KEOR SPE TOWER
5
2. Regulatory and safety requirements
This section contains important safety and operating instructions that should always be followed during
the installation, use and maintenance of the UPS.
DANGER
The UPS works with dangerous voltages. Only skilled technicians qualified and authorized by
LEGRAND must perform ordinary maintenance operations. No part of the UPS can be repaired by the
user. Extraordinary maintenance operations must be carried out by LEGRAND Technical Support
Service personnel.
• This product should be installed in compliance with installation rules, preferably by a qualified
electrician. Incorrect installation and use can lead to risk of electric shock or fire. Before carrying out
the installation, read the instructions and take account of the product’s specific mounting location. Do
not open up, dismantle, alter or modify the device except where specifically required to do so by the
instructions. All Legrand products must be opened and repaired exclusively by personnel trained and
approved by Legrand. Any unauthorised opening or repair completely cancels all liabilities and the
rights to replacement and guarantees. Use only Legrand brand accessories.
• Ensure that the mains supply voltage and frequency match those of the UPS (see the product label
and the technical specifications).
• If any visible damage is found on the product during the unpacking operation, do not install the UPS
but repack the unit and return it to your reseller or distributor.
• Before operating the UPS or connecting any load equipment, ensure the UPS is connected to a
properly grounded mains socket.
• The load applied must not exceed the one indicated on the type label of the UPS.
• The ON/OFF button of the UPS does not electrically isolate the internal parts. To isolate the UPS,
unplug it from the mains power socket.
• Do not attempt to open or disassemble the UPS; there are no user replaceable parts. Opening the
case will void the warranty and introduces the risk of electric shock even when the mains plug is
disconnected.
• Since the non-detachable power supply cable acts as a separation device, the mains power supply
socket shall be installed near the UPS and shall be easily accessible.
• In case of a mains power supply failure, do not unplug the power supply cable. Earth continuity must
be ensured to the connected loads.
• Do not plug non-computer-related items such as medical, life-support and house electric equipment
to the UPS output.
• Do not plug laser printers to the UPS back-up outputs because of their high start-up current.
• The UPS functions with TT and TN systems.
•The UPS has dangerous high voltages on its input and output connections. Contact with these
voltages may be life threatening.
• In case of emergency, immediately turn off the equipment and disconnect the power cord from the
AC power supply to disable the UPS.
• Do not allow any liquid or any foreign object to enter the UPS.
• The UPS is intended for indoor installation in a ventilated, controlled indoor environment with a range
of temperature between 0°C (+32°F) and +40°C (+104°F) and non-condensing humidity <95%.
• Do not install the UPS in locations with sparks, smoke, and hazardous gas or where there is water
and excessive humidity. Dusty, corrosive, and salty environments can damage the UPS.
• Do not plug the UPS input into its own output.
• Do not attach a power strip or surge suppressor to the UPS.
• Ensure that the cables connecting the loads to the UPS are not longer than 10 meters.
• Keep a clearance of 20 cm beyond the UPS rear panel. Avoid exposing it to direct sunlight or
installing it near heat emitting appliances.
• Unplug the UPS prior to cleaning and do not use liquid or spray detergent.