
ADJUSTMENT AND SERVICE
Leonard Type TM Thermostatic Water Mixing Valves are
simple in design and may be easily cleaned, adjusted and
repaired. If the installation is accessible, servicing may be
completed without disconnecting the valves.
NOTE: Thermostatic Water Mixing Valves, which must be
regularly maintained to provide best performance.
Frequency of cleaning depends on quality of local water
conditions and usage. See Maintenance Guide and Record
MGR-1000.
!!! WARNING !!!
These mixing valves are equipped with an adjustable high temperature limit stop factory set at approximately
130°F (54°C) with an incoming hot water supply temperature of 155°F (68°C). If the hot water supply
temperature of the job is greater than 155°F (68°C), the valves when turned to full HOT will deliver water in
excess of 130°F (49°C) and the limit stops MUST BE RESET BY THE INSTALLER!
TROUBLESHOOTING INSTRUCTIONS
While valve is running:
1. Remove POINTER ROD NUT AND POINTER
2. Temporarily place POINTER on the spline rod. turn RIGHT for warmer temperature,
turn LEFT for cooler temperature. When valve is delivering warmest temperature
desired, remove the pointer.
3. Replace POINTER on the spline rod so that its RIGHT edge is resting against the TOP
SIDE OF THE web which is cast on the RIGHT side of cover.
4. The new maximum temperature has now been set. Test this temperature by holding a
thermometer under the flow of water to be certain it is as desired.
SEE PAGES: 3 FOR COMPLETE PARTS BREAKDOWN
*Check for significant variations in outlet flow. Thermostatic valves will NOT provide the desired accuracy outside of
their flow capacity range. Minimum flows must be no less than shown (see Flow Capacities, page 4).
If installed on a recirculated hot water system, make certain the valve is piped according to Leonard Required Piping (see
page 1). 2
PACKINGS &
GASKETS
PORT SLEEVE
ASSEMBLY
THERMOSTAT GROUP
CHECKSTOPS
(TM-200,225 ONLY)
1. Leak at packing nut.
2. Leak between valve cover and base.
3. Valve delivers either all hot or all cold water,
or will not mix consistently.
4. After cleaning or replacing port sleeve
assembly, valve will not hold temperature.
5. Hot water by-pass into cold line.
6. Supplies cannot be shut-off completely.
7. Leak at checkstop bonnet.
PARTS REQUIRED
#24, 21/200, (TM-200) or 24, 21/300 (TM-
300)
#3/3A, TG-1 plus packings noted above or
Kit R/200 (TM-200) R/300 (TM-300)
TG-2/60 or Kit R/200 (TM-200)
TG-2/300 or Kit R/300 (TM-300)
Kit 2/200
TO RESET ADJUSTABLE HIGH TEMPERATURE LIMIT STOP: