LIH AHC-871 User manual

20
10
0
30
40
FIRE ALARM CONTROL PANEL
OPERATING MANUAL
Model # AHC-871
HORING LIH INDUSTRIAL CO., LTD.

zIntroduction and Characteristics……………………………………………………………….. 1
zFire Alarm System Assembly Diagram.……………………………………………………….. 2
zFire Alarm Signal Flow Chart………………………………………………………………….. 2
zPanel Description………………………………………………………………………………. 3
zSymbols………………………………………………………………………………………… 4
zDetector’s Standard Wiring Method…………………………………………………………… 4
zMethod of Wire………………………………………………………………………………… 5
zWiring Principle………………………………………………………………………………... 6
zOperating Instructions
1. Fire Surveillance…………………………………………………………………………….. 7
2. Fire Alarm…………………………………………………………………………………… 7
3. Reset…………………………………………………………………………………………. 7
4. Disconnection Alarm………………………………………………………………………... 8
5. Fire Alarm Test………………………………………………………………………………. 8
6. Disconnection Test…………………………………………………………………………... 8
7. Standby Power………………………………………………………………………………. 8
8. Telephone Communication………………………………………………………………….. 9
9. Consecutive Activation of Hydrants………………………………………………………… 9
10. Occurrence of Alarm Signal During Testing……………………………………………..… 9
11. “Attention Switch” Indicator……………………………………………………..………... 9
zInstallation Location…………………………………………………………………………… 9
zImportant Notes On Maintenance
1. Normal State of the Panel…………………………………………………………………… 9
2. Maintenance of Device……………………………………………………………………… 9
3. Overall Maintenance………………………………………………………………………… 10
zTrouble-shooting
1. Malfunction of Zone Indicator & PBL Combination Panel………..………………………... 10
2. Functions of Fuse……………………………………………………………………………. 10
3. Stand-by Power Source In Reverse Order…………………………………………………... 11
4. PBL Combination Panel Indicating Lamp and Area Bell Malfunction……..………………. 11
5. Zone Indicator Malfunction…………………………………………………………………. 11
6. Blinking of Zone Indicators and “Disconnection” Indicating LED….……………………... 11
7. Zone Indicator and “Fire” Alarm Indicator Lights Up…..………………………………….. 11
zMain Specifications……………………………………………………………………………. 12

- 1 -
zINTRODUCTION
In line with technological advanced. Fire alarm systems have become more sophisticated, especially in
developed countries. Likewise, our knowledge and expertise in Fire Alarm Control Panel is also
second-to-none as compared to those produced by developed countries. We have since designed an
Accumulation-type Control Panel that is easy to maintain, aesthetic in outlook and complete with
functions that meet most end-users requirements.
zCHARACTERISTICS
* Up-to-date Designs
(1) Accumulative Capability:
We focus on pulsative waves and interfering signals, which are the most common causes of
false alarm during operation, especially for panels with smoke detector loops. Our panels can
eliminate such phenomenon, minimize the possibilities on false alarm to a very low degree, or
even can completely preventing it from occurring.
(2) Automatic Reset Capability:
When the auto reset button is depressed, it will automatically reset after performs a Detector
Test, in addition to the normal reset function.
(3) Fuse Fault LEDs:
Any failures due to faulty wiring or other causes will be indicated on the panel.
(4) External Indicators:
Our product provides an option for ‘light-on’ or ‘light-off’ in the event of power failures.
Because Fire Indicating Lamp will light up during a power failure, it will easily drain-off the
battery supply and cause the control panel to be in-operative. In the ‘light-off’ mode Fire
Indicating Lamp will remain ‘off’ all the time and only blink during an outbreak of fire, thus
prolonging surveillance capabilities. For ‘light-on’ switch to position (I) and for ‘light-off’
switch to position (O).
(5) Reserve slot for relay output (Optional).
* The Zone Testing Button is located at the Zone Indicator of the control panel. It is self-returning
and can be use to perform test for individual zone.
* Voltage Stabilizer is verified with an applied sudden voltage load. It must pass this test before
leaving the factory for delivery.
* The control panel is made of steel-plate and coated with an attractive oven-baked paint.
* Every zone indicator is made up of two LEDs connected in series and covered with a delicate
glossy light bulb shield (removable plates are included for labeling of different areas).
* Each group of Circuits is detachable for easy maintenance. It also has a one-piece maintenance
Bracket which not only makes the structure of the control panel stronger, but also helps prevent
breakdowns during wiring.
* Zone Testing Button and Relay are tightly sealed from dust, preventing bad connection due to
accumulation of dust.

