INSTALLATION INSTRUCTIONS
J-BOX MOUNTING:
1.
Feed fixture leads through the back plate and connect to AC power supply (Fig A, page 1). For 120V use black and white wires
and for 277V, use red and white wires.
2.
Attach back plate to J-Box and secure with screws.
3.
Complete the battery connection. (Fig. B, page 1)
4.
Align snaps and push housing directly onto the back plate (Fig. C, page 1).Apply continuousAC power.
5.
After the battery has been left to charge for 24 hours, test the unit by pushing the test switch and the LED lamp head will turn ON.
CONDUIT MOUNTING:
1. Secure back plate to wall surface using keyhole knockouts on the back plate.
2. Route wires through hole in conduit flange and make conduit connection. For 120V use black and white wires and for 277V, use
red and white wires.
3. Complete the battery connection (Fig. B, page 1).
4. Align snaps and push housing directly onto the back plate. Apply continuous AC power.
5. After battery has been left to charge for 24 hours, test the unit by pushing the test switch and the LED lamp head will turn ON.
WALLMOUNTING:
SAVE THESE INSTRUCTIONS
and deliver to owner after installation
PAGE:2of 4
1. Secure back plate to wall surface using keyhole knockouts on the back plate.
2. Feed fixture leads through back plate and connect to AC power supply. For 120V use black and white wires and for 277V, use
red and white wires.
3. Complete the battery connection (Fig. B, page 1).
4. Align snaps and push housing directly onto the back plate. Apply continuous AC power.
5. After battery has been left to charge for 24 hours, test the unit by pushing the test switch and the LED lamp head will turn ON.
OPERATION:
1. During an electrical power failure, the LED lamps will automatically come on for a minimum of 90 minutes.
2. To test, press the "TEST" switch. The emergency LED lamps will illuminate and LED indicator will turn OFF. When the switch
is released, the lamps will turn OFF and the LED indicator will turn ON.
LED STATUS INDICATOR KEY and TROUBLESHOOTING:
Visual Status Indicaon Troubleshoong/Acons to Take
RED
GREEN
UNLIT
1. Baery connecon is not made.
2. Baery has been diagnosed as dead or defecve aer 24
hours of connuous charging with AC power supplied.
Baery is connected, AC power has been supplied and xture is in
charging state.
AC power has not been supplied.
1. Make connecon; or if baery is connected, disconnect
battery for eight seconds and then reconnect.
2. Replace the battery.
This is the normal state. No acon required.
Supply AC power.
TESTING:
National Electric Code (NEC) and NFPA101regulations require that routine tests need to be performed as listed below: Once every
month, the unit needs to be tested for duration of 30 seconds. Push in and hold the test switch to perform this test. Once every 12
months, a full 90 minute (per UL requirements) test needs to be performed on the unit. Disconnect power to the unit and leave it in
the emergency mode. The lamps should stay ON for at least 90 minutes. Written records of the testing are to be kept for
examination by the authority having jurisdiction.