
Reservoir-to-Pump Tubing:
1. For convenience, the reservoir assembly is equipped with three outlet ports, one vertical and two horizontal.
Choose an outlet port on the reservoir assembly, remove port cap, and connect the 5/32" ID x 3 ft (4mm ID x 1m)
tubing onto selected port.
a. Confirm that all unused outlet ports are capped off (with the provided port caps) or leakage from the
reservoir will occur.
2. Use supplied cable tie to secure the tubing.
3. Route the tubing to pump intake (indicated by the direction of flow arrow on the top of pump) and connect.
4. Use supplied cable tie to secure tubing to pump intake port.
5. Be certain the tubing is not kinked when pump is installed.
Pump Discharge Tubing:
The EC-1 pump is supplied with a section of silicone discharge tubing attached to the pump discharge and fitted with a 1⁄4"
(6mm) tubing adapter. Do not remove tubing.
1. Connect a length of 1⁄4" (6mm) ID discharge tubing (not provided) to the discharge tubing adapter using a cable tie
or hose clamp.
2. The other end of discharge tubing is to be directed into the nearest inside gravity-feed drain, or along the
refrigeration lines to an outside gravity-feed drain.
3. Maximum acceptable horizontal run of discharge tubing is dependent on the diameter of tubing used and the
vertical lift. The installer should apply a reasonable factor of safety and size the pump to handle a greater flow rate
than the maximum condensate to be produced.
4. Do not extend the discharge tubing more than 33 ft (10m) above the level of the pump.
5. NOTE: The end of the discharge tubing must be positioned such that it is no more than 3 ft (1m) below (vertically)
the collection reservoir. Otherwise, a siphon effect may occur causing the pump to lose its prime. This condition
would cause the pump to re-prime itself during each cycle, resulting in noisy operation and shortened pump life.
6. Ensure that there are no kinks, twists or breaks in the discharge tubing that could cause blockage. If cable ties are
used to strap tubing to structures, assure that cable ties do not crush or squeeze-closed the tubing.
Vent Tubing:
1. Connect the 1⁄4" ID (6mm) tubing to the vent port of the reservoir cover. The free end of the vent tubing must be
secured
above the highest level of the drip tray in the air conditioner to prevent overflow.
2. Route the vent tubing upward, ensuring that it is not kinked or blocked.
3. Do not remove, cut off, shorten, twist, or sharply bend the vent tube.
4. Do not connect this tube to the air handler; it is for venting only.
5. Be certain that the vent tubing will remain in an upward position during the operating life of the pump.
General Installation Notes:
• After connecting the reservoir inlet, reservoir-to-pump, vent, and discharge tubing, ensure that the reservoir and
pump remain positioned correctly.
• Keep all tubing and wires clear of moving parts in the air handler.
• Upon completion of the installation, test the pump and all connections, observing that water is being pumped to the
discharge point.
ELECTRICAL CONNECTIONS
BEFORE CONNECTING POWER LEADS, SHUT OFF ELECTRICAL POWER AT FUSE- OR BREAKER-BOX. ALL WIRING MUST
COMPLY WITH LOCAL ELECTRICAL AND BUILDING CODES, AS WELL AS THE MOST CURRENT NATIONAL ELECTRIC
STANDARDS. CHECK CONTROL UNIT/PUMP LABEL FOR PROPER VOLTAGE REQUIRED. DO NOT CONNECT TO VOLTAGE
OTHER THAN THAT SHOWN ON CONTROL UNIT/PUMP LABEL.
The EC-1 is designed to be used with an earth-grounding conductor. To reduce the risk of electrical shock, connect the
earth lead to a properly-grounded circuit. The use of a ground fault circuit interrupter is recommended.
All wiring should be performed by a qualified installer approved by local regulations and National Standards. For best
performance, connect the control unit/pump to a separate circuit. The control unit/pump MUST BE CONNECTED TO A
CONSTANT POWER SUPPLY, NOT AN INTERMITTENT SOURCE SUCH AS A FAN OR LIMIT CONTROL CIRCUIT.