Ultrasonic Level Gauge Model: CSB70

Ludwig China Representative Office
Ludwig Automation Instrumentation
(Guangzhou) Co., Ltd.
Ludwig International Trade (Shanghai) Co., Ltd.
TEL:400-860-9760
E-mail:lw@ludwig-schneider.com.cn
OS:www.Ludwig-Schneider.com.cn
Page 001-054
超声波液位计 型号: CSB70 055-108
Ludwig Schneider GmbH & Co. KG
KGAmEichamt 4-6,97877 Wertheim
EN
CH 页
Ultrasonic Level Gauge Model: CSB70

TEL:400-860-9760
www.Ludwig-Schneider.com.cn
EN
7017872.0609/2018 CH/EN
Table Of Contents
1. Product design function-----------------------------------------001
2. Sign description ----------------------------------------------001
1 Overview----------------------------------------------------002
2. Installation diagram--------------------------------------------002
3. Instrument self-check------------------------------------------002
4. Parameter code ----------------------------------------------002
5. Menu use ---------------------------------------------------003
6. Description--------------------------------------------------004
7. Accessories -------------------------------------------------004
1. Product introduction -------------------------------------------010
2. Debug -----------------------------------------------------010
3. Main technical indicators----------------------------------------011
4. Installation guide----------------------------------------------012
5. Settings ----------------------------------------------------036
6. Menu interface and operating instructions----------------------------036
7. Error phenomenon and handling-----------------------------------045
1. Purpose----------------------------------------------------047
2. Main technical indicators----------------------------------------047
3. Electrical wiring diagram----------------------------------------048
4. Warranty ---------------------------------------------------049
1. Resonance phenomenon----------------------------------------050
2. The liquid has entered the blind zone of the ultrasonic level gauge----------051
3. Electromagnetic interference-------------------------------------053
4. The impact of takeover on measurement-----------------------------054
一、Product design function/label description
二、Intelligent integrated 2-wire, 3-wire; split wall mount, panel mount
三、The ultrasonic level meter menu simple setting operation instructions
四、The ultrasonic level difference meter menu simple setting operation instructions
五、How to judge the cause of the field failure according to the echo graph

1.Product Design Function/Signature Description
1.1 Design Function Of Magnetic Flap Level Gauge Body
1.2 Sign Description
TEL:400-860-9760
www.Ludwig-Schneider.com.cn
①
EN
7017872.0609/2018 CH/EN
②
③
④
① Integrated LCD display
② Electrical interface
③ Process connection
④ Measuring body
① Model
② Voltage
③ Accuracy
④ Process connection
⑤ Instrument number
⑥ Output
⑦ Range
⑧ Protection level
⑨ Production date
①
②
③
④
⑤
⑥
⑦
⑧
⑨
001

1.Overview
TEL:400-860-9760
www.Ludwig-Schneider.com.cn
EN
7017872.0609/2018 CH/EN
CSB70 series ultrasonic liquid (material) level gauge is an intelligent non-contact liquid (material) level
measuring instrument. The product has automatic power adjustment, gain control, false target
removal, temperature compensation, etc. It adopts the imported chip processing and advanced
detection and calculation technology from the United States to improve the measurement accuracy of
the instrument and suppress the interference signal to ensure the trueness of the measurement
results. The product can be widely used to measure the level of various liquids and the height of solid
materials, and it can also be used to measure the distance.
Intelligent Integrated 2 Wire, 3 Wire; Split Wall Hanging, Panel Mounting
2.Installation Diagram
Installation height G
Air distance L
Dead
zone
Current level H
3.Instrument Self-Test
After you test or install the meter and power on normally, press the shift key to have an L value (no
need to set, automatic detection), it should be quite the actual air distance (try to detect when the
space is empty or low level, so as to ensure the entire channel Normal work); otherwise, the meter
cannot work normally, and judge whether the installation is reasonable (adjust the installation position,
angle, etc.).
4.Parameter Code
D Meter range
Press the shift key to view the code information.
A factory mode (must be 0.000)
C dead zone
The current value that P should output
U current tracking
G or E (G installation height; E current level)
L air distance
Shift Set number determine
002

