LIXiSE LXC706 Series User manual

LXC706 Series Genset Controller
Dongguan Tuancheng Automation Equipment Co.,Ltd.
LXC706 Product User Manual Dongguan Tuancheng Automation Equipment Co.,Ltd.
:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com
Page 1 of 17
LXC706
Genset Controller User Manual
Ver1.1 Date: 2014/03/20
Software version
Date
Versio
n
Note
2013-05-10
1.0
Original release.
2014-03-20
1.1
Added USB interface for directly connecting to PC.
LXC706 SERIES

LXC706 Series Genset Controller
Dongguan Tuancheng Automation Equipment Co.,Ltd.
LXC706 Product User Manual Dongguan Tuancheng Automation Equipment Co.,Ltd.
:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com
Page 2of 17
Contents
1. SUMMARY....................................................................................................................................................................... 3
2. FEATURES...................................................................................................................................................................... 3
3. PERFORMANCE............................................................................................................................................................ 3
4. SPECIFICATION.............................................................................................................................................................4
5. DISPLAY SYMBOL AMD OPERATION....................................................................................................................5
5.1. PUSH BUTTON...................................................................................................................................................5
5.2. LED ICON............................................................................................................................................................. 6
5.3. DISPLAY DESCRIPTION................................................................................................................................. 6
5.4. OPERATION........................................................................................................................................................ 7
5.4.1. Man Start ..........................................................................................................................................7
5.4.2. Auto State .........................................................................................................................................7
5.4.3. Stop State .........................................................................................................................................8
6. ALARM.............................................................................................................................................................................. 8
7. PARAMETERS TABLE(ONLY ADJUST VIA PC).................................................................................................. 9
7.1. PARAMETER SETTING LIST (TABLE I)..................................................................................................... 9
7.2. PROGRAMMABLE OUTPUT (TABLE 2)...................................................................................................12
7.3. PROGRAMMABLE INPUT (ACTIVE WHEN CONNECT GND (B-) (TABLE 3)...............................12
7.4. SENSOR SELECT (TABLE 4)...................................................................................................................... 13
8. CONDITIONS OF CRANK DISCONNECT............................................................................................................14
9. PARAMETERS SETTING..........................................................................................................................................14
10. TERMINAL...................................................................................................................................................................15
11. CASE DIMENSIONS.................................................................................................................................................16
12. TYPICAL CONNECTIONS...................................................................................................................................... 17
13. PRODUCT PACKAGING......................................................................................................................................... 17

LXC706 Series Genset Controller
Dongguan Tuancheng Automation Equipment Co.,Ltd.
LXC706 Product User Manual Dongguan Tuancheng Automation Equipment Co.,Ltd.
:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com
Page 3of 17
1. SUMMARY
The Module LXC706 is an small Automatic Engine Control Module. It selects 3 kinds of working
state(Manual, Auto, Stop), can pass panel light touch buttons artificially start/stop genset, also can
through remote start signal input automatic starting generator, and can detect fault (low oil pressure,
high water temperature, emergency stop alarm, over speed) automatically disconnect fuel relays
and stop electromagnet to electric suction close. Panel LED indicator fault state, provide real and
effective fault alarm signal.
2. FEATURES
Emerald green backlight, generator parameters are clearly visible during the day and night.
LCD icon display alarm, alarm information is visual, universal.
On the LCD digital display a variety of generator parameters.
The PC panel with durable, waterproof.
The control panel, easy realization of generator start stop, reduce the user connection.
All parameters can be set on the panel, convenient debugging and maintenance.
Set all the configuration parameters and monitoring computer through USB connection.
Ultra small size, suitable for small generator, intelligent control is particularly suitable for small
gasoline generator.
Equipped with a shockproof rubber ring, can achieve waterproof and shockproof panel.
Install the assembly, flame retardant ABS shell, pluggable terminal, embedded installation,
compact structure, convenient installation.
3. PERFORMANCE
The power supply a wide range (8~35) VDC, can adapt different starting battery voltage
environment.
The microprocessor as the core, for the LCD screen display icon symbols, light touch keys.
With low oil pressure, high water temperature, over speed, and emergency stop, start failures
and so on protection and instructions.
Can detect and display of power are: power voltage V, power frequency Hz, engine temperature
ºC, oil pressure kPa, speed rpm, total running time H, the battery voltage V, fuel level%.
voltage of the generator, battery voltage, speed, temperature, pressure, liquid level sensor
threshold can be set, can achieve the following alarm or warning: low oil pressure, water
temperature, cylinder temperature high, speeding, less speed, emergency stop, failure to start,
stop, failure of power voltage is too high, too low, power frequency is too high or too low, the
battery voltage is too high low, low fuel level.
With idle speed control and ETS solenoid function.

