* AC Clamp Adaptor
* AC/DC Current Adaptor
* Transistorised Electronic Analog & Digital Insulation
Resistance Testers(upto 10 KV)
* Digital Sound Level Meter & Sound Level Calibrator
* Digital contact & Non-contact Type Tachometer
* Digital Non-contact (infrared) Thermometer &
Portable Infrared Calibrator
* Thermo Hygrometer / Anemometer
Digital Absolute pressure meter
* Wood, Paper & Grain Moisture Meter
* Distance Meter & Network Cable Tester
* Digital Hand Held Temperature Indicators
* Digital Lux Meter
* Thermal Imaging Camera
* Power Factor Regulator
* Maximum Demand Controller/Digital Power Meter
* Earth Resistance Tester
* Digital Panel Meters & DC Power Supplies
* Digital Storage / Analog Storage Oscilloscope.
* Coating Thickness Guage
* Process Calibrators & Multifunction Calibrators
* Gas Analysers & Waterproof Pen Testers
* Frequency Counter / Function Generator
* Phasing Sticks & High Voltage Detector
* Transducer & Transmitter
* Digital Milli Ohm Meter
* Solar Power Meter
* EMF/ELF Detector / RF Field Strength Meter
Digital Multimeter
Digital AC & AC/DC Clampmeter
LIST OF PRODUCTS
OPERATION
MANUAL
Digital Leakage
Clampmeter
MODEL KM 2008
®®
INDEX
Warning..............................................................
1) Introduction....................................................
2) Model Series..................................................
3) Electrical Signs..............................................
4) Technical Specifications.................................
5) Structure of the Leaker...................................
6) Operating Method..........................................
i) Start-up, Shutdown......................................
ii) Leaker Measurement...................................
iii) Peak Holding...............................................
iv) Hold, Storage and Acess Reading...............
7) Function Quick Look Up.................................
8) Display Example and Meaning.......................
9) How to change Battery...................................
10) Accessories..................................................
11) Test Certificate .............................................
12) Warranty.......................................................
01
02
03
03
03
05
06
06
06
08
08
09
09
10
10
11
12
01
Warning
! !
Thank you for purchasing our company's High Accuracy
Leakage Clampmeter. For better use of this product,
please:
vR e a d c a r e f u l l y t h e u s e r ' s m a n u a l
vFollow strictly safety rules and notes listed in this
manual.
=Under all circumstances, please pay special
attention to your safety in the course of using this
leakage clampmeter.
=Give heed to label texts and symbols on panel and
back plate of this leakage clampmeter.
=Please don't place and store this leakage in hot and
humid condition, locations with moisture condensation
and under direct sunlight for a long time.
=In case voltage of battery is low, please replace
batteries.
=If you expect not to use the leakage for a long time,
please take out batteries.
=When changing batteries, please pay attention to
the polarity of battery.
=Use, disassembly and maintenance of this leakage
shall be operated by authorized personnel.
=Do not use the meter if it is damaged. It can be d
dangerous.
=Users shall carry out operation based on warning
sign on leakage clampmeter and manual.
!
=Users shall carry out safety operation based on
instructions listed in this manual, e.g. and danger
signs on this manual.
=Please use mA to test leakage current (test by
clamping grounding line, single-phase line together).
02
I) INTRODUCTION
High Accuracy leakage clampmeter, model KM 2008, is
specially designed for measurement of AC leakage
current; It is a product with relatively small size, high
accuracy and perfect function compared with similar
instrument in the world. The meter could be widely used
in different fields such as electricity, communications,
meteorology, railroad, oilfield, construction, measurement,
scientific & research teaching institutes, industrial and
mining establishments.
Clamp core of this High Accuracy Leakage Clampmeter
adopts special alloy; in addition, with utilization of
magnetic shielding technology, it is almost free from
influences of external magnetic field so as to ensure high
precision, high stability and high reliability of perennial
continuous measurement.
This High Accuracy Leakage Clampmeter has RS232
interface. With the help of the software that we provide,
many function are available. For example, on-line
monitoring, historical data inquiry, active curve drawing,
indication of max, min and average value, alarm setting
and indication. There are also functions like saving to
