manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. LEGRAND
  6. •
  7. Smoke Alarm
  8. •
  9. LEGRAND 643084 User manual

LEGRAND 643084 User manual

Specifications:
Cat No. 643084 (Ionisation)
643085 (Photoelectric)
Supply Voltage 230-240V a.c.
Frequency 50Hz
Backup Battery 9V battery included (recommended
replacement: Energizer 522, Duracell
MN 1604 or MX 1604)
Temperature Range +5oC to ~ +50oC
Humidity Range 10-95% at 20oC
Siren Sound Level >85 dB at 3 metres
Installation:
WARNING: In the interests of safety, a licensed electrician, in accordance with
the relevant requirements of AS/NZS 3000, must install this smoke alarm and
all wiring.
This alarm must be wired to a continuous 230-240V a.c. 50Hz circuit. Ensure
any switching device cannot inadvertently override the unit.
NOTE: See overleaf for recommended locations of alarms
INSTALLER PLEASE NOTE:
n Before you connect the mains power, check wiring polarity.
nIf the alarm ‘chirps ’ press the Test button to check the battery condition.
Replace battery if necessary.
nIf ‘chirps ’ persist return smoke alarm to your supplier.
WIRING INSTRUCTIONS:
n This smoke alarm can be interconnected with other 643084 or 643085
smoke alarms. Interconnection with other brands or models may cause
damage or result in a shock or fire risk.
n Up to a limit of 20 smoke alarms may be interconnected.
n Not interconnectable with HPM 645/3 ionisation smoke alarm
n There are four terminals in the supply terminal block, marked A, I, N and
E/LOOP. It is important that the alarm be wired correctly to ensure correct
operation. Incorrect wiring to the smoke alarm will damage the unit and
invalidate the warranty. See wiring diagrams.
n A maximum length of 300 metres of wire can be used in interconnecting
smoke alarms. Spacing between interconnected smoke alarms must not
exceed 30m per alarm.
n Interconnected smoke alarms must be connected to the same final
sub-circuit.
n Do not use any wire that could later be confused with the normal house
wires for the interconnect wire. For example, green/yellow earth wire.
n Do not connect AC power wires to I interconnect terminal. This may
damage smoke alarms.
n Do not connect the I interconnect wire to any device, except the
I interconnect terminal of another 643084 or 643085 smoke alarm or
interface 643086. Otherwise, smoke alarms will be damaged.
n Smoke alarms should be interconnected only within the confines of a
single-family living unit. If smoke alarms are interconnected between
different units, there may be excessive nuisance alarms. Residents may not
be aware that smoke alarms are being tested or that it is a nuisance alarm
caused by cooking, etc.
PROFESSIONAL IONISATION / PHOTOELECTRIC SMOKE ALARM
INSTALLATION INSTRUCTIONS
IMPORTANT: READ ALL INSTRUCTIONS BEFORE INSTALLATION.
NO USER SERVICEABLE PARTS INSIDE THIS SMOKE ALARM.
Do not attempt to repair the smoke alarm yourself.
I
A
N
IA
N
E/LOOP
IA
N
E/LOOP
40mm
10mm
CEILING / WALL JUNCTION
TYPICAL MULTIPLE
FLOOR INSTALLATION
SINGLE FLOOR
APEX OF
SLOPING
CEILING CEILING
ACCEPTABLE HERE
BEDROOMBEDROOM
BEDROOM W/C
KITCHEN DINING
BATH
BD/RM HALL BD/RM
KITCHEN
RUMPUS
LOUNGE
ROOM
LOUNGE ROOM
Smoke alarms for minimum protection.
Smoke alarms for additional protection.
BEST
HERE NEVER
HERE
HEAT &
SMOKE
FROM
FIRE
HEAT & SMOKE
FROM FIRE
DEAD AIR
SPACE
DEAD
AIR SPACE
SIDE WALL
300mm min
300mm min
600mm min
1500mm max
500mm min
500mmmin
BEST
HERE
BEST
HERE
THIS DEVICE CONTAINS A SMALL
AMOUNT OF RADIOACTIVE MATERIAL.
WARNING:
49mm Ø147mm
Red LED
Green LED
84mm
50mm
84mm
84mm mounting
centre suitable for
standard mounting
brackets
Applicable to 643084 Ionisation alarm only.
Green LED
n AC Mains-ON Indicator: indicates that the unit is operating with AC power. If
this LED goes out, it indicates that the AC power is off.
False Alarm Hush Control Feature:
n This smoke alarm has the capability of being temporarily desensitised for
approximately 10 minutes.
n If the smoke alarm is sounding it can be desensitised by pressing the
“HUSH/TEST” button on the smoke alarm cover.
n After pressing the “HUSH/TEST” button, the alarm will silence immediately
and red LED will flash every 15 seconds for approximately 10 minutes to
indicate the alarm is in the temporary desensitised condition.
n The smoke alarm will automatically reactivate after approximately 10
