LEDVANCE LMS Sensor Value Infrared
3
black
score dimension 148 x 210 mm
How to Install:
a. Switch off the power.
b. Unload the transparent vinyl cover which is at the bottom of the sensor.
c. Loose the screws in the connection terminal, and then connect the power lead to connection terminal of sensor
according to wire connection diagram.
d. Install back the transparent vinyl cover into the original location.
e. Fold the metal spring of the sensor upwards until they are in “I” position with sensor, and then put the sensor
into the hole or installation box with 61.5mm cut-out hole on the ceiling. Releasing the spring, the sensor will be
set in this installation position.
f. After finishing installing, turn on the power and then test it.
Wire Connection diagram:
(See the right figure)
SENSOR INFORMATION
Product Features:
a. Infrared motion sensor with integrated photocell sensing function can help to save power consumption via turn
on and turn off the power according to its setting; It detects human motion within its detection range.
b. Infrared motion sensor cannot receive the induction if there is glass, wood or metal materials in between within
detection range;
c. Selectable time delay period from 10 seconds to 7 minutes via knob switch;
d. Selectable daylight sensing level from 10 lux to 2000 lux via knob switch.
Product Specification:
a. Detection method: Infrared motion sensor with photocell integrated
b. Power Input: 220-240V/AC
c. Input Frequency: 50/60Hz
d. Detection Range: 360°
e. Installing Height: 2.2~4m
f. Ambient Light (Selectable): <10-2000LUX
g. Time-Delay (Selectable):
• Min.:10sec±3sec;
• Max.:7min±2min;
h. Nominal Power Consumption: 0.9W
i. Transmission Power: <10mW
j. Maximum Rated Load:
• 1200W (incandescent lamp)
• 300W (energy-saving / led-lamp)
k. Detection Motion Speed: 0.6~1.5m/s
l. Detection Distance (selectable): 6m (<24°C)
Selectable Functions via Knob:
a. Selectable daylight luminance level: Sensing luminance level can work both in the daytime and at night when
you select the “sun” position (max) via knob. It can work in the environment that the luminance is less than
10LUX when it is adjusted to the “-” position (min). As for the adjustment pattern, please refer to the testing
pattern.
b. Time-Delay is added continually: When sensor receives the second induction signal after the first induction, it
will perform the time delay period again according to the 2nd induction.
c. Selective time delay period length: It can be set according to the consumer’s desire. The minimum delay period
is 10sec±3sec. The maximum delay period is 7min±2min.
Installation Guide and product diagram
INSTALLATION ADVICE:
As the detector responds to changes of temperature, please avoid the following situations:
a. Avoid directing the detector towards objects with highly reflective surfaces, such as mirrors etc.
b. Avoid mounting the detector near heat sources, such as heating vents, air conditioning units, light etc.
c. Avoid directing the detector towards objects that may move in the wind, such as curtains, tall plants etc.
Testing Before Using:
a. Turn the TIME knob anti-clockwise to the minimum (10s). Turn the LUX knob
clockwise to the maximum (sun).
b. Switch on the power; the sensor and its connected lamp will have no signal at
the beginning. After warm-up 30sec, the sensor can start work. If the sensor
receives the induction signal, the lamp will turn on. While there is no another
induction signal any more, the load should stop working within 10sec±3sec and
the lamp would turn off.
c. Turn LUX knob anti-clockwise on the minimum (-). If the ambient light is more than 3LUX, the sensor would not
work, and the lamp stop working too. If the ambient light is less than 10LUX (darkness), the sensor would work.
Under no induction signal condition, the sensor should stop working within 10sec±3sec.
Note: When testing in daylight, please turn LUX knob to (SUN) position, otherwise the sensor lamp could not
work! If the load is >60W, the distance between lamp and sensor should be longer than 60cm.
Step 1 Step 2 Step 3
Height of installation: 2.2-4m Detection Distance: Max.6m
2.2-4m
3m 3m
Max:3m Max:3m
360°
11080856 MS-SV-INF-CR-360-230V-IP20 UI LEDV v3.indd 3 4/9/2019 4:54 PM