Labkotec SET/V Specification sheet

SET/V D27093AE-2
Operation and installation manual
We reserve the right to any changes. Copyright © 2019, Labkotec Oy
2(5)
SYMBOLS
To be considered in installations in po-
tentially explosive atmospheres.
Warning/Attention
1. GENERAL
SET/V is a level switch sensor that is to be con-
nected to analogical and digital SET control units of
Labkotec. Operating principle of the sensor is based
on the measurement of the vibration of the sensor.
Sensor is suitable to be used as a high level alarm
for liquid tanks, for example. Typical applications of
SET/V sensor include oil and grease separators.
The SET/V has been certified according to the
ATEX Directive in equipment category 1 and it can
be installed in potentially explosive atmospheres in
zoned areas 0, 1, and 2.
Figure 1. Dimensional drawing of the SET/V sensor
Figure 2. Application: high level alarm for an oil
separator
2. TECHNICAL DATA
Control unit:
LevelSET S and SET control units
by Labkotec Oy
Signal
Operating vol-
tage
Digital and analogical 7mA/13mA
8V…16V (DC)
Cable
Shielded oil-proof cable 2 x 0.75
mm2. Standard length 5 m. Other
lengths optional. The max. length
of the fixed cable is 15 m. Can be
extended with a shielded cable.
The recommended maximum
cable loop resistance is 75 Ω.
Materials
PA, PVC, aluminum, NBR
Temperature
range
Operation: 0…+60°C
Safety: -30…+60°C
EMC
Emissions
IEC/EN 61000-6-3
Immunity
IEC/EN 61000-6-2
IP-classification
IP68
Ex-classification
II 1 G Ex ia IIB T5 Ga
EESF 19 ATEX 005X
IECEx EESF 19.0005X
Ui = 16 V
Pi = 400 mW
Ii = 80 mA
Ci = 3500 pF
Li = 85 μH
Operating princi-
ple
Vibration
Manufacturing
year:
Please see the
serial number on
the type plate.
xxx x xxxxx xx YY x
where YY = manufacturing year
(e.g. 19 = 2019)
The sensor may be installed in potentially
explosive atmospheres of zones 0, 1, and 2
with the following special conditions (X):
–The ambient temperature is –30…+60°C.
–The risk of electrostatic charge must be observed!
Standards to be considered in the installation:
IEC/EN 60079-25 Intrinsically-safe electrical systems "i",
and/or IEC/EN 60079-14 Electrical installations in haz-
ardous areas. If the cabling is voltage-tested, the sensor
must be detached from the system.

SET/V D27093AE-2
Operation and installation manual
We reserve the right to any changes. Copyright © 2019, Labkotec Oy
3(5)
3. CONNECTIONS AND INSTALLATION
The SET/V sensor is equipped with a shielded 2-
wire cable. The numbered wires 1 and 2 of the cable
are connected to the corresponding connectors (1 =
+, 2 = –) in the control unit. Always check the con-
nections from the installation and operation manual
of the control unit as well.
In the example shown in figure 4A, an LJB2-78-83
junction box has been used to connect the cabling
to the equipotential bonding.
In figures 4B and 4C, equipotential bonding is not
available. The shield is connected to the appropriate
connector in the supply device.
In these kinds of arrangements, it must be
ensured that the electrostatic charges do not
cause a hazard. Make sure in the installation that
the device and cabling are not close to a strong
current or other installations and that they are not
exposed to strong stream flows, mechanical
abrasions, or impacts.
The cable may be shortened or extended with a
junction box, if necessary.
The sensor is installed by hanging it from its cable at a
suitable height so that the switch data is received as
the surface level reaches the sensing element.
SET-1000 OR SET-2000 CONTROL UNIT:
Figure 3. Settings of SET-1000 and SET-2000
control units and selection of SET/V sensor.
Figure 4. Installation example in an oil separator.

SET/V D27093AE-2
Operation and installation manual
We reserve the right to any changes. Copyright © 2019, Labkotec Oy
4(5)
4. OPERATION
This chapter provides a general description of the
operation of the alarm in different situations. For a
more detailed description, please refer to the man-
ual of the control unit in use.
5. OPERATION TEST
Always check the correct operation of the alarm af-
ter the installation and after making the connections.
You should also check the operation every time the
separator is emptied or at least once a year.
Testing the
operation
1. The sensor is in the air. The de-
vice should be in normal mode
(see chapter 4).
2. Lower the sensing element of the
sensor into the water or oil. The
“Tank full” alarm should be issued
(see chapter 4).
3. Lift the sensor in the air. The
alarm should stop after a while.
Clean the sensor before installing
it into the separator.
If the sensor does not function as described, check
the device settings from the control unit manual or
contact the representative of the manufacturer.
6. SERVICE AND REPAIR
The sensor must be cleaned and tested when emp-
tying the storage chamber and in connection with
the annual maintenance. A mild detergent (e.g.
washing-up liquid) and a scrubbing brush can be
used for cleaning the sensor, if necessary.
In fault situation check the cabling and connections
of possible short-circuits or interruptions, then, if
necessary, measure the sensor current and com-
pare it with current values below.
Attention! If the sensor is located in an explosive at-
mosphere, the multimeter must be Exi-approved!
Sensor (clean/dry) in the air:
5 –8 mA
Sensor in the water/oil:
10 –14 mA
Also measure the output voltage of control unit. It is
typically between 10 –12 V with Labkotec Oy’s
SET-control units. See details from the manual of
the control unit.
In case of queries, please contact Labkotec Oy’s
service.
During maintenance procedures (such as servic-
ing the oil/fuel separator systems), the sensor
should not be lifted out of the separa-
tor tank or installed back until there is
water in the tank.
The instructions concerning the inspection and
maintenance of Ex equipment contained in stand-
ards IEC/EN 60079-17 and IEC/EN 60079-19
should be observed when executing service, in-
spection, or repair procedures.
LevelSET S CONTROL UNIT:
See settings of LevelSET S control unit from its Op-
eration and Installation Manual.
Write down the 5 digit address from the
Code field of the sensor type plate in the in-
stallation phase for later use. This address
is required if the sensor has to be re-connected to
the LevelSET S system or another control unit.
Figure 5. Type plate of SET/V sensor
Normal
mode
The SET/V high level sensor is en-
tirely in the air.
The alarm indicator lights are off.
The relays are energized.
Tank full
The sensing element of the SET/V
sensor is immersed in liquid.
The Overfill indicator is on.
The relays are de-energized.
The relays are de-energized.
Once the alarm is off, the alarm indi-
cator lights switch off, the buzzer
stops, and the relays are energized.
Fault
alarm
The sensor is broken, there is a sen-
sor cable break or a short circuit, or
the sensor signal current is not recog-
nized (digital system).
The sensor circuit Fault indicator is on.
The buzzer sounds
The relays are de-energized.