LEI0193AAB LEG1408_B
Important Notice
Legrand recommends and advises that only suitably qualified personnel undertake installation and maintenance of this emergency lighting unit,
and that the installation complies with relevant safety and electrical standards.
Installation Testing - with the unit connected to the unswitched mains supply, check that the charge indicator is illuminated. If not illuminated check that the
supply is on, and that the battery leads in the unit are correctly connected. It is recommended that the batteries be charged for a minimum of 16 hours before a full
discharge test is performed. However, checking of the emergency lamp function may be performed after 1 hour by momentarily pressing the test switch on the unit.
Interrupting supply will Discharge Emergency Lighting Batteries. If supply remains interrupted for a long period, permanent damage to the batteries may result
due to excessive battery discharge.
Do not subject units to a high number of charge/discharge cycles as can occur on temporary (construction) power supply.
Inspection and Maintenance - must be performed in accordance with AS/NZS2293-2 for Australian and New Zealand installations and in accordance with relevant
local standards in other countries.
The batteries in this emergency lighting unit MUST be replaced when the unit no longer meets rated operating life.
Technical Data - for full technical or photometric data please consult Legrand.
Disclaimer - This product should only be cleaned with a damp cloth. Cleaning agents and solvents should not be used. The IP rating of this product is only valid when
all applicable seals, glands and their appropriate cables are installed correctly. This product must be installed and used as per these instructions. This product must
be installed by a licenced electrician. After installation this product must be commissioned and tested as required by the appropriate government and/or statutory
regulations. This product utilises intellectual property in the form of the registered designs, trademarks, and/or patents. Such intellectual property remains the
property of Legrand in all cases. Legrand reserves their right to modify the specifications of this product at any time. This product must be used with the loads
specified only. Other load types should be used only when written confirmation is given by Legrand. This product contains rechargeable batteries.If this product is
to be stored for an extended period of time (>3 months) then all batteries must be disconnected prior to storage. This product contains rechargeable batteries that
may contain heavy metals. At the end of their life the batteries should be recycled. This product has no user serviceable part and no attempt should be made to
repair this product. For repair please contact Legrand. Extended exposure to UV rays (such as exposure to direct sunlight) may cause discolouration of this product.
Severe electromagnetic interference from other products may cause malfunction of this product. This product is not suitable for marine environments such as areas
subject to salt spray and/or mist. This product is not suitable for installation in hazardous and/or corrosive areas. The material in this product may vary in colour
from batch to batch. Colour matching from one batch to another cannot be guaranteed. Electrical installations periodically received transient over voltages. This
product has been designed to minimise the effect of such voltages on connected equipment. It may not give full protection for extreme over voltage transients such
as those resulting from a close lighting strike. This product has been designed to operate on a nominal supply voltage of 230V - 6% to 240Va.c. + 6%. Performance
of this product may be affected if installed near RF transmitters such as mobile phone services or similar. Performance of this product may be affected if installed
in or around substantially metal enclosures or structures.
Status Indication
Battery charging LED
LED On: Unit is fully charged OR
Battery is charging.
LED Off: Loss of mains power, OR
Battery disconnection.
ECONOMY LED EXIT
Warranty
Legrand Australia Pty Ltd guarantees this emergency lighting
unit for a period of 36 months from date of despatch, solely
against failure arising from faulty materials or workmanship, and
provided that the unit has been stored, shipped, installed, used and
maintained in accordance with the manufacturers instructions and
relevant standards. Misuse, negligence or modification of the unit
voids all warranties. Consult Legrand Ausralia Pty Ltd Conditions of
Sale for details on warranty liability. If this emergency lighting unit
is faulty, return the unit freight pre-paid to your point of purchase, or
contact Legrand Australia Pty Ltd on 1300 369 777.
Customer Service
For all Customer Service and Technical Support enquires
please call Monday to Friday during business hours.
Legrand Australia
1300 369 777
www.legrand.com.au
Legrand New Zealand
0800 476 009
www.legrand.co.nz
ABN: 31 000 102 661