documents and printing when connected to PC.
This High Accuracy Leakage Clampmeter could be
used for AC line current measurement and on-line current
measurement with voltage lower than AC600V; it also
have those functions as peaking holding, data holding
and data storage; with convenient use, it is an essential
tool for electrician safety testing.
03
III) ELECTRICAL SIGNS
Extremely dangerous! Operators shall strictly adhere
to safety rules; otherwise there would be dangers
of electric shock to cause personal injuries or casualties
Dangerous! Operators shall strictly adhere to safety rules;
otherwise there would be dangers of electric shock to
cause personal injuries or casualties.
!
Warning! Operators shall strictly adhere to safety rules;
otherwise personal injuries or equipment damages
might be caused.
!
Double insulation
AC
DC
IV) ELECTRICAL SPECIFICATIONS
Function
Power Supply
Test Mode
Display Mode
Dimension
LCD Dimension
Sampling Rate
Frequency
Range shift
Voltage Range
Clip-on CT, integral mode
Four digits LCD display
LWH : 175mm x 70mm x 38mm
35mm x 21.5mm display
domain : 32mm x 15mm
about 2 times/s
50/60Hz Automatically
Measurement of AC leakage current,
AC current and on-line measurement
Zn-Mn dry battery, 6F22,9V
Automatically
AC600V
Accuracy : 0 ~ 30mA : ±1.5%rdg±5dgts
(23°C±3°C, 30mA ~ 300mA: ±2%rdg±5dgts
Below 300mA ~ 30A : ±4%±5dgts
70% RH) 30A ~ 300A : ±4%±5dgts
04
RS232 Interface
Storage
Peak Hold
Data Stored in the memory of the
meter via RS232 uploaded to PC,
or on-line monitoring
99units, all used when display FULL
Push HOLD without release, the meter
will show the peak value.
Data Hold DH indicating the reading is hold
Out of Range
OL indicating the current is out of range
Auto Power-off
Indicating the battery voltage is
lower then 7.2V. Then the battery
have to be changed
5 Minutes after power on, it will power
off automatically to lower the power
consumption
Battery Voltage
Weight
Consumption
Temperature
and Humidity
120g (including the battery)
About 5mW
Working : 10°C~50°C, below 80% RH
Storage : -10°C~60°C, below 70% RH
Insulating :
Strength
AC2kV/rms (between the alloy of
the clamp and the housing)
Applicable
Safety Rules
IEC1010-1, IEC1010-2-032, pollution,
degree CAT III (600V)
Accessories
RS 232 Com cable
Software
Battery (6F22 9V)
User Manual
05
V) Structure of the Leakage Clampmeter
Clamp Leaker
HOLD
POWER
AC mA
1
2
3 4
5
6
7
8
9
1. Double Input Clamp
2. Upper Cover
3. Clamp Opening Lever
4. HOLD key
5. POWER key
6. LCD
7. RS232 Interface
8. Back cover
9. Battery cover
06
VI) OPERATING PROCEDURE
1. Start-up, Shutdown
Press POWER key to start up, LCD will begin to display;
Press the POWER key again, the meter will shut down.
After starting up for 5 minutes, LCD will flick notes that
the meter will shut down automatically; After flickering
for 30s, it will shut down formally to reduce battery
consumption. In case you have pressed POWER key
when LCD was flickering, the leaker will continue to
work for 5 minutes. If LCD is very dark after starting
up, it might be caused by low-voltage battery, in this
case, please change battery immediately.
2. Leaker Measurement
Dangerous! Please don't use it to measure current
higher than 300A; otherwise there would be risk of
electric shock to cause personal injuries or equipment
damages
!
High voltage, extremely dangerous! Operators shall
strictly keep to safety rules; otherwise there would be
risk of electric shock to cause personal injuries or
casualties.
1) Power on.
2) Press down trigger to open clamp head and clamp
to-be-measured conductors. (clamp heads must be
totally closed)
!
Clamp live wire and null line together to measure
leakage current of electrical equipment. (Note: 2 lines)
Clamp earth wire is to measure grounding line leakage
current of electrical equipment. (Note: Single line)
Clamp main line is to measure total current of that main
line. (Note: Single line)
07
(See Reference Diagram Fig-1, Fig-2)
Detect Leakage
hazards at
buried cable Detect safety
situation of operating
equipment
Detect Leakage
of grounding
wire
Fig-1 Test Leaker
Detect current
of main line
Detect current
consumption of
equipment 2
Fig-2 Test Total Current
!
Attention! For your safety, when measuring heavy current,
after confirmed the completion of correct operating test,
please move the meter away from measured conductor,
In locations with difficulty to read out data, please use the
data holding function. If [DH] symbol displayed, please
exit data holding state first, and then do the test.
Grounding wire
Grounding wire Grounding wire
08
3) Read LCD display data. In case "OL mA"symbol
was displayed, it means that current of measured
line is beyond the maximum limit of this meater