LXC706 Series Genset Controller
Dongguan Tuancheng Automation Equipment Co.,Ltd.
LXC706 Product User Manual Dongguan Tuancheng Automation Equipment Co.,Ltd.
:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com
Page 4of 17
With 3 working state: manual, automatic, stop.
Through the software setting of controllers can be set to the engine controller (not choose the
power voltage input), suitable for control of pump unit.
Panel with a red light emitting diode (LED) display and alarm status.
A variety of temperature, pressure, oil level sensor can be used directly, and can custom parameters:
Temperature, pressure sensor, respectively, and temperature, pressure alarm in parallel, in providing
the digital quantity at the same time increase the level of protection.
Many successful starting condition (rotational speed sensor, oil pressure, power generation) can
choose.
Four fixed relay output( fuel oil output, starter output, to stop the output, Idle speed output).
A programmable output, can be set to public alarm output, stop failure output,preheating output
or idle speed control output function.
Allow the user to change the setting of parameters, and memory in the internal FLASH memory, will
not be lost in the system when the power is off, the controller from the front panel of the controller. All
the parameters can be adjusted, or through the USB interface by the PC machine USB power supply
controller, through monitoring software for parameter setting.
4. SPECIFICATION
project
content
Working Voltage
DC8. 0V to 35. 0V, Continuous Power Supply
Overall Consumption
standby mode: 12V:0.3W 24V:0.4W
working: 12V:1W 24V:1.1W
AC voltage Input
Single phase 2 Wire 15V AC - 360 V AC (ph-N)
Alternator Frequency
50/60Hz
Speed Sensor Voltage
1V --24V(effective value)
Speed Sensor Frequency
maximum 10kHz
The maximum total run time
99999.9 hours (After the decimal point is 1/10 hours,Six minutes
once changes)
Start Relay Output
1Amp DC28V B+ power supply
Fuel relay output
1Amp DC28V B+ power supply
Shutdown relay output
1Amp DC28V B+ power supply
Idle speed relay output
1Amp DC28V B+ power supply
Programmable relay output
1Amp DC28V B+ power supply
Switch input port
After B - effective
Overall Dimensions
97mm x 78mm x 44mm
Panel Cutout
78mm x 66mm

LXC706 Series Genset Controller
Dongguan Tuancheng Automation Equipment Co.,Ltd.
LXC706 Product User Manual Dongguan Tuancheng Automation Equipment Co.,Ltd.
:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com
Page 5of 17
Working Conditions
Temperature:(-25~+70)ºC Relative humidity:(20~90)%
Storage Conditions
Temperature:(-30~+80)ºC
Protection Level
IP55:When waterproof rubber seal installed between the
controller and panel fascia
IP42:When waterproof rubber seal is not installed between the
controller and panel fascia
Insulation Intensity
Object:input/output/power
Quote standard:IEC688-1992
Test way:AC1.5kV/1min leakage current:1mA
Weight
0.13kg
5. DISPLAY SYMBOL AMD OPERATION
5.1. PUSH BUTTON
Symbol
Defined
Description
Manual start
button
Push this button, generator will start, and the
module comes into manual state
Auto state button
Push this button, the module comes into auto state
Stop button
Push this button, generator will stop, and the
module comes into stop state.
In the standby mode, if long pressing the button for
3 seconds all LED lights
LCD page
button/confirm
button
Change the page display, used for LCD and can
move the cursor in the parameter Settings and
confirm set information
Alarm light
When an alarm occurs, exhibit of lanterns flicker

