 75
CPS 3000 250 – 3000 60 – 80
CPS 4000 500 – 4000 40 – 100
Wiring
CPS (silver contact)
24 – 250 V AC:
I = 0.05 – 5 A, cos φ = 1,
I = 0.05 – 1 A, cos φ = 0.6.
CPS..G (gold contact)
12 – 250 V AC:
I = 0.01 – 5 A, cos φ = 1,
I = 0.01 – 1 A, cos φ = 0.6;
12 – 48 V DC:
I = 0.01 – 1 A.
▷If the CPS..G has switched a voltage > 24 V and
a current > 0.1 A once, the gold plating on the
contacts will have been burnt through. It can then
only be operated at this power rating or higher
power rating.
▷In the case of low switching capacities, as 24 V,
8 mA, for example, we recommend using an RC
module (22 Ω, 1 μF) in air containing silicone or oil.
1 Disconnect the system from the electrical power
supply.
2 Remove the CPS cover.
▷
CPS 300, CPS 1000, CPS 3000: remove the
cover for the connection terminals.
Feed the cable through the cable gland into the
CPS.
COM
3
NC
1
NO
2
4
NO
2NC
1
COM
3
L1(+)
5 Replace the CPS cover and screw into place.
Maintenance
▷We recommend a function check once a year.
Accessories
Tube set
For connecting the CPS to an air duct.
Order No. 74919272