
CD 617 ISSUE 1 : 27/07/2020
11. SET FLOOR LEVELS.
Up to this point the actual physical floor levels should NOT have been set. The aim was to setup the
positioning system to stop at the learned values rather than the actual floor levels. NOW is the time to
set the actual floor levels from within the lift car!
a. Travel to each floor in turn, making a note of the position error in mm. Travelling to each floor in
both directions IS NOT NECESSARY as the system should be the same for both UP and DOWN.
b. From the menu POSITIONING SYSTEM PARAMETERS->FLOOR LEVELS, select each floor
in turn and use the selection wheels to adjust the absolute position in millimetres as Fig 4 below.
12. SETTING UP RE-LEVELLING.
Only setup re-levelling when the floor levels are correctly set otherwise the position point will be inaccurate
thus the re-levelling operation will most likely report warnings and errors. As can be seen from Fig 5 the
distances are short so accurate floor levels in the first place will ensure trouble free operation.
13. LIMITS (SLOWING/STOPPING) AND BUFFER TESTS
A set of dedicated buttons are available to assist in the testing of the slowing limits, stopping limits and lift
buffers (i.e. buffer test). To make the buttons appear press and hold the shaft area of the screen for 5
Seconds. Once the buttons appear they need to be held under “constant pressure” to invoke the function. If
the buttons are not pressed for a period of 20 minutes they will disappear. Also to clear the buttons, simply
press MENU and press LIFT/GROUP VIEWER to re initialise the lift viewer. (see Fig 6).
a. TESTING THE SLOWING LIMITS
Press TOP button to register a top car call and, then press SLOW LIMIT TEST button under constant
pressure to inhibit the STEP signal, thus forcing the lift to slowdown via the slowing limit. Press BOT
to register a bottom car call and repeat the above process.
b. TESTING THE TERMINAL LIMITS
Press TOP button to register a top car call and then press STOP VANE TEST button under constant
pressure to inhibit the stopping signals, thus forcing the lift to stop on the terminal limit. Press BOT to
register a bottom car call and repeat the above process.
c. TESTING THE OVERTRAVEL MECHANICAL BUFFERS (BUFFER TEST)
Note this function is to be used only by responsible Lift Test Engineers!
Press TOP button to register a top car call and then press BUFF TEST button under constant pressure
to inhibit the slowing, slowing limits and stopping signals, thus forcing the lift to crash stop onto the
lift buffers on HIGH SPEED! Press CPB to register a bottom car call and repeat the above process.
14. CAN/CANopen INFORMATION
a. The Positioning system is designed for use with Position Devices incorporating CAN or the
industry standard CANopen communication protocol. Therefore information can be transferred
from the device and viewed by selecting option MENU->POSITIONING SYSTEM INFO->
CAN/CANOPEN INFO. In particular the error information can be viewed as below:
i. Schmersal USP: = USP wire Errors / Warnings / CANopen information.
ii. Hengstler AC58: = Contains Alarm / Warnings / CANopen information.
a. Ensure Re-level vane is set 15mm above / below floor level
as shown in fig 5. Test for Re-level UP as follows:
b. Lower the lift down until it actuates the re-level vane.
c. Ensure the lift re-levels UP on level speed.
d. Make a note of the position where it stops, e.g. 3997.
e. The result shows in the UP direction the lift stopped LOW
by 3mm. Therefore decrease POSITIONING SYSTEM
PARAMETERS ->RELEV UP STOP DIST by 3mm to
compensate.
f. Increasing the distance compensates for overshooting
floor level. Reducing the distance compensates for
stopping short of floor level.
g. Repeat the procedure for relevel DN (if reqd). Adjust
parameter POSITIONING SYSTEM PARAMETERS -
>RELEV DN STOP DIST to compensate.
Re Level Vane
UP / DN (LV1)