minutes and sound the alarm if particles of combustion are still present.
n The “HUSH” feature may be used repeatedly until the air has cleared.
TESTING
NOTE: Before testing, make sure that the smoke alarm is connected to AC
power supply (make sure the green LED is ON) and there is a 9V battery
properly installed.
n Test alarm by pushing and holding the test “HUSH/TEST” button for 5
seconds. This should sound the alarm if all electronic circuitry and horn are
working.
n If no alarm sounds, check battery wiring, fuses or circuit breaker and make
certain that alarm is connected to a continuous final sub-circuit.
n With interconnected units, holding test button down on one unit will cause
all connected units to sound.
n Continuous chirping or erratic noise or low sound from an alarm may
indicate a defective alarm.
Smoke alarm should be tested on a monthly basis. To accurately test the
integrity of the sensing chamber use a smoke detector (aerosol) tester.
NOTE: After the above alarm test with the ‘HUSH/TEST’ button, the alarm will
be desensitised for about 10 minutes. ONLY DO THE SMOKE AEROSOL TEST
AFTER THIS DESENSITISED PERIOD.
WARNING: Do not apply excessive force on the “HUSH/TEST” button this may
damage the smoke alarm and may void the warranty.
WARNING: Never use an open flame of any kind to test your alarm. You may
damage the alarm or set fire to your home. The built-in test switch enables
testing of all electronic components and the horn.
MAINTENANCE
The smoke alarm is virtually maintenance free. However, under dusty or
greasy conditions, a vacuum cleaner may be used to clean the exterior of unit
(including slots on cover). DO NOT IMMERSE IN OR SPRAY WITH HOUSEHOLD
CLEANERS.
If the unit gives a chirping sound every 60sec the battery may need to be
replaced.
Mounting Instructions:
1. Write down the date of installation on label provided.
2. Strip the Active/Neutral and Interconnect (if used) wires back to the strip
length shown above.
3. Connect the wires to the correct terminals on the base as indicated and
ensure the screws are fully tightened.
4. Clip the flap closed to prevent accidental contact with the live terminals.
5. Screw the mounting base to the ceiling or wall using the plugs and screws
provided or No.6/No.8 superscrews.
6. Install the 9V battery. The smoke alarm will not latch to the base unless
battery is installed.
7. Turn on the mains power and check the green and red LED function. Green
LED should glow to show main power present. Red LED will pulse every 60
seconds to indicate correct operation and the 9V battery is OK.
8. Press the Test/Hush button for 5 seconds to check the alarm works.
9. When installing onto a wall the mounting hinge must be on left hand side.
Battery:
BATTERY INSTALLATION
n The smoke alarm uses one 9V battery to automatically provide
back-up power to the alarm if AC power fails. The battery will operate the
alarm for approximately one to three months with AC power off.
n USE ONLY BATTERIES AS SPECIFIED IN THE PRODUCT LABEL. USE OF A
DIFFERENT BATTERY MAY HAVE A DETRIMENTAL EFFECT ON OPERATION
OR MAY CAUSE THE BATTERY TO EXPLODE.
n USE ONLY THE FOLLOWING 9-VOLT ALKALINE BATTERIES FOR
REPLACEMENT: EVEREADY/ENERGIZER 522 DURACELL MN1604, MX1604
n Battery can only be inserted in one direction. Ensure polarity is correct.
BATTERY REPLACEMENT
n To replace battery, unlatch unit from mounting base and remove the battery
from compartment. Replace the old battery with a fresh one and close unit.
Verify that the green LED is on.
n To ensure proper operation, the battery should be replaced once a year.
n Smoke alarm cannot be closed properly without battery in place.
PROFESSIONAL IONISATION / PHOTOELECTRIC SMOKE ALARM
INSTALLATION INSTRUCTIONS
Installation:
n Terminals at back of mounting base are marked as follows:
A - Active I - Interconnect N - Neutral E/Loop - Earth or Loop
EXAMPLE OF MULTIPLE ALARM WIRING:
When interconnected, all smoke alarms will sound upon activation. However,
only the originating smoke alarm will have flashing Red LED.
WARNING: Connecting the Interconnect terminal to any supply conductor will
result in damage to the alarm, failure to operate or shock hazard and will void
the warranty of the alarm.
WARNING: Under no circumstances must an insulation resistance test be
carried out on a circuit to which a smoke alarm is connected.