3. Peak Hold
Pressing HOLD key continually in the course of
measurement (More than 3 seconds), the leaker will
capture current peak values of lines. 3 five times;
release the key, it then will return to measuring state.
4. Hold, Storage and Access Reading
1) Pressing HOLD key for a short time in the course of
measurement (less than 3 seconds), DH symbol will
display, the meter will hold current measuring data
and automatically stored in the memory with a unit
ID; press HOLD key again to release the hold state,
and the meter continues its measuring; in case stored
data reached to 60 groups, press HOLD key again,
the "FULL" symbol will display, which means storage
memory is full; press HOLD key to cancel "FULL"
flickering and return to measuring mode.
2) Press HOLD + POWER keys to enter into data access
mode and display shows Unit 1 storage data automatically;
and then press HOLD key again to turn the page of
stored data; NULL will display when there is no data in
stored in the memory, press POWER key to exit data
access mode.
3) After entering into data access mode, press HOLD key
for more than 3 seconds will clean up all stored data;
when the leaker displaying "dEL" symbol, it means that
it has finished cleanup process, and then return to
measuring state automatically.
09
VII) Function Quick Look Up
POWER Key Short PressPower on/Shutdown/Exit
HOLD Key Short Press Data Hold/Release/Storage
HOLD Key Pressing for
more than 3s
Peak Hold (at measuring
mode)
HOLD Key Pressing for
3s
Clear Data (at access data
mode)
HOLD Key+ POWER
Key
Data access/Turn pages
(HOLD Key)
VIII) Display Example and Meaning
1. ---- Measured leakage current is 0.25mA.
AC mA
0.25
2. ---- Low battery, please change.
AC mA
6.30
-+
3. ---- Measured leakage current is 0.25mA is held and
automatically stored unit ID is NO.03.
AC mA
5.00
DH 03
4. ---- Access the unit 3 of the stored Data
AC mA
5.00
03
10
IX How to Change Battery
!
Warning! It is dangerous to carry out test when the
battery cover plate is not on its position
Please pay attention to the polarity of battery to avoid
damaging the meter.
Change the low battery in time
If you expect not to use the meter for a long time,
please remove the battery for storage.
-+
1) " " symbol means the battery is undercharge and
need to be replaced.
2) Press POWER key to shut down the meter; before
opening the battery cover, please confirm the meter
is in off position, and then replace with qualified new
battery; special attention shall be paid to the polarity
of battery; at last, cover battery cover plate.
11
QC
PASS
KUSAM-MECO
TEST CERTIFICATE
DIGITAL LEAKAGE
CLAMPMETER
MODEL NO. __________
KM 2008
SERIAL NO. ___________
MUMBAI
DATE: ___________
ISO 9001
REGISTERED
The instrument has been calibrated by using
equipment which has already been calibrated
to standards traceable to national standards.
This Test Certificate warrantties that the
product has been inspected and tested in
accordance with the published specifications
WARRANTY
Each “KUSAM-MECO” product is warranted to be free from
defects in material and workmanship under normal use &
service. The warranty period is one year (12 months) and
begins from the date of despatch of goods. In case any defect
occurs in functioning of the instrument, under proper use, within
the warranty period, the same will be rectified by us free of
charges, provided the to and fro freight charges are borne by
you.
This warranty extends only to the original buyer or end-user
customer of a “KUSAM-MECO” authorized dealer.
This warranty does not apply for damaged Ic’s, Burn't PCB's,fuses,
disposable batteries, carrying case, electrodes probes, clamps.
cables or to any product which in “KUSAM-MECO’s” opinion, has
been misused, altered, neglected, contaminated or damaged by
accident or abnormal conditions of operation or handling.
“KUSAM-MECO” authorized dealer shall extend this warranty on
new and unused products to end-user customers only but have no
authority to extend a greater or different warranty on behalf of
“KUSAM-MECO”.
“KUSAM-MECO’s” warranty obligation is limited, at option, free of
charge repair, or replacement of a defective product which is
returned to a “KUSAM-MECO” authorized service center within
the warranty period.
THIS WARRANTY IS BUYER’S SOLE AND EXCLUSIVE REMEDY AND IS IN
LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING
BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY
OR FITNESS FOR A PARTICULAR PURPOSE. “KUSAM-MECO” SHALL
NOT BE LIABLE FOR ANY SPECIAL, INDIRECT, INCIDENTAL OR
CONSEQUENTIAL DAMAGES OR LOSSES, INCLUDING LOSS OF DATA,
ARISING FROM ANY CAUSE WHATSOEVER.
All transaction are subject to Mumbai Jurisdiction.
12