LXC706 Series Genset Controller
Dongguan Tuancheng Automation Equipment Co.,Ltd.
LXC706 Product User Manual Dongguan Tuancheng Automation Equipment Co.,Ltd.
:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com
Page 6of 17
5.2. LED ICON
5.3. DISPLAY DESCRIPTION
Generate electricity:Phase voltage Ua,Frequency F Battery voltage,Engine speed
Symbol
Defined
Symbol
Defined
High Temperature
Automatic state
Low Oil Press
Stop state
Over Speed
Manual states
Under speed
Generator voltage
Emergency Stop
Battery voltage
High voltage
Amount of fuel
Low voltage
Speed units (rpm/minute)
Over Crank
Oil pressure unit
Warning
Voltage unit
Stop alert
Current unit
Stop Failure
Fuel level units ( Percentage )
Rotation during normal
operation
Temperature unit
flywheel tooth number
Frequency unit
Battery voltage is
abnormal
Total running time
External alarm
Parameter setup instructions
Low fuel level
L1-L2 Line voltage
L2-L3 Line voltage
L3-L1 Line voltage
L1 Phase voltage
L2 Phase voltage
L3 Phase voltage
Panel lock(Close button
function )

LXC706 Series Genset Controller
Dongguan Tuancheng Automation Equipment Co.,Ltd.
LXC706 Product User Manual Dongguan Tuancheng Automation Equipment Co.,Ltd.
:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com
Page 7of 17
Oil pressure,Water temperature Liquid level %, Total running time
Parameter Settings
5.4. OPERATION
Module has three states: stop state 、man state 、auto state .
5.4.1. Man Start
When push Man start button ,preheat will first output, and start preheat delay, when preheat
delay is end, fuel output 1 second, preheat output will stop, and crank output is start.Here engine
will start, when crank successfully, crank output stop. Then engine comes into the safe time. When
the safe time is end, then engine comes into the idle time. When the safe time is end, then idle
output is out and engine will run at full tilt.
5.4.2. Auto State
When push button, the module will enter automatic state. Here if remote start input is
active (connect to B-), the engine will start after the delay of start engine. Preheat will first
output, and start preheat delay, when preheat delay is end, fuel output 1 second, preheat
output will stop, and crank output is start. Here engine will start, when crank successfully,
crank output stop. Then engine enter the safe delay. When the safe delay is end, then
engine enter the idle delay. When the safe delay is end, then idle relay is close and genset
raise high speed.
When remote start input is inactive, the engine enter the idle process after the delay of
engine stop, idle relay disconnect, fuel relays output after the idle delay, ETS solenoid output,
genset will automatically stop, ETS solenoid disconnect when genset stop steady.

LXC706 Series Genset Controller
Dongguan Tuancheng Automation Equipment Co.,Ltd.
LXC706 Product User Manual Dongguan Tuancheng Automation Equipment Co.,Ltd.
:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com
Page 8of 17
NOTE: During the starting delay period, the fuel output disconnect. 3 seconds after entering
the starting delay process, pre-heat and ETS output.After the end of the starting delay period,
ETS output disconnect. Fuel output and pre-heat output disconnect before starting.
5.4.3. Stop State
Push the button when engine is running, the button beside led will lighten, enter idle
process, idle relay disconnect, idle delay ended, fuel disconnect, ETS solenoid output,
genset stop, ETS solenoid disconnect when genset stop steady.
When engine is waiting state, push button 1 second above, ETS solenoid will output and all
led will be Lighten. Loosen the stop buttons, ETS solenoid output disconnect instantly, and
test lamps function is over.
When engine is waiting state, only emergent stop alarm can be check.
6. ALARM
Low Oil Pressure: check after the safe delay, the duration of 5 seconds above, the module
will alarm and stop engine.
High Temperature:check after the safe delay, the duration of 10 seconds above, the
module will alarm and stop engine.
Low Fuel Level: When the fuel level is consistently below the preset value of 10 seconds,
and issuing fuel level is too low signal, this value is only a warning will not stop.
Over speed: check after the preheat delay, the duration of 2 seconds above, the module will
alarm and stop engine.
Under speed: check when engine run at full tilt, the duration of 15 seconds above, the
module will alarm and stop engine.
Over Crank: when engine crank fail over the times of configure, the module will alarm and
stop engine.
Stop Failure: when engine is stop fail, the module will warn.
Battery over voltage: The DC supply has risen above the high volts setting level for the
duration of the high battery volts 20 seconds.
Battery under voltage: The DC supply has low above the under volts setting level for the
duration of the low battery volts 20 seconds.

LXC706 Series Genset Controller
Dongguan Tuancheng Automation Equipment Co.,Ltd.
LXC706 Product User Manual Dongguan Tuancheng Automation Equipment Co.,Ltd.
:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com
Page 9of 17
Emergency Stop: When emergency stop input, ETS solenoid stop immediately output, and
then fuel disconnect, preheat and start signal emit emergency stop alarm signal.
Gen Over Voltage: When the continuous sampling voltage higher than the preset value, at
the end of the abnormal delay, signal generator voltage is too high, outage alarm at the
same time.
Gen Under Voltage: When sampling the voltage is lower than the preset value continuously,
at the end of the abnormal delay signal generator voltage is too low, outage alarm at the
same time.
Gen Over Frequency: When the sampling frequency for 10 seconds after the signal
generator frequency is too high, outage alarm at the same time.
Gen Under Frequency: When the sampling frequency for 2 seconds after the signal
generator frequency is too low, outage alarm at the same time.
Common Alarm: when any alarm or warn is appear, this alarm will active. When the over
speed, under speed, high temperature, low oil pressure, emergency stop, no generator,
crank failure, stop failure alarm, battery over voltage, battery under voltage, common alarm
LED illuminate, and common alarm output.
7. PARAMETERS TABLE(ONLY ADJUST VIA PC)
7.1. PARAMETER SETTING LIST (TABLE I)
Set the content as follows:
NO.
Parameter
Range
Default
Description
P00
Start delay
(0-3600s)
1s
It’s the delay from remote start signal is active or
mains is failure, to start generator.
P01
Stop delay
(0-3600s)
1s
It’s the delay from remote start signal is inactive or
mains is normal, to stop generator.
P02
Number of
Crank
(1-9)
3
Numbers of crank cycles.
P03
Preheat time
(0-300)S
0s
This timer dictates the duration that the pre-heat
output will be active before an attempt is made to start
the engine. Once this timer has expired cranking will
commence.
P04
Cranking time
(1-60)S
8s
This is the maximum amount of time that the module
will energize the starter motor for during starting
attempts once the starter has engaged.
P05
Crank rest
time
(3-60)S
10s
This is the amount of time the module will wait for
between start attempts.This is to allow the starter
motor to cool and the starter batteries to recover.
P06
Safe running
time
(1-60)S
10s
This timer dictates how long the module will ignore the
Low oil pressure, High Engine Temperature, Under
speed, Under volts and any other inputs configured as
active from safety on.

LXC706 Series Genset Controller
Dongguan Tuancheng Automation Equipment Co.,Ltd.
LXC706 Product User Manual Dongguan Tuancheng Automation Equipment Co.,Ltd.
:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com
Page 10 of 17
P07
Start idle time
(0-3600)S
0s
This is the amount of time that the start Idle speed is
held active.These allow the engine to hold low speed.
P08
Warming up
delay
(0-3600)S
10s
P09
Cooling delay
(0-3600)S
10s
P10
Stop idle time
(0-3600)S
0s
This is the amount of time that the stop Idle speed is
held active. These allow the engine to hold low speed.
P11
ETS solenoid
hold
(0-120)S
20s
This timer is used if the unit is configured to operate an
Energize to stop engine. It dictates the duration that
the ETS output will remain active after the module has
detected the engine has come to rest. If the ETS
output is not configured, this timer will still operate,
preventing an immediate restart.
P12
Fail to stop delay
(0-120)S
0s
Once the module has given a shutdown signal to the
engine it expects the engine to come to rest. It
monitors the Oil pressure and speed sensing sources
and if they still indicate engine movement when this
timer expires a ‘Fail to stop’ alarm signal is generated.
P13
Flywheel Teeth
(100-300)
118
Tooth number of the engine, for judging of starter
crank disconnect conditions and inspecting of engine
speed. See the installation instructions.
P14
Poles
(2-16)
4
P15
Gen Abnormal
Delay
(0-20.0)s
10.0s
The alarm delay of generator over voltage and under
voltage.
P16
Gen Over
Voltage
(30-620)V
264V
When generator voltage has exceed the set value and
the “Gen abnormal delay” has expired, Gen Over
Voltage is active. When set the value as 620V, the
controller does not detect over voltage signal.
P17
Generator Under
Voltage
(30-620)V
196V
When generator voltage has fallen below the set value
and the “Gen abnormal delay” has expired, Gen Under
Voltage is active. When set the value as 30V, the
controller does not detect under voltage signal.
P18
Over Speed
(0-6000)RPM
1710RPM
When engine speed has exceed the set value for 2s,
Over Speed is active. It will initiate a shutdown alarm
signal.
P19
Under Speed
(0-6000)RPM
1200RPM
When engine speed has fallen below the set value for
10s, Under Speed is active. It will initiate a shutdown
alarm signal.
P20
Over Frequency
(0-75.0)Hz
57.0Hz
When generator frequency has exceed the set value
for 2s, Over Frequency is active. It will initiate a
shutdown alarm signal.
P21
Under
Frequency
(0-75.0)Hz
45.0Hz
When generator frequency has fallen below the set
value but Not equal to 0 for 10s, Under Frequency is
active. It will initiate a shutdown alarm signal.
P22
Charge Alt
Failure
(Warning)
(0-30.0)V
6.0V
During generator is normal running, when alternator
D+(WL) voltage has fallen below the set value and
remains for 5s, It will initiate a shutdown alarm signal.
(Return value is 1V).
P23
Battery Over
Voltage
(Warning)
(12.0-40.0)V
33.0V
When battery voltage has exceeds the set value and
remains for 20s, It will initiate a warning alarm signal.
Only warning and not to shutdown the generator.
(Return value is 1V).

LXC706 Series Genset Controller
Dongguan Tuancheng Automation Equipment Co.,Ltd.
LXC706 Product User Manual Dongguan Tuancheng Automation Equipment Co.,Ltd.
:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com
Page 11 of 17
P24
Battery Under
Voltage
(Warning)
(4.0-30.0)V
8.0V
When battery voltage has fallen below the set value
and remains for 20s, It will initiate a warning alarm
signal. Only warning and not to shutdown the
generator.(Return value is 1V).
P25
High
Temperature
(80-140)ºC
98
When the temperature value of the external
temperature sensor exceeds the set value, high
temperature signal is sent. Detecting only after
safety on delay is over. If the set value is 140, high
temperature signal will not be sent (this only concerns
external temperature sensor, not high temperature
signal via configuration. input port).
P26
Low Oil
Pressure
(0-400)kPa
103kPa
When the external pressure sensor value falls below
this set value, low oil pressure signal is sent. Detecting
only after safety on delay is over. If the set value is 0,
low oil pressure signal will not be sent (this only
concerns pressure sensor and does not concern low
oil pressure warning signal via configurable input port).
P27
Low fuel
(0-100)%
10%
When the liquid level of the external liquid level sensor
is smaller than this value and lasts 10 seconds, the
signal level is too low, Only warning and not to
shutdown the generator.
P28
Configurable
output
(0-6)
0
0:Not used
1:Common alarm
2:Energized To Stop output
3:Idle control
4:Preheat control
5:Close Gens
6:Reserved
P29
Digital input type
(0-8)
0
0:not used
1:High temperature downtime input
2:Low oil pressure shutdown input
3:Low fuel warning input
4:External shut down input
5:High temperature thermal shutdown
6:Reserved
7:Reserved
8:Fuel level sensor
P30
Digital input
activation delay
(0-20)s units:
0.1s
2.0s
P31
Crank
Disconnect
(0-8)
6
0:Freq
1:Engine speed
2:speed +Electricity generation
3:Oil pressure
4:Oil pressure + Electricity generation
5:Oil pressure + speed
6:Oil pressure + speed + Electricity generation
7:Charge D+
8:Oil pressure + speed + Electricity generation
9:Invalid combination
P32
Freq disconnect
(10.0-30.0)Hz
14.0Hz
In the process of cranking, when the gens frequency
exceeds this value, the starter will be separated.

LXC706 Series Genset Controller
Dongguan Tuancheng Automation Equipment Co.,Ltd.
LXC706 Product User Manual Dongguan Tuancheng Automation Equipment Co.,Ltd.
:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com
Page 12 of 17
P33
Disconnect
Engine Speed
(0-3000)RPM
360RPM
When engine speed higher than the set value, starter
will be disconnected.
P34
Disconnect Oil
Pressure
(0-400)kPa
200kPa
When generator oil pressure higher than the set value,
starter will be disconnected.
P35
D+
Disconnect
(3.0-32.0)V
8.0V
When generator D+ higher than the set value, starter
will be disconnected.
P36
Temp. Sensor
Curve
(0-10)
3
VDO120 ºC
P37
Oil Pressure
Sensor Curve
(0-9)
3
VDO0-10BAR
P38
Fuel sensor
(0-5)
0
not used. (Using the fuel level sensor will switch input
port is set to unused)
P39
Temperature
Sensor Open
(0-2)
0
0: Never (temperature sensor will show “+++”);
1:Warn; 2:Shutdown
P40
Oil Pressure
Sensor Open
(0-2)
0
0: Never (temperature sensor will show “+++”);
1:Warn; 2:Shutdown
P41
Fuel sensor open
(0-1)
0
0: Never (temperature sensor will show “+++”);
1:Warn;
P42
Device ID
1-247
1
P43
Power On Mode
0-2
0
0:Stop Mode 1:Auto mode 2:Manual Mode
P44
technician
password
0-9999
0000
P45
operator
password
0-9999
1111
7.2. PROGRAMMABLE OUTPUT (TABLE 2)
No.
ITEM
Description
0
Not Used
When selected, the output port is not output.
1
Common Alarm
Includes all stop alarm and warning alarm, when only warning alarm
input, this alarm is not self-locking, when outage alarm occurs, the
alarm self-locking, until the alarm is reset.
2
ETS Control
Used for engines with ETS electromagnet. Pull in when stop idle is
over and pull out when set“ETS delay”is over.
3
Idle Control
Used for engine which has idles.Pull in before starting and pull out
after into hi-speed warming; Pull in during stopping idle mode and pull
out after shutdown completed.
4
Preheat Control
Before the boot is closed, power is disconnected before starter.
5
Close Generator
Generator load conditions are ripe for action.
6
Reserved
7.3. PROGRAMMABLE INPUT (ACTIVE WHEN CONNECT GND (B-) (TABLE 3)
No.
ITEM
Description
0
Switch
input
Not Used
1
Aux High Temp
In after the success of the generator starting, if the
signal is effective, generator alarm and shutdown
immediately
2
Aux Low OP
3
Low fuel
If the signal is effective, warn only, not shutdown
4
External stop
generators
If the signal is effective, warn only, not shutdown

LXC706 Series Genset Controller
Dongguan Tuancheng Automation Equipment Co.,Ltd.
LXC706 Product User Manual Dongguan Tuancheng Automation Equipment Co.,Ltd.
:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com
Page 13 of 17
5
When
temperature is too
high downtime
When this signal is effective and normal operation, If
the temperature is too high, controller high-speed
cooling delay until after the downtime; When this signal
is invalid, If there is high temperature, the controller
directly to the high-speed stop.
6
Reserved
7
Reserved
8
Fuel level sensor
Sensor selection (table 4)
7.4. SENSOR SELECT (TABLE 4)
No.
ITEM
Content
Description
1
Temperature
sensor
0 Not used
1 Digital input low effective
2 Digital input high effective
3 VDO 120℃
4 CURTIS
5 VOLVO-EC
6 DATCON
7 SGX
8 SGD
9 SGH
10 PT100
Digital input is the switch signal, can
choose low level or high level, grounding is
low level, suspend in midair is the high
level, not plugged into a power supply for
the Cathode. Defined resistive range is
0-999.9 Ω, the factory default is SGD
sensor.
2
Pressure
sensor
0 Not used
1 Digital input low effective
2 Digital input high effective
3 VDO0-10BAR
4 CURTIS
5 VOLVO-EC
6 DATCON?10BAR
7 SGX
8 SGD
9 SGH
Digital input is the switch signal, can
choose low level or high level, grounding is
low level, suspend in midair is the high
level, not plugged into a power supply for
the Cathode. Defined resistive range is
0-999.9 Ω, the factory default is SGD
sensor.
3
Fuel level
sensor
0 Not used
1 Digital input low effective
2 Digital input high effective
3 VDO0-180ohm
4 SGD
5 SGH
Digital input is the switch signal, can
choose low level or high level, grounding is
low level, suspend in midair is the high
level, not plugged into a power supply for
the Cathode. Defined resistive range is
0-999.9 Ω,the factory default is no sensor.
In setting fuel level sensor type when,
Should put the programmable input port
type is set to 0, then set the fuel level
sensor type.

LXC706 Series Genset Controller
Dongguan Tuancheng Automation Equipment Co.,Ltd.
LXC706 Product User Manual Dongguan Tuancheng Automation Equipment Co.,Ltd.
:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com
Page 14 of 17
8. CONDITIONS OF CRANK DISCONNECT
Pictured above,select the desired options,can be selected or not selected
There are 4 conditions to make starter disconnected with engine,that is,speed sensor, generator
frequency ,Charge D + and engine oil pressure. They all can be used separately. We
recommend that engine oil pressure should be using with speed sensor and generator frequency
together, in order to make the starter motor is separated with engine immediately and can check
crank disconnect exactly.
Speed sensor is the magnetic equipment which be installed in starter for detecting flywheel teeth.
When set as speed sensor, must ensure that the number of flywheel teeth is as same as setting,
otherwise,“over speed stop”or“under speed stop”may be caused.
If genset without speed sensor, please don’t select corresponding items, otherwise, “start
fail”or“loss speed signal”maybe caused.
If genset without oil pressure sensor, please don’t select corresponding items.
If not select generator in crank disconnect setting, controller will not collect and display the
relative power quantity (can be used in water pump set);if not select speed sensor in crank
disconnect setting, the rotating speed displayed in controller is calculated by generator frequency
and number of poles.
If the generator without magnetoelectric sensor and Oil pressure sensor,the“Charger D+”is
optional as a starter motor separation conditions.It is recommended to select“Oil Pressure+
Charger D+”for safety.
9. PARAMETERS SETTING
1) The controller in standby mode simultaneously press the and ,entering the
password input interface ( following figure), When the first digit flashing, enter the password
0000;
2) press the numerical plus 1, press the Numerical minus 1, Set the correct numerical
value press the change;
3) Set the second bit to fourth bit digital in accordance with the above method;
4) If the input the correct password to enter parameter setting interface (following figure), Displays
the current settings of the serial number and parameter, press the set options flip up, press
the set options flip down;