- 2 -
S G
IR
P
P
B
B
L
L
(1) (2) (3) (4)
(8)
(9)
(10)
(6)
(5)
(7)
1.Occurrence
of Fire
2-1.Detector 3.Control Panel 4.Area Bell
5.Indicatin
g
Lamp
6.Annunciator
2-2.Manual
Call Point
1.Heat Detector
2.Smoke Detector
3.Gas Detector
4.Flame Detector
5.Area Bell
6.Indicatin
g
Lam
p
7.Manual Call Point
8.Annunciator
9.Extin
g
uishin
g
Device
10.Control Panel
20
10
0
30
40
20
10
0
30
40
zFIRE ALARM SYSTEM ASSEMBLY DIAGRAM
zFIRE ALARM SIGNAL FLOW CHART
20
10
0
30
40
20
10
0
30
40

- 3 -
zPANEL DESCRIPTION
1.Zone Indicator 13.Signal Transfer Switch 24.Water-shortage Indicating LED
2.Zone Test Button 14.Accumulation Switch 25.Water-drawing Indicating LED
3.Voltmeter 15.Auto Revert Switch 26.Fire-fighting Pump Indicating LED
4.Sound 16.Revert Switch 27.AC Power Failure LED
5.Fire Alarm Indicator 17.AC Power Indicating LED 28.Battery Power Failure LED
6.Disconnection Sound
Switch
18.Battery Indicating LED 29.Relay Device Failure LED
7.Main Bell Switch 19.Disconnection Indicating LED 30.Indictor Lamp Failure LED
8.Area Bell Switch 20.Attention Switch
Indicating LED
31.Area Bell Failure LED
9.Disconnection Test
Switch
21.Accumulation In Motion LED 32.DC Power Failure LED
10.Fire Alarm Test
Switch
22.Telephone Indicating LED 33.Panel Door Lock
11.Test Switch 23.Transmitter Indicating LED 34.Telephone
12.Battery Test Switch
20
10
0
30
40
34
6 7 8 9 10 1112 13 14 1516
2
54333
1
31 3229 3027 2825 2623 2421 2219 201817

- 4 -
(L) Diameter of Circuit line shall be 1.2 mm.
(C) Common line 1.6mm.
End of Line
Resistor 10kΩ
Connect
to Control
Panel
Common Line LC(z-)
Circuit Line L(z+)
10KΩ 10KΩ 10KΩ
End of Line
Resistor 10kΩ
Control
Panel
(C)1.6x1
(L1) (L2) (L3)
Indicating Lamp 1.6mm
Area Bell 1.6mm
Rate of Rise
Detector
Control
Panel Fixed Temp.
Detector Smoke
Detector P.B.L.
Combination Box Manual
Call Point
Indicating
Lamp
Bell
L
LL
B
BB
P
P
P
L
PB
LB
P
S
HH
zSYMBOLS
zDETECTOR’S STANDARD WIRING METHOD

- 5 -
zMETHOD OF WIRING
BBB
S
S
P
Common line
H2
H2
COM
L1
L2
L3
LN
A
Max. connection=no.
of zone x 1.2
Max. connection=no. of
zone x 1.2
Extinguishing Facility
Hydrant Activating
Board
10kΩ
Terminal
device 10kΩ
+
+
-
-
Detector
Indicating
Lamp
Area
Bell
Hydrant
Detector
Manual call
point.
T
Tc
External wiring method
AC Power
Stand-by
Power
AC 220V
DC 24V
The relay
device DC 24V
DC 24V
DC 24V
AC 220V 50Hz
24VDC according to
number of zone.
U1
U2
U3
C
Water-shortage
Water-drawing
Pump lamp
Transmitter
Telephone
If any zones are not in use, please set Dip Switch to "ON" position.

- 6 -
WIRING PRINCIPLE
1. Wire Calculation Table (Separate calculation for long distance wiring or large control panel)
ITEM WIRING
SPECIFICATION
QUANTITY REMARKS
Auto. Fire Alarm Control Panel
Circuit point Signal-transfer point
LC LC L1 L2 L3 L4 L5
L6 L7 L8 L9
L10
EC EC E1
E2 E3 E4 E5 E6 E7 E8
E9
E10
Area bell Relay device
HA HA A
T TC C U3
U2
U1 24V 24V 24V DC 24V 220V
Annunciator
LC LC E1 E2 ... ... EN
Reserved
Reserved
LC T B BSW BSW V V
Reserved
Reserved
Reserved
Reserved
Circuit Line
Common Line
Area Bell
Indicating Lamp
Manual Call Point
Telephone
Transmitter
Earth
AC Power
1.2mm
1.6mm
1.6mm
1.6mm
1.2mm
1.2mm
1.6mm
1.2 to 1.6mm
N
N
2
2
2
1
1
2
Depends on devices, one line for
every zone.
Every common line should not
have more than 7 zones.
Parallel connection to each zone’s
detector.
E
Depending on the load of the
control panel.