The test could cause irreparable damage to the internal circuitry of the smoke
alarm and make it inoperative.
The warranty would be void under such circumstances.
I
A
N
IA
N
E/LOOP
IA
N
E/LOOP
40mm
10mm
CEILING / WALL JUNCTION
TYPICAL MULTIPLE
FLOOR INSTALLATION
SINGLE FLOOR
APEX OF
SLOPING
CEILING CEILING
ACCEPTABLE HERE
BEDROOMBEDROOM
BEDROOM W/C
KITCHEN DINING
BATH
BD/RM HALL BD/RM
KITCHEN
RUMPUS
LOUNGE
ROOM
LOUNGE ROOM
Smoke alarms for minimum protection.
Smoke alarms for additional protection.
BEST
HERE NEVER
HERE
HEAT &
SMOKE
FROM
FIRE
HEAT & SMOKE
FROM FIRE
DEAD AIR
SPACE
DEAD
AIR SPACE
SIDE WALL
300mm min
300mm min
600mm min
1500mm max
500mm min
500mmmin
BEST
HERE
BEST
HERE
Operation, Testing and Maintenance:
OPERATION
The smoke alarm is operational once all wires are properly connected, the
smoke alarm is correctly installed on the mounting base, battery inserted and
the alarm has been tested. There are two LED indicators. Each of them has a
unique function:
Red LED
n Stand-by condition: will flash once approximately every 60 seconds to
indicate unit is functioning properly.
n Alarm condition: will flash quickly when unit goes into alarm. The flashing
red LED and pulsating alarm will continue until the air is cleared. For
interconnected units, the originating smoke alarm red LED will be flashing.
All other units will sound but not flash.
Repairs and Services:
n If the smoke alarm is defective in any way, do not tamper with the unit.
See warranty for instructions on in-warranty returns. Note: NO USER
REPLACEABLE PARTS INSIDE.
643084 only:
n The smoke alarm uses a very small amount of radioactive element that
is safely contained within the sealed source.
NOTE: When this product is no longer required dispose by returning
to HPM Legrand office in your state capital or your state’s Health
Department. Alternative disposal is not permitted unless accepted
under your state’s Health and Safety Regulations.
n Please note: It is illegal to send radioactive material through Australia
Post. Check for similar conditions with any forwarding agency before
sending this article.
WARNING: DO NOT TAMPER WITH RADIOACTIVE SOURCE.
Mobile Home Installation:
n Modern mobile homes have been designed and insulated to be energy
efficient. Install smoke alarms as recommended (refer to RECOMMENDED
LOCATIONS).
n In mobile homes that are not well insulated extreme heat or cold can
be transferred from the outside through poorly insulated walls and roof.
This may create a thermal barrier that can prevent smoke from reaching
a smoke alarm mounted on the ceiling. In such units, install the smoke
alarm on inside partition between 300mm and 600mm from the ceiling.
n If you are not sure about the insulation in your mobile home, or if you notice
the walls and ceilings are either hot or cold, install alarm on an inside wall.
For minimum protection, install one alarm close to the bedrooms.
For additional protection, see SINGLE FLOOR plan. We recommend that the
smoke alarm be tested after each journey.
Installation of Smoke Alarms:
IMPORTANT: INCORRECT ORIENTATION OF SMOKE ALARMS MAY
DECREASE OPERATIONAL EFFECTIVENESS
Recommended Locations of Alarms:
n Install at least one alarm for each separate sleeping area. Try to cover the
exit path as the bedrooms are usually farthest from an exit. If there is more
than one sleeping area, install additional alarms in each sleeping area in the
immediate vicinity of bedrooms.
n Install at least one alarm to protect any stairway as stairways act like
chimneys for smoke and heat.
n Install at least one alarm on every floor level.
n Install an alarm in every room where a smoker sleeps as additional
protection.
n Install an alarm in every room where electrical appliances are operated (i.e.
portable heaters or humidifiers) as additional protection.
n Install an alarm in every room where someone sleeps with the door closed
as additional protection. The closed door may prevent the alarm from
waking the sleeper.
n Smoke, heat and other combustion products rise to the ceiling and spread
horizontally. Mounting the alarm on the ceiling in the centre of the room
places it closest to all points in the room. Ceiling mounting is preferred in
ordinary residential construction.
n For mobile home installation select location carefully to avoid thermal
barrier that may form at the ceiling. For more details see Mobile Home