TEL:400-860-9760
www.Ludwig-Schneider.com.cn
7017872.0609/2018 CH/EN
5.Menu Use
EN
Intelligent Integrated 2 Wire, 3 Wire; Split Wall Hanging, Panel Mounting
06. Current tracking mode (0.000 means abnormal tracking; 1.000 means continuously waiting for
tracking)
3 → 4800, N, 8,1. 4 → 9600, N, 8,1.
21. The first group (programmable) upper limit control 22. The first group (programmable) lower limit
control
23. Second group (programmable) upper limit control 24. Second group (programmable) lower limit
control
32. Baud rate 1 → 1200, N, 8,1. 2 → 2400, N, 8,1.
31. Instrument number (for communication network)
25 *, third group (programmable) upper limit control 26 *, third group (programmable) lower limit control
29. Control hysteresis (to prevent frequent relay jitter, 0.050 is recommended)
27. Upper limit audible alarm (programmable) 28. Lower limit audible alarm (programmable)
30. Backlight (delayed off when 0.000 backlight; 1.000 backlight always on)
07. Change rate (every change amount received, 2.000 is recommended)
10. Factory mode (must be 0.000)
(Anomaly tracking means refreshing at all times; waiting for tracking means that the target is refreshed
at the moment of detection, and no current wait for a few moments is detected)
(When the meter sounds an alarm, press any key to eliminate the alarm sound)
Press and hold the SET button for a few seconds, the -XXXX- interface appears, enter -0000- and
press the SET button to enter the menu loop. To exit, press and hold the SET button for a few
seconds. Required number)
(The factory default setting is to install the height measurement level, and the current is waiting for
tracking)
01. Setting the level (ie the reference setting)
When 04 is set to 0.000, please set the installation height number (analog setting is possible)
(The current H display value is equal to the installation height value minus the air distance value)
When 04 is set to 1.000, please set the actual number of the level (must be set on site)
(The current H display value is equal to the value you set)
Due to the discreteness of the probe and the difficulty of estimating the installation height, it is
recommended to set the current level when measuring with high accuracy
02, range (the current output is proportional to it)
03. Liquid level resection (usually used for measuring flow, 0.003)
04. Mode code setting (0.000 represents installation height mode; 1.000 represents current level
mode)
05.Measuring mode (0.000 represents the measured material level; 1.000 represents the measured
air distance, there is no need to set the distance measurement)
003

7.Annexes
TEL:400-860-9760
www.Ludwig-Schneider.com.cn
EN
7017872.0609/2018 CH/EN
6.Description
1.The function of the split wall hanging menu is exactly the same as above
23.The second set of upper limit control 24.The second set of lower limit control
25. The third set of upper limit control 26. The third set of lower limit control
29. control hysteresis 30. backlight control
2. The split-panel menu is the same as above. The following functions are not available.
23.The second set of upper limit control 24.The second set of lower limit control
25. The third set of upper limit control 26. The third set of lower limit control
3. The integrated 3-line menu is the same as above, and the following functions are not available.
27. Upper limit audible alarm 28. Lower limit audible alarm
29.Backlight control
31. Instrument number (for communication and networking) 32. Baud rate
27. Upper limit audible alarm 28. Lower limit audible alarm
21.First set of upper limit control 22.First set of lower limit control
4. The integrated 2-line menu is basically the same as above, and the following functions are not
available.
25. The third set of upper limit control 26. The third set of lower limit control
23.The second set of upper limit control 24.The second set of lower limit control
Transmission angle: 6°~12° Blind zone: 0.20~0.8m
Signal output: 4 ~ 20mA standard (or optional RS485, RS232, specify when ordering)
Display: LCD Power supply voltage: 220VAC or 24VDC
Range: 0.5~ 30m Accuracy: 0.25%, 0.5%
Resolution: 1 ~ 5mm Frequency: ~40KHZ
Maximum load: 750 ohm Housing material: PVC ABS
Protection level: IP65 Ambient temperature: -20~+ 55 ℃
Mounting thread: M66x3
A. Displayed as F000 or FFFF (indicating that no signal has been acquired)
(1) Whether the wiring is good
(2) Whether the installation is vertical
(3) Whether the power is too small (such as foam, floating objects, smoke, dust, etc. on the surface of
the liquid; it can increase the power)
7.1 Performance
7.2 Instrument Anomaly Analysis
004
Intelligent Integrated 2 Wire, 3 Wire; Split Wall Hanging, Panel Mounting

TEL:400-860-9760
www.Ludwig-Schneider.com.cn
EN
7017872.0609/2018 CH/EN
(2) There are obstacles above or to the side of the level
(3) the instrument itself is bad
Tip: When you cannot find the cause repeatedly, please communicate with the manufacturer if
necessary
(1) There are obstacles above or to the side of the level. (Change the installation position or contact
the manufacturer)
(3) The setting or position of the installation port does not meet the requirements
C. Display numbers change back and forth
(1) Level height enters the blind zone
B. The displayed number does not change (it does not change with the level of the material).
(2) Strong interference sources, etc.
Host (unit: mm) Sensor (unit: mm)
B. Dimensional drawing of split-panel instrumentation C. Dimensional drawing of integrated
2-wire and 3-wire instrument
7.3 Instrument Size
005
Intelligent Integrated 2 Wire, 3 Wire; Split Wall Hanging, Panel Mounting

TEL:400-860-9760
www.Ludwig-Schneider.com.cn
EN
7017872.0609/2018 CH/EN
7.4 Wiring Diagram (The Instrument Itse lf Is Also Attached)
A. Split wall mount meter
B. Split-board instrumentation
C. Integrated 3-wire instrument D. Integrated 2-wire instrument
Current signal output
220VAC power supply 24DC power supply T r a n s d u c e r t e r m i n a l
(Corresponding connection)
Host terminal
Engineering
equipment input
24VDC
power supply
24VDC
power supply
Engineering
equipment input
006
Intelligent Integrated 2 Wire, 3 Wire; Split Wall Hanging, Panel Mounting

TEL:400-860-9760
www.Ludwig-Schneider.com.cn
EN
7017872.0609/2018 CH/EN
7.5 Installation Matters
Because of the existence of the ultrasonic level meter's emission angle and blind zone, we must not
choose the installation position too close to the edge, so as not to affect the normal operation of the
meter
Angle mort
Maximum liquid level
Air distance
Installation height G
Current level H
Lowest liquid level
When the displayed L value is equal to the air distance
it means the installation is good
Still pipe
installation Flange mounting Bracket
installation
Do not make
the probe and
the liquid
surface
non-vertical
Do not install
too close to
thecontainer
Do not install
ontop of
obstructions
during sound
wave
transmission
Do not install
in a vacuum
environment
007
Intelligent Integrated 2 Wire, 3 Wire; Split Wall Hanging, Panel Mounting

TEL:400-860-9760
www.Ludwig-Schneider.com.cn
EN
7017872.0609/2018 CH/EN
Ultrasonic Level Meter Menu Simple Setting Operation Instructions
Note: Because the product is constantly updated, the product manual and installation manual cannot
be guaranteed to be consistent with the latest product. If there are changes in the product itself and
the instructions for use, it will not be notified to every customer. If necessary, please contact our sales
staff directly. Changes include but are not limited to the following.
1. Blind zone, performance parameters, function, structure, shape, color, etc. of the product.
2. The function, structure, display mode, and operating habits of the software.
3. Any operation of the hardware must be performed after the power is cut off. If the live operation
causes a short circuit or other fault, it is not covered by the warranty.
The ultrasonic level meter produced by our company, under normal circumstances, according to the
installation requirements of the instructions, after the equipment is installed, you only need to set the
following parameters, the equipment can be used normally.
4. The operation of opening the cover must be performed after the power is turned off, and no liquid
can enter the instrument. If liquid enters and causes failure, it is not covered by the warranty.
There are three keys on the panel, and the instrument can be debugged through these three keys.
The measured value is displayed on the LCD screen after commissioning.
(1) After the meter is powered on, press and hold the SET button for two seconds to enter the first-
level menu.
The menu modes are: expert setting mode and easy setting mode.
Menu lookup table for easy setting mode, as shown in the following table
SET key
◇ Enter menu item ◇ Move cursor
◇ Confirm menu item ◇ Select menu item
◇ Confirm parameter modification ◇ Parameter modification
key
Easy setting mode menu lookup table
Note: Enter the menu for the first time, please press and hold the "SET" button for 2 seconds,
and press the "SET" button to enter
Please enter probe
emission surface
Distance to the
bottom of the pond
10.00m
Please select to
output
Level or distance
Level value
Level value
Distance value
Please enter 4mA
Corresponding
liquid level during
output
0.00 m
Please enter 20mA
Corresponding
liquid level during
output
10.00 m
Finish setting
no
no
Yes
Setting
parameters
Easy setting
mode
For the menu query table of the expert setting mode, see "Six, menu interface and operation instructions:".
08

TEL:400-860-9760
www.Ludwig-Schneider.com.cn
EN
7017872.0609/2018 CH/EN
Ultrasonic Level Meter Menu Simple Setting Operation Instructions
(2) Select the measurement mode:
The measurement mode is divided into distance measurement and level measurement. The factory
default is level measurement.
(3) Enter the height value of the probe into the "reference zero point". (Probe height is the distance
from the probe's emitting surface to the tank or tank bottom)
① In the distance measurement mode, the setting of the reference zero point is meaningless. For the
positions of the high range and low range points, please refer to Figure 1.1.
② In the level measurement mode, refer to Figure 1.2 for the positions of the reference zero point, the
high range point, and the low range point.
Figure 1.1 Schematic diagram of distance measurement
Figure 1.2 Schematic diagram of level measurement
Distance measurement mode: It is to measure the height
of the probe's launch surface to the watersurface, and the
output 4-20ma corresponds to the height change of the
distance. Ultrasonic sensor
Reference zero Low range
point 0%
4mA
20mA
Measuring range
Distance: It is the length fromthe
launch surface of the probeto the
water surface, or solid material
surface.
Distance: It is the length fromthe
launch surface of the probeto the
water surface, or solid material
surface.
Level measurement mode: it is to measure the height from
the water surface to the bottom, and the output 4-20ma
corresponds to the change of the water level.
Range high
point 100%
Blind spot
Reference zero Range high
point 100%
Low range
point 0%
Ultrasonic sensor
Distance: It is the length fromthe
launch surface of the probeto the
water surface, or solid material
surface.
Distance: It is the length fromthe
launch surface of the probeto the
water surface, or solid material
surface.
4mA
20mA
009

TEL:400-860-9760
www.Ludwig-Schneider.com.cn
EN
7017872.0609/2018 CH/EN
High range point: The distance from the reference plane to the position. The value is positive when the
high point of the range is higher than the reference plane, and negative when it is lower than the
reference plane. When the liquid level is in this position, 20mA current is output.
① Alarm mode: select high alarm, low alarm or off.
Low range: The distance from the reference plane to the position. The value is positive when the low
point of the range is higher than the reference plane and negative when it is lower than the reference
plane. When the liquid level is in this position, 4mA current is output.
(4) With relay: Enter the alarm setting option and set three parameters:
② Alarm value: high alarm: alarm when the liquid level is higher than the alarm value
Low alarm: alarm when the liquid level is lower than the alarm value
③ Hysteresis value: Hysteresis value is to prevent measurement error from causing the alarm
switch to jump repeatedly near the alarm point.
High alarm state: the alarm will be canceled when the liquid level is lower than (alarm value-return
difference value)
Low alarm state: the alarm will be canceled when the liquid level is higher than (alarm value + return
difference)
(5) Please set the probe selection, parameter calibration and algorithm selection under the guidance of
professional technicians.
(6) After the equipment is installed, it must be truly grounded separately, and not with the common
ground of the electrical box or meter box.
(7) Suggestion: When the ultrasonic level meter is connected with interference equipment such as
inverters and PLCs, an isolation transformer should be added to the power part, and a signal isolator
should be added to the signal part, and reliable grounding should be done.
·The signal line should not be in the same trough with the power line and power line. It should be
installed separately through metal pipes, or installed away from the power line and power lines. At
least 1 meter.
·This is an important reminder, please read it carefully and do it strictly according to the
requirements.
·This is a general tip, please read it carefully to avoid causing trouble during use.
Graphic description:
Others: Please do not modify the three items of probe selection, parameter calibration and algorithm
selection.
Due to the different on-site installation environment of the instrument. Therefore, the ultrasonic level
meter must know the basic conditions of the measurement before the work, such as: measurement
range, zero point, full range and field conditions, etc. Therefore, the instrument must be set before
measurement. For details, please refer to the “Easy Setting Operation Instructions of the Ultrasonic
Level Gauge Menu” on the first page.
Ultrasonic level meter (measure material level, liquid level) is a non-contact, high reliability, high cost
performance, easy to install and maintain level measurement instrument. It can meet most of the level
measurement requirements without touching the medium. It is a new generation ultrasonic level meter
with completely independent property rights developed by our company after many years of hard
work.
1.Product Introduction
2.Debugging
010
Ultrasonic Level Meter Menu Simple Setting Operation Instructions

TEL:400-860-9760
www.Ludwig-Schneider.com.cn
EN
7017872.0609/2018 CH/EN
3.The Main Technical Indicators
Features
Range
Resolution
Analog output
Relay
Output
powered by
Communication
Protection class
Probe cable
Probe installation
Show
Measurement accuracy
Ambient temperature
Integrated
5m、10m、15m、20m、30m、
40m、50m、60m
Standard 24VDC
Optional 220V AC + 15% 50Hz
Display instrument -20 ~ + 60 ℃,
Probe -20 ~ + 80 ℃
Optional 485, 232 communication
(manufacturer agreement)
Display instrument IP65, probe Ip68
0.5%-1.0%
3mm or 0.1% (whichever is greater)
Chinese LCD
4-wire 4 ~ 20mA / 510Ω load
2-wire 4 ~ 20mA / 250Ω load
Optional 2 sets of AC 250V / 8A or DC 30V / 5A
State programmable
no
Selection based on range and probe
Split type
5m、10m、15m、20m、30m、40m、
50m、60m、70m
0.5%-1.0%
4 ~20mA / 510Ω load
Standard 220V AC + 15% 50Hz
Optional 24VDC 120mA
Custom 12VDC or battery powered
Up to 100 meters, standard 10 meters
Selection based on range and probe
3mm or 0.1% (whichever is greater)
Chinese LCD
Display instrument -20 ~ + 60 ℃,
Probe -20 ~ + 80 ℃
Optional 485, 232 communication
(manufacturer agreement)
Display instrument IP65, probe Ip68
(Optional) single channel is 2 groups,
Dual channels are 4 groups of AC 250V / 8A
or DC 30V / 5A
State programmable
Product power
consumption
Product power
consumption
Product power
consumption
The split type is powered by a 24V power supply. The power consumption without a relay is 100mA,
and with a relay it is 120mA.
145mA for 2 relays, 170mA for 3 relays, 190mA for 4 relays.
The specific power is as follows:
Without relay is 24 × 100mA = 2.4W;
One relay is 24 × 120mA = 2.9W;
2 relays are 24 × 145mA = 3.5W;
3 relays are 24 × 170mA = 4.1W;
4 relays are 24 × 190mA = 4.6W;
The integrated four-wire system is powered by a 24V power supply, the power consumption without a
relay is 80mA, and the one with a relay is 105mA.
2 relays 130mA,
The specific power is as follows:
Without relay is 24 × 80mA = 1.9W;
One relay is 24 × 105mA = 2.5W; two relays are 24 × 145mA = 3.1W;
The integrated two-wire system is powered by a 24V power supply without a relay, and the power
consumption is 30mA.
The specific power is as follows:
Without relay is 24 × 30mA = 0.72W;
Note: This series of ultrasonic probes can also be customized according to customer needs: special
pressure probes such as high pressure resistance, high temperature resistance, small diameter, small
blind area, etc.
011
Ultrasonic Level Meter Menu Simple Setting Operation Instructions

4.Installation Guide
(1)split ultrasonic level meter Standard:
(2) Integrated ultrasonic level gauge enhanced
4.1 Level Gauge Installation Dimensions
Physical map Structure diagram
Physical picture side Physical map positive
M48 × 2 or G1-1 / 2 thread sensor M60 × 2 or G2 thread sensor
012
EN
7017872.0609/2018 CH/EN
Ultrasonic Level Meter Menu Simple Setting Operation Instructions

M78 × 2 thread sensor M78 × 2 thread sensor
(3) Explosion-proof type of integrated ultrasonic level meter:
Physical map Structure diagram
4.2.1 Understanding technical terms
①Range: When selecting the instrument, the meaning of the range is very important. Please see the
diagram below.
4.1 Installation Guide
013
EN
7017872.0609/2018 CH/EN
Ultrasonic Level Meter Menu Simple Setting Operation Instructions

For example: a false echo caused by a pipe 6 meters away from the probe is 9 times stronger than a
false echo caused by the same pipe 18 meters away from the probe.
4.2.2 Measurement range selection
The measurement range depends on the range of the ultrasound probe. The range of the ultrasonic
probe depends on the working environment on site, the target to be measured, and the temperature.
According to the table below, you can choose the measurement range you need is a few meters.
The ultrasonic wave speed is focused by the probe, and the emission of the pulse wave speed is like
the speed of light of a flashlight. The farther away from the probe, the larger the diffusion area.
Any object within the emission angle, such as: pipes, supports, welds, stiffeners, stirring propellers,
and objects on the wall, will cause strong false echoes, especially objects closer to the probe within the
emission angle.
② Launch angle and false echo
★ Try to make the axis of the sensor perpendicular to the surface of the medium, and avoid any other
objects within the launch angle. Such as: pipes and supports.
Liquid surface
smooth
ripple
Large fluctuations (such as
Stirring blade)
Liquid surface
Smooth
Ripple
Large fluctuations (such as
Stirring blade)
Multiple of attenuation
0dB
5...10dB
10...20dB
Percent attenuation
0%
50~67%
90%
Increase the range multiple
No need to increase
1x range
3 times the range
Surface of solid materials
Hard, rough
(such as granular rubber)
Soft (e.g. pulverized coal,
cement, fly ash)
Multiple of attenuation
40dB
40...60dB
Percent attenuation
99%
99~99.9%
Increase the range multiple
10 times range
Not recommended for use
Dusty
No
Small amount
Massive
Multiple of attenuation
0dB
5dB
5...20dB
Percent attenuation
0%
50%
50~90%
Increase the range multiple
No need to increase
1x range
3 times the range
With feed
no
Small amount
Massive
Multiple of attenuation
0dB
5...10dB
10...40dB
Percent attenuation
0%
50~67%
67~99%
Increase the range multiple
No need to increase
1x range
3 times the range
014
EN
7017872.0609/2018 CH/EN
Ultrasonic Level Meter Menu Simple Setting Operation Instructions

Foggy
no
Small amount
Massive
Multiple of attenuation
0dB
5...10dB
10...20dB
Percent attenuation
0%
50~67%
67~90%
Increase the range multiple
No need to increase
1x range
3 times the range
With steam
no
Small amount
Massive
Multiple of attenuation
0dB
5...10dB
10...20dB
Percent attenuation
0%
50~67%
67~90%
Increase the range multiple
No need to increase
1x range
3 times the range
Probe and media surface
temperature difference
≤20℃
≤40℃
≤80℃
Multiple of attenuation
0dB
5...10dB
10...20dB
Percent attenuation
0%
50~67%
67~90%
Increase the range multiple
No need to increase
1x range
3 times the range
Signal attenuation calculation method. If there are multiple situations in the field, it is necessary to add
up these several situations to calculate the amount of signal attenuation.
Total minimum 15dB, maximum 40dB.
▲ It is recommended to use a plastic flange to connect the sensor during installation
4.2.3 bottom thread installation
In this case, if the actual maximum measurement range is 5 meters, you need to use the ultrasonic
level meter with a range of 50 meters.
Temperature difference between probe and medium surface ≤40 ℃ 5 ... 10dB
With a small amount of feed 5 ... 10dB
With a small amount of steam 5 ... 20dB
015
EN
7017872.0609/2018 CH/EN
Ultrasonic Level Meter Menu Simple Setting Operation Instructions

① Install a flange above the measured object ② Put a gasket with the same inner diameter on the flange
③ Align the transducer with the flange hole ④ Put the transducer into the flange hole
⑤ As seen from the bottom of the flange ⑥ Put a gasket with the same inner diameter under the flange
⑦ Screw on the nut to fix the transducer ⑧The installed transducer
016
EN
7017872.0609/2018 CH/EN
Ultrasonic Level Meter Menu Simple Setting Operation Instructions

4.2.4 Top Thread Installation-Hoisting Installation
① Fix the thread on the top of the probe with a nut ② Use a protective tube for the probe inlet
Flange mounting, installed in very short nozzles
The most ideal installation is to directly install the instrument on a flat-topped container, without using
a pipe, the circular opening on the container can be sufficient to fix the flange or universal joint for
installation. The probe emission surface is below the reference surface.
▲ The installation on the tank, pool, cover and bracket is basically the same as above.
★ After the probe is installed, the emission surface of the probe must expose the cover plate or the
waveguide. Do not shrink inside the cover or waveguide.
4.2.5 Measuring liquid
4.2.5.1 Flat-top tank
Flat-top tanks generally have a very short tube. The reference surface of the tube is the bottom
surface of the flange. The length of the tube is ≤60mm, the diameter of the tube is ≥100mm, and the
inner wall of the tube is flat without burrs or protrusions. The emission surface can be measured 3cm
below the bottom surface of the flange.
图片翻译
017
EN
7017872.0609/2018 CH/EN
Ultrasonic Level Meter Menu Simple Setting Operation Instructions