Other Kusam-meco Measuring Instrument manuals

Kusam-meco KM 2783 User manual

Kusam-meco

Kusam-meco KM 2783 User manual

Kusam-meco KM 1120 User manual

Kusam-meco

Kusam-meco KM 1120 User manual

Kusam-meco KM 63A User manual

Kusam-meco

Kusam-meco KM 63A User manual

Kusam-meco KM 035 User manual

Kusam-meco

Kusam-meco KM 035 User manual

Kusam-meco KM 2720 User manual

Kusam-meco

Kusam-meco KM 2720 User manual

Kusam-meco KM 061 User manual

Kusam-meco

Kusam-meco KM 061 User manual

Kusam-meco KM 711 User manual

Kusam-meco

Kusam-meco KM 711 User manual

Kusam-meco 500HP User manual

Kusam-meco

Kusam-meco 500HP User manual

Kusam-meco KM 1002 User manual

Kusam-meco

Kusam-meco KM 1002 User manual

Kusam-meco KM 078 User manual

Kusam-meco

Kusam-meco KM 078 User manual

Kusam-meco 108 User manual

Kusam-meco

Kusam-meco 108 User manual

Kusam-meco KM 033 User manual

Kusam-meco

Kusam-meco KM 033 User manual

Kusam-meco KM 2820EL User manual

Kusam-meco

Kusam-meco KM 2820EL User manual

Kusam-meco KM 088 User manual

Kusam-meco

Kusam-meco KM 088 User manual

Kusam-meco KM 2234BL User manual

Kusam-meco

Kusam-meco KM 2234BL User manual

Kusam-meco 2700 User manual

Kusam-meco

Kusam-meco 2700 User manual

Kusam-meco KM 039F User manual

Kusam-meco

Kusam-meco KM 039F User manual

Kusam-meco KM 2009 User manual

Kusam-meco

Kusam-meco KM 2009 User manual

Kusam-meco KM 175D User manual

Kusam-meco

Kusam-meco KM 175D User manual

Kusam-meco 288SVD User manual

Kusam-meco

Kusam-meco 288SVD User manual

Kusam-meco KM 63 User manual

Kusam-meco

Kusam-meco KM 63 User manual

Kusam-meco KM-LUX-200K User manual

Kusam-meco

Kusam-meco KM-LUX-200K User manual

Kusam-meco KM 2008A User manual

Kusam-meco

Kusam-meco KM 2008A User manual

Kusam-meco KM 071 User manual

Kusam-meco

Kusam-meco KM 071 User manual

Popular Measuring Instrument manuals by other brands

Abus TVVR36301 quick start guide

Abus

Abus TVVR36301 quick start guide

Promax PROLITE-55 user guide

Promax

Promax PROLITE-55 user guide

Base Line 12-0235 Standard instruction manual

Base Line

Base Line 12-0235 Standard instruction manual

Global Test Supply 5 Series quick start guide

Global Test Supply

Global Test Supply 5 Series quick start guide

Lake Shore Model 421 user manual

Lake Shore

Lake Shore Model 421 user manual

Wyrestorm TT-KIT-4K instruction manual

Wyrestorm

Wyrestorm TT-KIT-4K instruction manual

Delta REVEZ-HD-TRIO DVB-T/T2 user manual

Delta

Delta REVEZ-HD-TRIO DVB-T/T2 user manual

EMU Check Short manual

EMU

EMU Check Short manual

Next Century RR4-TR Operation and installation guide

Next Century

Next Century RR4-TR Operation and installation guide

PerkinElmer DSC 6000 Installation and hardware guide

PerkinElmer

PerkinElmer DSC 6000 Installation and hardware guide

ACU-RITE 00256 instruction manual

ACU-RITE

ACU-RITE 00256 instruction manual

Applied Instruments DIRECTV SWM SL5S KaKu Application note

Applied Instruments

Applied Instruments DIRECTV SWM SL5S KaKu Application note

J-TECH Solar Auxiliary Power Unit Operator's guide

J-TECH

J-TECH Solar Auxiliary Power Unit Operator's guide

Aqualytic SD 60 operating manual

Aqualytic

Aqualytic SD 60 operating manual

S.E. International RADIATION ALERT Sentry manual

S.E. International

S.E. International RADIATION ALERT Sentry manual

PureLink HDG 2.0 owner's manual

PureLink

PureLink HDG 2.0 owner's manual

Axio MET AX-5002 user manual

Axio MET

Axio MET AX-5002 user manual

Digi-Sense 20250-14 user manual

Digi-Sense

Digi-Sense 20250-14 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.