- 7 -
2. Wire Connection Box
In order to facilitate inspection, maintenance and repair, every floor or appropriate area shall install a
Wire Connection Box in which connecting joints are provided. The Box’s casing shall be water-proof
and the wording “Fire Fighting Only” should labeled on an aluminum plate.
3. Wire-Point Labels And Joint Clips
Inside the control panel and every Wire Connection Box, the wire points are to be attached to Label
Covers or Label Stickers and then connected to the Y-clip.
4. Wiring Method
Please refer to page 4 ~6
5. Terminal Resistor Connecting Method
Every end of Circuit line shall be fitted with a Resistor (not more then one). If any zone in the control
panel are not in use should set Dip Switch on the Terminal to the “ON” position, please refer to page 5
for details.
6. Zone Labeling
Once the wiring is completed, label the ‘Zone Labeling Card’ provided. For easy identification, type
or print the labeling cards.
7. Wiring Record
Once the external wires are laid a record of the detailed external wiring diagram shall be kept for
future inspection and repair.
zOPERATING INSTRUCTIONS
1. Fire Surveillance
After installing system devices to the panel, connect to an 220VAC 50/60HZ supply source, set all
switches on the display board to ready position. At this stage, the “AC Power” indicating LED will be
on, Voltmeter should indicate 24V (the allowable voltage is 20V-28V). Indicating Lamp in the
combination PBL box light up and surveillance begins.
2. Fire Alarm
When any detector has activated or manual call point has pressed, it is an indication of fire. At this
moment, the “Fire” Indicator (red) and the concerned zone indicator will light up simultaneously. The
Main Bell and Area Bell will also sound and the Indicating Lamp on the Combination PBL box will
switch from still to blinking. These activities indicate that the fire alarm is valid.
(1) Disable Main Bell
To stop the Main Bell from sounding, set the Main Bell Switch to ‘off’ position. The alarm will
stop immediately.
(2) Disable Area Bell
To stop the Area Bell, set the Area Bell Switch to ‘off’ position.
3. Reset
Once the fire alarm is activated, the “Fire” Indicator and the Related Zone Indicator will remain
lighted. If the control panel is required to start the surveillance again after the previous fire situation
has been resolve, just depress the ‘Revert’ button. However, if detectors have been burnt or the manual
call point press-down not recovered, reset cannot be activated. In this instance, repair should be
completed first, then depress the ‘Revert’ button to reset the system.

- 8 -
4. Disconnection Alarm
The panel is equipped with a ‘Zone Disconnection Auto Indication’ function. Should there be a
Circuit Break in certain areas, or detachment of the terminal resistor, the “Disconnection” LED and
the related zone indicator will blink simultaneously. The Disconnection Beeper will also sound. Upon
repair of the circuit, the above mentioned will cease.
(1) Stopping Disconnection Sound
To stop the disconnection sound, move the ‘Disconnection Sound’ switch to ‘OFF’ position.
5. Fire Alarm Test
To Perform Fire Alarm Simulation Test or test the functions of the fire alarm.
(1) “Auto Revert” switch “Accumulation” Switch. “Signal Transfer” Switch.
To perform one-men fire alarm test, first set “Auto Revert” switch to down position; set
“Accumulation” Switch to down “off” position; set “Signal Transfer” Switch to down “off”
position and then test the Circuit. For every Circuit tested, the signal will automatically reset itself.
(2) Field Fire Alarm Test
(A) Detector Test Method: use a Tester, place it near detector for a few seconds. As soon as
detector has back to normal condition, the fire alarm signal on the control panel will
automatically reset itself.
(B) Manual Call Point Test Method: depress the manual call point to activate the alarm. Pull up
the button and the fire alarm signal on the control panel will automatically reset itself.
(3) Control Panel Self Testing
After repeat test (1), set “Test” Switch to ‘Test’ position, “Fire Test” Switch to ‘Test’ position, and
then depress Zone Test button (on the Zone Indicator). It will automatically reset after the test.
Once completed, set all switches to up position.
6. Disconnection Test
(1) Set “Test” Switch to ‘Test’ position, set “Disconnection Test” Switch to ‘Test’ position, and then
depress Zone Test button (on the Zone Indicator). It will automatically reset after the test. Once
completed, set all switches to ‘up’ position.
(2) Disconnection Site Test: remove the Detector.
7. Standby Power
The panel is equipped with automatic rechargeable batteries the stand-by power source (24VDC) shall
be installed during operation. When the Main power source has been terminated, the “AC Power”
Indicating LED will light off and the “Battery” Indicating LED will light up. The Voltmeter reading
will indicate 24V.
(1) Stand-by Power Test
The control panel should be powered by the main source under normal condition. To test the
function of the stand-by power source, depress “Battery Test” Switch and the control panel should
response same as power-off situation.