Installation.
n When mounting an alarm on the ceiling install it at a minimum of 300mm
from the side wall and 600mm from any corner (see diagram).
n When mounting an alarm on a wall, install it at a minimum of 300mm from
the ceiling level but not more than 600mm from the ceiling level and any
corner (see diagram) NOTE: The performance of smoke alarms mounted on
a wall is unpredictable, and is not recommended when ceiling mounting can
be implemented.
n When mounting an alarm at the apex of a sloping ceiling it should be located
a minimum of 500mm from the apex but should not exceed 1500mm (see
diagram).
n Locate smoke alarm at both ends of a bedroom hallway if the hallway is
more than 9m long.
Avoid These Locations:
Do not place alarm in the following locations:
n The garage. Gas released when you start your automobile may cause false
alarms.
n In front of forced air supply ducts used for heating and air-conditioning and
other high airflow areas.
n In the peak of an “A” frame type of ceiling.
n In areas where temperatures may fall below +5ºC or rise above +50ºC.
n In dusty areas, dust particles may cause smoke alarm to false alarm or fail
to alarm.
n We do not recommend installation in or directly adjacent to areas of high
condensation such as bathrooms & laundries due to potential for false alarms.
n Kitchen/cooking areas.
I
A
N
IA
N
E/LOOP
IA
N
E/LOOP
40mm
10mm
CEILING / WALL JUNCTION
TYPICAL MULTIPLE
FLOOR INSTALLATION
SINGLE FLOOR
APEX OF
SLOPING
CEILING CEILING
ACCEPTABLE HERE
BEDROOMBEDROOM
BEDROOM W/C
KITCHEN DINING
BATH
BD/RM HALL BD/RM
KITCHEN
RUMPUS
LOUNGE
ROOM
LOUNGE ROOM
Smoke alarms for minimum protection.
Smoke alarms for additional protection.
BEST
HERE NEVER
HERE
HEAT &
SMOKE
FROM
FIRE
HEAT & SMOKE
FROM FIRE
DEAD AIR
SPACE
DEAD
AIR SPACE
SIDE WALL
300mm min
300mm min
600mm min
1500mm max
500mm min
500mm min
BEST
HERE
BEST
HERE
Good Safety Habits:
The use of this product should not be seen as a substitute for basic safety
precaution in the prevention of fire.
n Do not smoke in bed.
n Do not leave children at home alone.
n Do not clean with flammable liquids, such as petrol.
n Safely store flammable materials.
n Smoke alarms must be tested regularly to ensure that the batteries and
alarm circuit are in good operating condition.
The Limitations of Smoke Alarms:
n Smoke alarms cannot provide an alarm if smoke does not reach the alarm.
Therefore, smoke alarms may not sense fires starting in chimneys, walls,
on roofs, on the other side of a closed door, or on a different floor.
n If the alarm is located outside the bedrooms, or on a different floor, it may
not wake up sound sleepers. A smoke alarm in the bedroom, is therefore
recommended as additional protection.
n Smoke alarms have been significant in saving lives in many parts of the
world. However, U.S. Government research indicates that they may not
give early enough warning in up to 35% of fires. Hence, the use of this
product does not act as a substitute for basic prevention.
n Although smoke alarms can help save lives by providing early warnings of
a fire, they are not a substitute for an insurance policy.
n This smoke alarm alone will not alert the hearing impaired. Use special
purpose smoke alarm with lights or vibrating devices, for those hard of
hearing.
Develop and Practise a Plan of Escape:
n Make a floor plan indicating all doors and windows and at least two
escape routes from each room. Second storey house windows may need
a rope or chain ladder.
n Have a family meeting and discuss your escape plan, showing everyone
what to do in case of fire.
n Determine a place outside your home where all of you can meet, if a fire
occurs.
n Familiarise everyone with the sound of the smoke alarm and practice
leaving your home when they hear it.
n Practice a fire drill at least every six months, including drills at night.
Practice allows you to test your plan before an emergency. You may not
be able to reach your children. It is important that they know what to do!
What to do when the Alarm Sounds:
n Leave immediately by your plan of escape. Every second counts, so don’t
waste time getting dressed or picking up valuables.
n In leaving, don’t open any inside door without first feeling its surface.
If hot, or if you see smoke seeping through cracks, don’t open that
door! Instead, use your alternative exit. If inside door is cool, place your
