
- 8 -
4. Disconnection Alarm
The panel is equipped with a ‘Zone Disconnection Auto Indication’ function. Should there be a
Circuit Break in certain areas, or detachment of the terminal resistor, the “Disconnection” LED and
the related zone indicator will blink simultaneously. The Disconnection Beeper will also sound. Upon
repair of the circuit, the above mentioned will cease.
(1) Stopping Disconnection Sound
To stop the disconnection sound, move the ‘Disconnection Sound’ switch to ‘OFF’ position.
5. Fire Alarm Test
To Perform Fire Alarm Simulation Test or test the functions of the fire alarm.
(1) “Auto Revert” switch “Accumulation” Switch. “Signal Transfer” Switch.
To perform one-men fire alarm test, first set “Auto Revert” switch to down position; set
“Accumulation” Switch to down “off” position; set “Signal Transfer” Switch to down “off”
position and then test the Circuit. For every Circuit tested, the signal will automatically reset itself.
(2) Field Fire Alarm Test
(A) Detector Test Method: use a Tester, place it near detector for a few seconds. As soon as
detector has back to normal condition, the fire alarm signal on the control panel will
automatically reset itself.
(B) Manual Call Point Test Method: depress the manual call point to activate the alarm. Pull up
the button and the fire alarm signal on the control panel will automatically reset itself.
(3) Control Panel Self Testing
After repeat test (1), set “Test” Switch to ‘Test’ position, “Fire Test” Switch to ‘Test’ position, and
then depress Zone Test button (on the Zone Indicator). It will automatically reset after the test.
Once completed, set all switches to up position.
6. Disconnection Test
(1) Set “Test” Switch to ‘Test’ position, set “Disconnection Test” Switch to ‘Test’ position, and then
depress Zone Test button (on the Zone Indicator). It will automatically reset after the test. Once
completed, set all switches to ‘up’ position.
(2) Disconnection Site Test: remove the Detector.
7. Standby Power
The panel is equipped with automatic rechargeable batteries the stand-by power source (24VDC) shall
be installed during operation. When the Main power source has been terminated, the “AC Power”
Indicating LED will light off and the “Battery” Indicating LED will light up. The Voltmeter reading
will indicate 24V.
(1) Stand-by Power Test
The control panel should be powered by the main source under normal condition. To test the
function of the stand-by power source, depress “Battery Test” Switch and the control panel should
response same as power-off situation.