LIXiSE LXC620 User manual

LXC620 Generator controller user manual
Dongguan Tuancheng Automation Equipment Co.,LTD.
LXC620 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD.
:T:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com Page 1 of 39
LXC620
Generator controller user manual
Ver1.1 Date: 2012/08/08
Software Version
Date
Version
Note
2010-10-20
1.0
Start publishing
2012-08-08
1.1
Increased DTU binding and remote monitoring function
LXC620 Series
LXC610 Series

LXC620 Generator controller user manual
Dongguan Tuancheng Automation Equipment Co.,LTD.
LXC620 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD.
:T:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com Page 2 of 39
Sign
Instruction
NOTE
Highlights an essential element of a procedure to ensure correctness.
CAUTION!
Indicates a procedure or practice, which, if not strictly observed, could
result in damage or destruction of equipment.
WARNING!
Indicates error operation may cause death, serious injury and
significant property damage.

LXC620 Generator controller user manual
Dongguan Tuancheng Automation Equipment Co.,LTD.
LXC620 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD.
:T:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com Page 3 of 39
Contents
1. Performance and characteristics................................................................................................................................ 4
2. Technical parameters.................................................................................................................................................... 6
3. Operation.......................................................................................................................................................................... 7
3.1. Key functions........................................................................................................................................................7
3.2. Automatic start/stop operation.........................................................................................................................8
3.2.1. Starting sequence:..................................................................................................................................8
3.2.2. Stopping sequence:................................................................................................................................9
3.2.3. Manual start/stop operation:.................................................................................................................9
3.3. Switch control procedures..............................................................................................................................10
3.3.1. LXC620 ATS switch control procedures.........................................................................................10
3.3.2. LXC610 Switch control procedures..................................................................................................10
4. SMS remote control、wireless remote control......................................................................................................11
5. Based on the GPRS DTU remote online monitoring...........................................................................................12
5.1. DTU with the binding of the controller.........................................................................................................13
5.2. Password generation and change the interface....................................................................................... 15
6. History query..................................................................................................................................................................16
6.1. Event log.............................................................................................................................................................16
6.2. History alarm......................................................................................................................................................16
7. Protection........................................................................................................................................................................17
7.1. Warnings.............................................................................................................................................................17
7.2. Shutdown alarm................................................................................................................................................ 18
7.3. Trip alarm............................................................................................................................................................20
7.4. SMS alarm..........................................................................................................................................................20
8. Parameter setting......................................................................................................................................................... 22
8.1. Parameter setting,content and scope of list.............................................................................................. 23
8.2. Programmable output port can be defined content table1-4.................................................................27
8.3. Programmable input port 1-6 definition content list................................................................................. 29
8.4. Custom project name list................................................................................................................................ 29
8.5. Sensor selection list.........................................................................................................................................30
8.6. Conditions of crank dinsconnect selection.................................................................................................32
9. Wirings connection.......................................................................................................................................................32
10. Typical applications................................................................................................................................................... 34
11. Installation.................................................................................................................................................................... 38
11.1. Case dimension and fixing size..................................................................................................................38
11.2. Battery voltage input......................................................................................................................................38
11.3. Speed sensor input........................................................................................................................................38
11.4. Output and expand relays............................................................................................................................38
11.5. Ac input.............................................................................................................................................................38
11.6. Withstand voltage test...................................................................................................................................39
12. Common faults and exclusion method..................................................................................................................39
13. Product packaging..................................................................................................................................................... 39

LXC620 Generator controller user manual
Dongguan Tuancheng Automation Equipment Co.,LTD.
LXC620 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD.
:T:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com Page 4 of 39
1. Performance and characteristics
LXC610:Auto Start Module. It controls gen-set to start or stop automatically by remote start signal.
LXC620:Auto Main Failure, updates based on LXC610, especially for automatic system composed by
gens and mains.
With ARM-based 32-bit MCU, highly integrated hardware, new reliability level;
132x64 LCD with backlight, multilingual interface (including English, Chinese or other
languages)which can be chosen at the site, making commissioning convenient for factory personnel;
Equipped with advanced networking capabilities,via GPRS mobile network and Internet
connectivity,in any place where the network can be remotely monitor;
Leasing industry applications: management provides the perfect solution: leased out via PC remote
Management of the unit, you can monitor all operating parameters (oil pressure, water temperature,
voltage, current, power, etc),you can always change the configuration to protect the unit is not proper
application, can record 200 detailed fault information, including: time to failure, because ,when the
voltage, current, power, oil pressure, water temperature and other key parameters, and ready to
upload to the monitoring machine. Another multi-level password management options to facilitate the
lease management;
RS485 communication port enabling remote control, remote measuring, remote communication via
ModBus protocol;
Protection, automatic Start & Stop gen-set, ATS(Auto Transfer Switch) control with perfect fault
indication and protection function;
Parameter setting: parameters can be modified and stored in internal FLASH memory and cannot be
lost even in case of power outage; most of them can be adjusted using front panel of the controller
and all of them can be modified using PC via USB;
Equipped with SMS (Short Message Service) function. When gen-set is alarming, controller can send
short messages via SMS automatic to max. 5 telephone numbers. User can control or check genset
by sending Short Message;
Adjust the controller `s configuration by the computer via USB, RS232, RS485 interface;
More kinds of curves of temperature, pressure, fuel level can be used directly and users can define
the sensor curves by themselves;
Multiple crank disconnect conditions (speed sensor, oil pressure, generator frequency) are optional;
Event log, real-time clock, scheduled start & stop generator (can be set as start gen-set once a
day/week/month with load or not);
All output ports are relay-out;

LXC620 Generator controller user manual
Dongguan Tuancheng Automation Equipment Co.,LTD.
LXC620 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD.
:T:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com Page 5 of 39
For Mains, controller has over and under voltage, over and under frequency, loss of phase and phase
sequence wrong functions; For generator, controller has over and under voltage, over and under
frequency, loss of phase, phase sequence wrong, over and reverse power, over current functions;
3 fixed analog sensors (temperature, oil pressure and liquid level);
2 configurable sensors can be set as sensor of temperature, pressure or fuel level;
Widely power supply range DC(8~35)V, suitable to different starting battery voltage environment;
Can be used for the pumping unit as an indicating instrument (indicate and alarm are enable only,
relay is inhibited );
Fully functional,and can detect almost all the generating units of electrical parameters and
non-electrical parameters.
DETECT PROJECT :
Mains
Line voltage Uab,Ubc,Uca
Phase voltage Ua,Ub,Uc
Frequency Hz
Gens
Line voltage Uab,Ubc,Uca
Phase voltage Ua,Ub,Uc
Frequency Hz
Load current IA,IB,IC
Each phase and total active power kW
Each phase and total reactive power kVar
Each phase and total apparent power kVA
Each phase and average power factor PF
Accumulate total gens power kWh、kVarh、kVAh
Sensor
Temperature WT °C、°F Choose to display
Oil pressure OP kPa、Psi、Bar Choose to display
Fuel level FL %(unit)
Speed SPD RPM(unit)
Voltage of Battery VB V (unit)
Voltage of Charger VD V (unit)
Hour count HC can accumulate Max.65535 hours.
Start times can accumulate Max.65535 times
MAINS AND GENERATOR ABNORMAL
CONDITIONS:
Voltage is too high
Voltage is too low
Frequency is too high
Frequency is too low
Phase loss
Loss of power
THE FAULT DISPLAY AND PROTECTION
FUNCTION PROJECT:
High water temperature warn
High water temperature shutdown alarm
Low oil pressure warning
Low oil pressure shutdown
Over speed shutdown alarm
Box high temperature warn
Low fuel level warn
Battery voltage is too high warn
Battery voltage is too low warn
Load over current shutdown alarm
Failed to stop alarm
Emergency stop alarm
Oil pressure sensor open circuit

LXC620 Generator controller user manual
Dongguan Tuancheng Automation Equipment Co.,LTD.
LXC620 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD.
:T:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com Page 6 of 39
2. Technical parameters
Items
Contents
Operating Voltage
DC 8.0V to DC 35.0V, Continuous Power Supply.
Power Consumption
<3W(standby:≤2W)
Alternator Input Range
3-Phase 4-Wire
3-Phase 3-Wire
Single-Phase 2-Wire
2-Phase 3-Wire
12V AC - 360 V AC (ph-N) 3 Phase 4wire
23V AC - 620 V AC (ph-ph) 3 Phase 3wire
12V AC - 360 V AC (ph-N)
12V AC - 360 V AC (ph-N)
Alternator Frequency
50/60Hz
Speed sensor voltage Vpp
1.0 - 70Vpp(Peak to peak)
Speed sensor Frequency
10000Hz(max.)
Start Relay Output
10Amp DC28V
Fuel Relay Output
10Amp DC28V
Programmable Relay Output 1
10Amp DC28V
Programmable Relay Output 2
10Amp DC28V
Gens Closed Programmable Relay Output 3
10Amp 250VAC Free output
Mains Closed Programmable Relay Output 4
10Amp 250VAC Free output
Case Dimension
209mm x 146mm x 33mm
Panel Cutout
182mm x 137mm
C.T. Secondary
5A Rated
Working Conditions
Temperature:(-25~+70)℃Humidity:(20~90)%
Storage Condition
Temperature:(-40~+70)℃
Protection Level
IP55: when waterproof rubber seal installed
between controller and panel fascia.
Insulating Intensity
Object: input/output/power
Quote standard: IEC688-1992
Test way: AC1.5kV/1min leakage current: 3mA
Net Weight
LXC620=0.448Kg LXC610=0.433Kg

LXC620 Generator controller user manual
Dongguan Tuancheng Automation Equipment Co.,LTD.
LXC620 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD.
:T:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com Page 7 of 39
3. Operation
3.1. Key functions
Stop/Reset key
This button places the module into its Stop/reset mode.
When engine is running,pressing this key will stop the engine.
When a shutdown alarm occur,pressing this key will reset alarm.
his button is for testing the LEDs and screen.Press for a long time to
light them.
Start key
Start genset in Manual mode or Test mode.
Manual mode key/
Config“-”key
Pressing this key will set the module into manual mode.
In setting parameter status,pressing this key will decease setting value.
Manual test mode/
Config“+”key
Pressing this key will set the module into manual test mode.
In setting parameter status,pressing this key will increase setting value.
Auto key/
Config“enter”key
Pressing this key will set the module into automatic mode.
In setting parameter status,pressing this key will shift cursor or confirm
Setting value.
View history record
key
In the parameter display and record query screen,press this key to
make a scroll operation.
Press this button more then three seconds, it show genset abnormal
shutdown record.If long press again, display back to main page.
Scroll key
In the parameter display and record query screen,press this key to
make a scroll operation.
Tips: Press and simultaneously, enter into advanced parameters setting menu if password
is correct.
Tips: default password is 0000, user can change it in event of others change the senior parameters
setting.Please closely remember it after changing If you forget your password, please contact our
customer service, at the same time press the key all the information back to the service personnel.
Note: the lights indicate
Configurable indicating lamp: a total of 4, but the action needed by PC configuration, very flexible;
Gens normal indicator: it brights when gens is normal .it flickers when gens abnormal .it extinguished
when there is no gens.
Gens load indicator lamp: indicator when load is on gens.
Mains normal indicator: it brights when mains is normal .it flickers when mains abnormal .it extinguished
when there is no mains.
Mains load indicator lamp: indicator when load is on mains.

LXC620 Generator controller user manual
Dongguan Tuancheng Automation Equipment Co.,LTD.
LXC620 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD.
:T:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com Page 8 of 39
3.2. Automatic start/stop operation
Press ,and the indicator besides the key illuminates, which indicates unit is in auto start mode.
3.2.1. Starting sequence:
Press ,then the button indicating lamp bright. The generator is in “automatic start mode”. In the
automatic mode, the generator will be auto to start and stop according requirement (no need any human
action). In this mode, three type starting request can trigger starting process.
The 1st one is mains failure (over voltage, under voltage, over frequency, under frequency , simulation of
mains failure enter valid).(This condition is valid only for LXC620)
The 2nd one is the remote start input or SMS remote start .
The last one is the schedule running.
Once the start request is triggered and no fault, began to perform automatic boot sequence:
Start Delay timer is shown on Status page of LCD;
When start delay is over, preheat relay outputs (if this be configured),“preheat start delay XX s”is
shown in LCD;
When preheat delay is over, fuel relay outputs 1s and then start relay output; if engine crank fails
during“cranking time”, the fuel relay and start relay deactivated and enter into“crank rest time”to wait
for next crank;
If engine crank fails within setting times, the controller sends Fail to Start signal and “Fail To Start”
message appears on LCD alarm page;
In case of successful crank attempt,“safety on timer”starts. During this period, low oil pressure, high
water temperature, under speed, charge failure alarms are disabled. As soon as this delay is
over,“start idle delay”is initiated (if configured);
During“start idle delay”, under speed, under frequency, under voltage alarms are inhibited. When this
delay is over,“warming up delay”starts (if configured);
When“warming up delay”is over, if generator state is normal, its indicator will be illuminated. If voltage
and frequency has reached on-load requirements, the closing relay will be energized, generator will
accept load, generator power indicator will turn on, and generator will enter Normal Running state; if
voltage and frequency are abnormal, the controller will initiate alarm (alarm type will be displayed on
LCD alarm page).
NOTE: In case of “Remote Start (off Load)”, the procedure is the same, except for step NO. 7: the
closing relay will NOT be energized, generator will NOT accept load.

LXC620 Generator controller user manual
Dongguan Tuancheng Automation Equipment Co.,LTD.
LXC620 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD.
:T:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com Page 9 of 39
3.2.2.Stopping sequence:
LXC620:when mains return normal during gen-set running, enters into mains voltage “Normal
delay”.When mains normal delay are over, enter into “stop delay” and mains indicator lights; also can
be into this mode when “remote start on load” is inactive.
LXC610:generator enters into“stop delay”as soon as“Remote Start” is inactive.
When stop delay is over, close generator relay is un-energized; generator enters into “cooling time
relay”. After “transfer rest time”, close mains relay is energized. Generator indicator extinguishes
while mains indicator lights.Then began "cooling delay", and during the period if mains failure or
remote start is active,generator return to the gens on load.
Idle relay is energized as soon as entering “stop idle delay”.
In the "stop idle delay" after the end,if enter“ETS hold delay”, ETS relay is energized. Fuel relay is
deactivated and decides whether generator is stopped or not automatically.;
In the "ETS delay" after the end,then enter genset "Fail to stop timer",auto decides whether generator
is stopped or not.
When the generator stopped,enter the standby generator;If the generator does not stop the controller
alarm(LCD Screen Display Shutdown failure warning).
3.2.3.Manual start/stop operation:
LXC620: Press , controller enters into Manual mode and its indicator lights. Press then
controller enters into "Manual Test Mode"and its indicator lights. In the both mode, press to start
generator, can automatically detect crank disconnected, and generator accelerates to high-speed
running. With high temperature, low oil pressure and abnormal voltage during generator running,
controller can protect genset to stop quickly (please refer to No.4~9 of Auto start operation for
detail procedures). In“manual mode ”, the procedures of ATS please refer to ATS procedure of
generator in this manual.In“Manual Test Mode ”, generator runs well, whether mains normal or
not, loading switch must be transferred to generator side.
LXC610: Press , controller enters into Manual starts mode and its indicator lights. Then
press to start generator, can automatically detect crank disconnected, and generator accelerates
to high-speed running. With high temperature, low oil pressure and abnormal voltage during
generator running, controller can protect genset to stop quickly (please refer to No.4~9 of Auto start
operation for detail procedures). After generator runs well, if remote start signal is active, controller
will send closing gens signal; if the remote signal is inactive, controller won‟t send closing signal.
Manual shop:press can shutdown the running generator(please refer to No.3~8 of stopping
sequence for detail procedures)

LXC620 Generator controller user manual
Dongguan Tuancheng Automation Equipment Co.,LTD.
LXC620 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD.
:T:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com Page 10 of 39
3.3. Switch control procedures
3.3.1.LXC620 ATS switch control procedures
Auto transfer procedures:
When controller is in Manual Test, Auto or Stop mode, switch control procedures will start through
automatic transfer.
Note: When the input port has the following configuration of situations:
1If input port is configured as Close Mains/Gens Auxiliary
When transferring load from mains to generator, controller begins detecting “fail to transfer”, then the
open delay and transfer rest delay will begin. When detecting time out, if switch open failed, the
generator will not switch on, otherwise, generator switch on. Detecting transfer failure while gens
switch on. When detecting time up, if switch on fail, it is need to wait for generator to switch on. If
transfer failed and warning“SELECT Enable”, there is alarming signal whatever switch on or off
failure.
The way to transfer from generator load to mains load is as same as above.
Note: the above is in the middle position switch.
2If input port is not configured as Close Mains/Gens Auxiliary
Mains load be transferred into gens load, after switch off and transfer interval delay, gens switch on.
The way to transfer gens load to mains load is as same as above.
Note: The above configuration is for an no-air-hang type ATS. But it can also be used for an
air-hang type ATS.
When controller is in Manual mode, manual transfer will be executive. After the generator normal starting,
when mains failure or remote start input is valid, mains switch off, then gens switch on.If you have
configured closing state input, during switching transitions also need to check the input state of closing
signals. If fail to close or open it will generate an alarm.
3.3.2.LXC610 Switch control procedures
Auto control procedures,
When controller is in manual test, auto or stop mode, switch control procedures will start auto transfer.
After the generator starting successfully, gens switch on. When the remote start signal fail, gens switch
off.
If input port is configured as Close Mains Auxiliary,Gens load is transferred into generator un-load, after
the delay of switch off, detecting transfer failure while switch off output. When detecting time up, if switch
off failed, to wait for switch off. Otherwise, switch off is completed. Gens unload is transferred into gens
load, after the delay of switch on, detecting transfer failure while switch on outputting. When detecting
time up, if switch on failed, to wait for switch on. Otherwise, switch on is completed.If transfer failed and
warning “SEL Enable”, there is alarming signal whatever switch on or off failure.
If input port is not connected with closing breaker signal,gens un-load is transferred into gens load,
gens switch on and output. Gens load is transferred into gens un-load, gens switch off and output.

LXC620 Generator controller user manual
Dongguan Tuancheng Automation Equipment Co.,LTD.
LXC620 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD.
:T:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com Page 11 of 39
Manual control procedures:
When controller is in Manual mode, manual transfer will be executive:
After the generator starting successfully,when remote start input is active, gens switch.on.When gens is
on load, if the remote start input fail, it will not uninstall or shutdown. But uninstall or shutdown will happen
when the conversion to automatic mode or pressing the Stop button . If you have configured the switch
status input, you also need to check the input state of signals. If fail to close it will generate an alarm.
4. SMS remote control、wireless remote control
This feature allows users to use GSM mobile communication terminal device for remote control.When
generators are running , if you want to stop the genset unit, you can send text messages to mobile phone
code“ SMS STOP MODE”. When the controller return code “SMS STOP MODE OK”, it means that genset
has got the command and try to stop.
SMS Code is described as follows:
NO.
SMS Command
Description
1
SMS STOP MODE
Set as stop mode
2
SMS MANUAL MODE
Set as manual mode
3
SMS TEST MODE
Set as trial test mode
4
SMS AUTO MODE
Set as auto mode
5
SMS START
Start in manual or auto mode
6
SMS GENSET
Query command, query the current state of the controller:
item
Description (controller user custom description,
can only be defined on the PC software)
feirui1234567890abcd
Working mode
MANUAL MODE
Working state
GENSET AT REST
Mains (without the LXC620)
MAINS=230V
Gens voltage
GENS=230V
Gens frequency
F=50.0Hz
Oil pressures
OPS=4.35Bar
Temperature
WTP=55C
Level Fuel
FLE=85%
Battery voltage
BAT=27.5V
Note:Write text messages are not case sensitive, but must be written in strict accordance with the
instructions in the format, the spaces between all the words are a bit of spaces, all commands have to
wait until the return code indicates that the operation is valid only.

LXC620 Generator controller user manual
Dongguan Tuancheng Automation Equipment Co.,LTD.
LXC620 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD.
:T:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com Page 12 of 39
5. Based on the GPRS DTU remote online monitoring
The scheme is based on LXI680G provide wireless data transmission network, remote control
operation of the generator on the Internet; and through the increase in the generator controller
LXI680G Room communication protocol, so that the controller can the use of LXI680G SMS via SMS
to control the generator run and generators receive alarm SMS.
Remark:LXI680G is Dongguan Feirui Electronics Co.,Ltd designed tailor-made for the generator
controller wireless data transmission module, in particular to optimize the data exchange between the
controller and the DTU, truly a fast and reliable data transmission.
Brief introduction:LXI680G is an industrial grade with GPS global satellite positioning function GPRS
DTU product. The product integrates a high-performance, low-power industrial-grade GPS module
and GPRS module, GPS global positioning technology and GPRS wireless communication
technology the perfect combination of a product.
LXI680G platform based on ARM and embedded operating system, built-in industrial-grade module, it
can be used in harsh environments, working temperature range can be up to -40℃~ + 85℃.LXI680G
provide standard RS232 serial interface, can be quickly and PLC, industrial control, instruments,
meters, RTU equipment is linked together, through the GPRS network will be linked to LXI680G
equipment data transmission to a host on the Internet, realize the data remote transparent
transmission, at the same time to the front-end equipment of GPS location information reported to
host, realize positioning of the equipment.
LXI680G with positioning, wireless data communications and data processing capabilities in a
compact, rugged, reliable, easy to install, can be widely used in construction, transportation and other
industries. Particularly suitable for tower crane monitoring, heavy machinery management, but also
can be used in the field of taxi operations management, transport vehicles, special vehicles, vehicle
rental management and leasing.
WIRELESS CONNECTION SCHEMATIC DIAGRAM

LXC620 Generator controller user manual
Dongguan Tuancheng Automation Equipment Co.,LTD.
LXC620 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD.
:T:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com Page 13 of 39
5.1. DTU with the binding of the controller
Controller and LXI680G after binding, it is only through the password to unbundling, if forced the controller
and the DTU apart, the controller will record the alarm and displayed on the LCD panel and the warning
information, or refuse the next start generator (the user can set up the binding deal) after failure, this
feature is especially suitable for generator leasing industry.
Multilevel password management
Users need to configure the parameters,through different permissions password input, the parameters of
the controller will present different configuration interface.
N
o.
Password
type
Extend of
competence
Password
modification
Unbound
Parameter
configuration
Password
Managers
Deadline
1
manager
All change
permissions
(dynamic
password
Based on the
password
And the
application
code
For calculating
income)
Leasing
companies
Long
time

LXC620 Generator controller user manual
Dongguan Tuancheng Automation Equipment Co.,LTD.
LXC620 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD.
:T:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com Page 14 of 39
2
technician
Only have the
parameter
Configure
permissions
(not can
unbound)
Leasing
Companies、
Client
Long
time
3
Dynamic
password
Disposable(on
ly has a
one-time
password
Parameter
configure
permissions,
and
unbound)
can’t change
password
Dynamic
calculations
(Dynamic
code
providedby
The
customer)
Certain
time
effectively

LXC620 Generator controller user manual
Dongguan Tuancheng Automation Equipment Co.,LTD.
LXC620 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD.
:T:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com Page 15 of 39
5.2. Password generation and change the interface

LXC620 Generator controller user manual
Dongguan Tuancheng Automation Equipment Co.,LTD.
LXC620 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD.
:T:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com Page 16 of 39
6. History query
6.1. Event log
In the control panel, press keys to view controller before abnormal shutdown record, including the time
of the outage warning content display and the state,press keys can search record back.Return
according to state controller real-time show press key again.LXC620 controller can record99 abnormal
downtime record recently.
6.2. History alarm
Controller will record the momentary generator all monitoring parameters. Users can remote access,easy
to cause analysis,due to a single record data is more, the record can only be through monitoring software
review,monitoring software can be through the DTU wireless remote read data.
Record reading window

LXC620 Generator controller user manual
Dongguan Tuancheng Automation Equipment Co.,LTD.
LXC620 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD.
:T:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com Page 17 of 39
Recorded data display window
7. Protection
7.1. Warnings
When the controller detects warning signal,controller only warning does not stop,and the LCD display a
warning alarm type.
The following table warning volume controller:
No.
Warning type
Description
1
High Temp.Warn
When controller detects the temperature is higher than the set value, it
will send a warn alarm signal and it will be displayed in LCD.
2
Low oil pressure
warn
When controller detects the oil pressure is lower than the set value,it will
send a warn alarm signal and it will be displayed in LCD.
3
Over Speed Warn
When controller detects the speed is higher than the set value,it will
send a warn alarm signal and it will be displayed in LCD.
4
Under Speed Warn
When controller detects the speed is lower than the set value,it will send
a warn alarm signal and it will be displayed in LCD.
5
Loss of Speed
Signal Warn
When controller detects the speed is 0 and the action select"Warn", it will
send a warn alarm signal and it will be displayed in LCD.
6
Over Frequency
Warn
When controller detects the frequency is higher than the set value,it will
send a warn alarm signal and it will be displayed in LCD.
7
Under Frequency
Warn
When controller detects the frequency is lower than the set value,it will
send a warn alarm signal and it will be displayed in LCD.
8
Over Voltage Warn
When controller detects the voltage is higher than the set value,it will
send awarn alarm signal and it will be displayed in LCD.

LXC620 Generator controller user manual
Dongguan Tuancheng Automation Equipment Co.,LTD.
LXC620 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD.
:T:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com Page 18 of 39
9
Under Voltage Warn
When controller detects the voltage is lower than the set value,it will
send awarn alarm signal and it will be displayed in LCD.
10
Over Current Warn
When controller detects the current is higher than the set value,it will
send awarn alarm signal and it will be displayed in LCD.
11
Fail to Stop
When generator can not stop after the“stop delay”/”ETS delay”,
controller will send warning alarm signal and it will be displayed in LCD.
12
Low Level Warn
When controller detects the oil lever is lower than the set value,it will
send a warn alarm signal and it will be displayed in LCD.
13
Charge Alt Fail
When controller detects the charger voltage is lower than the set value,it
will send awarn alarm signal and it will be displayed in LCD.
14
Battery Under
Voltage
When controller detects the battery voltage is lower than the set value,it
will send a warn alarm signal and it will be displayed in LCD.
15
Battery Over
Voltage
When controller detects the battery voltage is higher than the set value,it
will send a warn alarm signal and it will be displayed in LCD.
16
Auxiliary input port
1-6warning
When digit input port1-6is set as warning and active,controller sends
corresponding warning signal.
Note: the auxiliary input port warning types,must be user configuration,to be effective.
7.2. Shutdown alarm
When controller detects shutdown alarm,it will send signal to stop the generator to load out,and the
Display alarm type.
Shutdown alarms as following:
No.
Warning types
Description
1
Emergency Stop
When controller detects emergency stop signal,it will send a stop alarm
signal and it will be displayed in LCD.
2
High Temperature
When controller detected the temperature of water/cylinder is higher than
preset,it will send a stop alarm signal and it will be displayed in LCD.
3
Low Oil Pressure
When controller detected oil pressure is lower than the preset,it will send
a stop alarm signal and it will be displayed in LCD.
4
Over Speed
When controller detected genset speed is over the preset,it will send a
stop alarm signal and it will be displayed in LCD.
5
Under Speed
When controller detected genset speed is under the preset,it will send a
stop alarm signal and it will be displayed in LCD.
6
Loss Of Speed
Signal
When controller detected genset speed is 0,it will send a stop alarm
signal and it will be displayed in LCD.
7
Over Frequency
When controller detected genset frequency is over the preset,it will send
a stop alarm signal and it will be displayed in LCD.
8
Under Frequency
When controller detected genset frequency is under the preset,it will send
a stop alarm signal and it will be displayed in LCD.
9
Over Voltage
When controller detected genset voltage is over the preset,it will send a
stop alarm signal and it will be displayed in LCD
10
Under Voltage
When controller detected genset voltage is under the preset,it will send a
stop alarm signal and it will be displayed in LCD
11
Over Current
When controller detected genset current is over the preset and delay is
not0,it will send a stop alarm signal and it will be displayed in LCD
12
Fail To Start
During the start at tempt times, if genset start failed, it will send a stop
alarm signal and it will be displayed in LCD
13
Oil Pressure
Sensor Open
When oil pressure sensor opens circuit and the input is active,controller
will send a stop alarm signal and it will be displayed in LCD.

LXC620 Generator controller user manual
Dongguan Tuancheng Automation Equipment Co.,LTD.
LXC620 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD.
:T:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com Page 19 of 39
14
Input Port 1-6
When controller detected the input port1-6external warning is active,
controller will send shutdown alarm signal and it will be displayed in LCD.
Note: the input port shutdown alarm types,must be user configuration,to be effective.

LXC620 Generator controller user manual
Dongguan Tuancheng Automation Equipment Co.,LTD.
LXC620 User Manual Dongguan Tuancheng Automation Equipment Co.,LTD.
:T:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com Page 20 of 39
7.3. Trip alarm
When controller detects shutdown alarm signal,it will shutdown generator quickly and stop after high
speed cooling.
Trips shutdown alarm as following:
No.
Warning type
Detection range
Description
1
Over Current
Remain valid
When controller detects the value is higher thant he set
value, and the action select"trip and shutdown",it will send
a trip alarm signal and it will be displayed in LCD.
2
Input port1-6
The user setting
range
When digital input port1-6 is set as"trip and shutdown",
and the action is active,it will send atrip alarm signal and it
will be displayed in LCD.
Note: the input port trip alarm types,must be user configuration,to be effective.
7.4. SMS alarm
These items are sent via SMS to the user to set the GSM mobile communication terminal.
No.
Condition
1
Emergency stop
2
High temperature1 shutdown
3
Low oil pressure1shutdown
4
Over speed shutdown
5
Under speed shutdown
6
Speed signal loss shutdown
7
Over frequency shutdown
8
Under frequency shutdown
9
Over voltage shutdown
10
Under voltage shutdown
11
Over current shutdown
12
Starting failure shutdown
13
Oil pressure sensor open shutdown
14
Input 1 shutdown
15
Input 2 shutdown
16
Input 3 shutdown
17
Input 4 shutdown
18
Input 5 shutdown
19
Input 6 shutdown
20
Over current trip alarm
21
Input port 1 trip alarm
22
Input port 2 trip alarm
23
Input port 3 trip alarm
24
Input port 4 trip alarm
25
Input port 5 trip alarm
26
Input port 6 trip alarm
27
High temperature 2 shutdown
Table of contents
Other LIXiSE Controllers manuals
Popular Controllers manuals by other brands

Christie
Christie Terra TXO 102 SO Setup and installation guide

Invertek
Invertek Optidrive P2 series Installation & operating instructions

CD Automation
CD Automation REVO C 3PH 690V user manual

Swiss Made
Swiss Made START BOOSTER user manual

Eurotops
Eurotops TH-230BH instructions

SCHUNK
SCHUNK SRH-plus 20 Assembly and operating manual