- 9 -
8. Telephone Communication
The control panel is equipped with a telephone communication device. It has a hand-held telephone
which can be plugged into a manual call point to begin communication when connected. The
‘Telephone Buzzer’ begins to sound inside the panel. Just lift up the telephone and the ‘Telephone
Buzzer’ sound will stop but “Telephone” Indicator will remain lights up and now communication is
conducted. The telephone must be replaced to its original position after use. Once this is done, signal
will be automatically reset.
9. Consecutive Activation of Hydrants
The control panel has a voltage-free contact for signal transfer (A contact point x 1 set voltage pack =
24V/10A). It can be utilized to simultaneous activate the Hydrant Activating Devices when the Fire
Alarm is valid.
10. Occurrence of Alarm Signal During Testing
If there is a alarm signal in any Circuit other than those under testing, the test must be terminated.
immediately and handle the alarm signal circuit first.
11. “Attention Switch” Indicator
When any switch on the display board is not set to up position the “Attention Switch” indicator will
blink. The signal will only cease when all switches have been set to up position.
zINSTALLATION LOCATION
Please refer to your local regulation for installation details.
zIMPORTANT NOTES ON MAINTENANCE
1. Normal State of The Panel
(1) Normal Condition (Fire Surveillance Alert)
Under normal conditions, the “AC Power” LED should light up, Voltmeter to indicate 24V
(allowable range is 20V to 28V). All switches should be set to up position and Indication Lamp on
the PBL combination panel should be lighted up.
(2) Power Failure
When there is a power failure, the “AC Power” LED will turn off and “Battery” LED will light up.
The Voltmeter should indicate 24V (allowable range is 20V to 28V).
2. Maintenance of Devices
(1) If maintenance may cause disturbances to public, appropriate co-ordination must be made before
hand.
(2) Priority should be given to those faulty devices in the area.
(3) Maintenance should be scheduled at least twice a year and must include both physical and
functional inspections.

- 10 -
3. Overall Maintenance
A yearly overall inspection should be carried out by a professional institution, or the Original
Equipment Manufacturer. Inspection records must be tabulated and kept by a responsible person or
the department concerned, to safeguard the public.
(1) Power Supply
Check whether the external wiring of the panel its power consumption are within the safety
regulation, whether the standby power conforms to specifications and whether the duration of
power supply is within the safety regulation.
(2) Control Panel
(A) Fire Test: to check whether the fire alarm system is functioning properly.
(B) Circuit Break Test: to check the whether the “Zone Test” button is functioning properly.
(3) Detectors
To perform a site test for the detectors in order to check whether they are functioning properly and
also to check the condition of detector’s indicating LED (on the detector’s base).
(4) Manual Call Point
To check for integrity of plastic plate, press-down button and condition of wiring inside the MCP.
(5) Insulation Test
The insulation between power terminal of control panel and earth shall have a value of 250V
20MΩand above.
zTROUBLE-SHOOTING
The control panel is produced with an advanced technology and delicate design that is easy to assemble.
It requires no special skills to trouble-shoot a malfunction, thus avoiding any teething problems that might
be encountered during maintenance.
1. Malfunction of Zone Indicator and PBL Combination Panel
The system devices are assembled with many single units (refer page2). Either the ‘Detectors’,
‘Wiring’ or ‘PBL Combination Panel’ is used incorrect, it will affect the function of control panel.
(1) Measure AC power with a Multi-meter for any (AC) voltage. It should read 220V, according to the
specifications of the panel.
(2) Check whether the “Normal Power” Switch inside the control panel is set to “ON” position and the
green color LED Power Light on the power board is lighted up.
(3) Check whether the “AC Power” Indicator and Voltmeter on the panel board are functioning
properly. The system should specify 24VDC.
(4) Check whether fuses are in good condition (or the “AC Power Failure” LED on the Display Board
is lighted up).
(5) Check whether the external devices and wiring conform to specifications, as sated in this
handbook.
2. Functions of Fuse
The panel has six fuses (F1~F6), each with individual protection function. It must not be replaced
with fuses that do not conform to specifications or low quality, otherwise we will not be liable for any
damage. Burnt fuses are probably caused by external wiring error, short circuit or faulty external
devices.