shoulder against it, open it slightly and be ready to slam it shut if heat and
smoke rush in.
n Stay close to the floor if air is smoky. Breathe shallowly through a wet
cloth if possible.
n Once outside, go to your selected meeting place and make sure everyone
is there.
n Call the Fire Brigade from your neighbour’s home - not from yours!
n Don’t return to your home until officials say that it is safe to do so. For
additional information on fire safety, contact your local Fire Brigade.
This smoke alarm has a maximum 10 year life span. THIS SMOKE ALARM HAS BEEN TESTED AND PASSED TO AS3786-1993
DEAR ELECTRICIAN: PLEASE LEAVE THIS MANUAL FOR THE OWNER. THANK YOU FOR CHOOSING THIS SMOKE ALARM.
PROFESSIONAL IONISATION / PHOTOELECTRIC SMOKE ALARM
INSTALLATION INSTRUCTIONS
Warranty
HPM Legrand will honour all statutory guarantees that you as a consumer
are entitled to rely upon under the Australian and New Zealand Consumer
Laws against a manufacturer including a guarantee that any products
HPM Legrand has manufactured or imported are of acceptable quality.
To make a claim under any statutory guarantee (or other warranty) you
should first contact the supplier, contractor or retailer from whom you
purchased the products.
Customer Service
For all Customer Service and Technical Support enquires please call
Monday to Friday during business hours.
HPM Legrand Australia
1300 369 777
www.legrand.com.au
HPM Legrand New Zealand
0800 476 009
www.legrand.co.nz
ABN: 31 000 102 661
LE05841AAC
Disclaimers:
1. This product must be installed by a licenced electrician.
2. For indoor use only
3. This product should not be installed in areas exposed to constant vibration,
temperature fluctuations, or areas of high humidity.
4. This product contains no serviceable parts and no attempt should be made to
repair this product. If the product is faulty it should be discarded.
5. Severe electromagnetic interference from other products may cause
malfunction of this product.
6. Ionisation smoke alarms contain radioactive particles. Please refer to
instructions for disposal requirements.
7. This product has a 10 year design life. At the end of this time it should be
replaced. The date of Manufacture is coded on every alarm in the form
B/N 15 March 2013.
8. This product has been designed to operate in ambient temperatures:
5°C to 50°C.
9. This product is not suitable for marine environments such as areas subject to
salt spray and/or mist.
10. This product is not suitable for installation in hazardous and/or corrosive areas.
11. This product has been designed for domestic or similar uses and is not suitable
for a commercial installation.
12. The material in this product may vary in colour from batch to batch. Colour
matching from one batch to another cannot be guaranteed.
13. Electrical installations periodically receive transient over voltages. This product
has been designed to minimise the effect of such voltages on connected
equipment. It may not give full protection for extreme over voltage transients
such as those resulting from a close lighting strike.
14. This product has been designed to operate on a nominal supply voltage of
230V - 240V a.c. ± 6%.
15. This product must be installed and used as per these instructions.
16. After installation this product must be tested as required by the appropriate
government and/or staturatory regulations.
17. This product utilises intellectual property in the form of registered designs,
trademarks, and/or patents. Such intellectual property remains the property of
HPM Legrand in all cases.
18. HPM Legrand reserves the right to modify the specification of this product at
any time.
False Alarms:
n In very humid areas or near a bathroom, moisture can cause false alarms
in Ionisation smoke alarms.
n This smoke alarm is designed to minimise false alarms. Smoking will not
normally set off the alarm unless smoke is blown directly into the alarm.
n Combustion particles from cooking may set off the alarm if the alarm is
located close to the cooking surface.
n Because large quantities of combustion particles are generated from
spills or grilling an alarm with a Hush Control device is preferable near a
kitchen environment.
n If the alarm does sound, check for a fire before silencing the alarm. If a fire
is discovered, escape quickly and call the Fire Brigade.

This manual suits for next models

1

Other LEGRAND Smoke Alarm manuals

LEGRAND 0333-CPD-292050 User manual

LEGRAND

LEGRAND 0333-CPD-292050 User manual

LEGRAND tynetec ZXT819 User manual

LEGRAND

LEGRAND tynetec ZXT819 User manual

LEGRAND 643087 User manual

LEGRAND

LEGRAND 643087 User manual

LEGRAND Tynetec FireAngel ZXT810 User manual

LEGRAND

LEGRAND Tynetec FireAngel ZXT810 User manual

LEGRAND tynetec ZXT811 User manual

LEGRAND

LEGRAND tynetec ZXT811 User manual

LEGRAND 0 405 17 User manual

LEGRAND

LEGRAND 0 405 17 User manual

LEGRAND Tynetec FireAngel User manual

LEGRAND

LEGRAND Tynetec FireAngel User manual

LEGRAND 0 405 15 User manual

LEGRAND

LEGRAND 0 405 15 User manual

LEGRAND Tynetec Deaf Smoke ZXT487 User manual

LEGRAND

LEGRAND Tynetec Deaf Smoke ZXT487 User manual

LEGRAND tynetec ZXT810 User manual

LEGRAND

LEGRAND tynetec ZXT810 User manual

Popular Smoke Alarm manuals by other brands

SEBSON GS558 operating instructions

SEBSON

SEBSON GS558 operating instructions

Honeywell ALL-SPEC installation instructions

Honeywell

Honeywell ALL-SPEC installation instructions

Edwards LaserSense Nano Installation handbook

Edwards

Edwards LaserSense Nano Installation handbook

FBII XL4760SDT Installation and maintenance instructions

FBII

FBII XL4760SDT Installation and maintenance instructions

Panasonic 2318 Specification sheet

Panasonic

Panasonic 2318 Specification sheet

Apollo XPERT 8 installation guide

Apollo

Apollo XPERT 8 installation guide

Intec Controls HS-100 installation instructions

Intec Controls

Intec Controls HS-100 installation instructions

Lexing LX708 instructions

Lexing

Lexing LX708 instructions

Honeywell Home PROSiXCOMBO quick start guide

Honeywell Home

Honeywell Home PROSiXCOMBO quick start guide

Rokonet Nova 30 installation instructions

Rokonet

Rokonet Nova 30 installation instructions

Mircom FA-1025U Installation and operation manual

Mircom

Mircom FA-1025U Installation and operation manual

teko Astra-421 Operation manual

teko

teko Astra-421 Operation manual

ThermoWorks Smoke Receiver operating instructions

ThermoWorks

ThermoWorks Smoke Receiver operating instructions

SAFE-T-ALERT SA-668 owner's manual

SAFE-T-ALERT

SAFE-T-ALERT SA-668 owner's manual

Honeywell SiXSMOKE-CN Quick installation guide

Honeywell

Honeywell SiXSMOKE-CN Quick installation guide

Nittan EVC-PY-IS instruction manual

Nittan

Nittan EVC-PY-IS instruction manual

Konyks FireSafe quick start

Konyks

Konyks FireSafe quick start

Alecto SA-300 manual

Alecto

Alecto SA-300 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.