LXC706 Series Genset Controller
Dongguan Tuancheng Automation Equipment Co.,Ltd.
LXC706 Product User Manual Dongguan Tuancheng Automation Equipment Co.,Ltd.
:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com
Page 15 of 17
5) press the enter the parameter setting state, the first digit flashing, set of numerical methods
with the same password input method.
Password input interface:Parameter Settings interface:
Matters needing attention:
1) Please change the controller parameters when generator is in standby mode only (e. g. Crank
disconnect conditions selection, digital input, digital output, various delay), otherwise, shutdown
and other abnormal conditions may occurs.
2)When set each parameter, must be within the allowed range, otherwise will not be able to change
the parameters.
3) Over voltage set value must be higher than under voltage set value, otherwise the controller will
not save the data.
4)Over speed set value must be higher than under speed set value, otherwise the controller will not
save the data.
5) Please set the generator frequency value as low as possible when cranking, in order to make the
starter be separated quickly as soon as possible.
6)Set the serial number with reference to the front “7.1 Parameter setting list (Table I)”.
7)In setting fuel level sensor type when, the programmable output type is set to 0, set the fuel level
sensor type again.
﹡NOTE 1:In the process of setting up, any time button will interrupt parameter settings.
﹡NOTE 2:In manual mode, startup success condition configuration:(2 magnetic sensor+generate
electricity) or (5 generate electricity + magnetic sensor +oil pressure), power frequency
and speed is not zero, press the start button and flip keys at the same time (0.5s),
controller according to the power frequency and generator series automatic generator
teeth.
10. TERMINAL
Terminal 1(B-):connect to the cathode of battery.
Terminal 2 (B+): connect to the anode of battery.
Terminal 3 (Em. stop input): emergent stop input, connect to (B+) is active.
Terminal 4 (Fuel Output): Fuel Output, (B+,1A).
Terminal 5 (Start Output): Start Output, (B+, 1A).
Terminal 6(Remote Start Input): Remote Start Input, connect to (B-) is active.
Terminal 7(Configurable Input):Programmable input port, By setting the input signal
switch quantity or fuel level sensor signal, switch input connect to (B-) is active.
Terminal 8(LOP Input): Low oil pressure input, switch input connect to (B-) is active.
Terminal 9(HWT. Input): High temperature input,switch input connect to (B-) is active.

LXC706 Series Genset Controller
Dongguan Tuancheng Automation Equipment Co.,Ltd.
LXC706 Product User Manual Dongguan Tuancheng Automation Equipment Co.,Ltd.
:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com
Page 16 of 17
Terminal 10(L)、11(N):Alternator Input.
Terminal 12(Idle Output):Idle speed control output port (B+,1A).
Terminal 13(Stop Output):ETS output (B+ ,1A).
Terminal 14(Configurable Output3):Configurable output, (B+, 1A).
Terminal 15(D+):Connect to charging starter’s D+ terminal. If there is no this terminal,
then be hang up.
Terminal 16 (Magnetic pickup):Magnetic head signal input,suggest using the shielded
wire.
USB Interface:Controller directly through the USB line connected to the computer for
parametric programming.
11. CASE DIMENSIONS
(HOLE: 78mm*66mm)

LXC706 Series Genset Controller
Dongguan Tuancheng Automation Equipment Co.,Ltd.
LXC706 Product User Manual Dongguan Tuancheng Automation Equipment Co.,Ltd.
:+86-769-23836636 :F:+86-769-23166296 :www.lixise.com
Page 17 of 17
12. TYPICAL CONNECTIONS
13. PRODUCT PACKAGING
This product should be following sets:
(1)1 piece of controller model LXC706;
(2)2 piece of fixed cards;
(3)1 piece of product certificate;
(4)1 piece of product manual.
Dongguan Tuancheng Automation
Equipment Co.,LTD.
Tel:8+86-769-33263276
Fax:+86-769-23166296
http://dgfeirui.en.alibaba.com
http://www.lixise.net
E-mail:sales@ smartgenset.com
Add: 18# Chashang industrial zone,
WenTang Road Dongguan City,
Guangdong, China
Table of contents
Other LIXiSE Controllers manuals