- 11 -
(1) F1: Fuse for alternate power source 24VDC.
(2) F2: Fuse for AC power source 220VAC.
(3) F3: fuse for Stand-by power source.
(4) F4: Extra power source when the need arises.
(5) F5: Fuse for Area Bell.
(6) F6: Fuse for Indicating Lamp in the combination PBL box.
3. Stand-by Power Source In Reverse Order
If the stand-by power polarity is in a reverser order, F3 fuse will be burnt. The polarity should be
immediately corrected.
4. PBL Combination Panel Indicating Lamp and Area Bell Malfunction.
(1) Remove the external wiring of the Indicating Lamp and Area Bell inside the panel.
(2) Measure the (+) outlet of Indicating Lamp with a multi-meter and check whether it reads DC24V.
Then perform a fire test to check for any intermittent power supply. Reset after the test is
completed.
(3) Measure the (+) outlet of the Area Bell with multi-meter. It should not have any voltage supply.
Then perform a fire test and a 24VDC voltage should be recorded. Reset after the test.
(4) When the test results conform to (2) and (3), it indicates that the panel is functioning properly.
The wires should only be connected after the external wiring have been repaired.
5. Zone Indicator Malfunction
Based on our experience, about 90% of the zone indicators’ malfunction is due to incorrect external
wiring. Other factors are mainly due to incorrect handling or incorrect wire joints inside the panel.
6. Blinking of Zone Indicators and “Disconnection” Indicating LED.
When one or several zone indicators and “Disconnection” Indicating LED blink simultaneously, it
should be regarded as a signal of circuit break. In this instance, inspection and repairs should be
carried out in the following manner.
(1) Check for any zones in the control panel are not in use, if yes, check whether the Dip Switch on
the Terminal is in the “ON” position.
(2) Remove the trouble circuit; the disconnection signal should immediately go off.
(3) If test results conform to (2), it indicates that the control panel is functioning properly. The wire
shall only be connected after the external wiring has been repaired.
(4) Inspect the external circuit to check whether last detector has been installed one End of Line
Resistor or improperly installed.
(5) Check for any break in the external wiring as well as any dislocation of Detectors.
(6) Set the multi-meter to Ωmode and measure the malfunction circuit resistance value. The
resistance value between the circuit line and circuit common-line should be 10KΩ.
(7) After removal of the circuit line, there should not be any voltage between the circuit line and
common line. The wire shall only be connected after the external wiring has been repaired.
7. Zone Indicator and “Fire” Alarm Indicator lights Up
When one or many of the zone indicators and “fire” Indicator lights up simultaneously, it should be
regarded as a fire alarm signal. The inspection and repair guidelines are as follows:

- 12 -
(1) Remove the trouble circuit. Measure between the circuit line and common line to check for short
circuit or any resistance value lower than 2KΩ(normal value=10kΩ).
(2) After removal of the trouble circuit line, the panel must be reset. At this moment, the zone indicator
should carry a disconnection signal. To cut off the signal, set the Dip Switch on the Terminal to “ON”
position. After repairing the circuit lines, re-activate the Dip Switch on the Terminal and then
re-connect the external circuit line.
(3) Check for presence of any short circuit of the external wiring, or any defective detectors.
zMain Specifications
DESCRIPTION REMARKS
Power Source 220VAC 50/60Hz Others also available
Stand-by Power 24VDC
Charging Voltage Current 26VDC 100mA~400mA With auto adjustment function.
Voltage Current 24VDC short circuit under 5V
30mA
External Line Resistance Below 50Ωround trip
# of Heat Detector Connected No limit. Except electronic-type
# of Smoke Detector Connected 30/zone Horing Lih manufactured
PBL Combination Panel Wiring 4 Lines or 6 Lines Depending on requirements
# of Indicating Lamp, Area Bell
Connected # of zone ×1.2
End of Line Resistor 10KΩOne per zone
Material 1.6mm steel
Color Ivory-white Others also available
Accessory Functions
Water Shortage Indicating LED,
Water Drawing Indicating LED,
Hydrant In-action LED.
Contacts for the PBL
combination panel.
Built-in intercom
Table of contents
Popular Control Panel manuals by other brands

Mitsubishi Electric
Mitsubishi Electric GT1020 Series Startup guide

GE
GE NetworX NX-8-EUR installation manual

Essmann
Essmann TRZ Basic DG Technical information and operating instruction

Teknim
Teknim TFP-121 Series Installation & operating manual

LinkAYL
LinkAYL LK-UP22 Series manual

Balboa Water Group
Balboa Water Group SpaTouch2 user guide