Lumel RE70 User manual

1
1
TEMPERATURE CONTROLLER
48 x 48 mm
RE70
USER’S MANUAL

RE70-09-R1 User's Manual 2
Contents:
1. Application........................................................................................................................ 3
2. Controller set.................................................................................................................... 3
3. Basic requirements, operational safety.......................................................................... 3
4. Installation ........................................................................................................................ 4
4.1. Controller installation................................................................................................... 4
4.2. Electrical connections.................................................................................................. 4
4.3. Recommendations for installation ............................................................................... 5
5. Starting work..................................................................................................................... 6
6. Service............................................................................................................................... 7
6.1. Programming Controller Parameters........................................................................... 7
6.2. Programming matrix.................................................................................................... 8
6.3. Setting Change............................................................................................................ 9
6.4. Parameters description ............................................................................................. 10
7. Inputs and outputs of the controller............................................................................. 12
7.1. Inputs ........................................................................................................................ 12
7.1. Output ....................................................................................................................... 12
8. Control............................................................................................................................. 13
8.1. ON-OFF algorithm..................................................................................................... 13
8.2. Innovative SMART PID algorithm.............................................................................. 13
9. Alarms............................................................................................................................. 15
10. Additional functions..................................................................................................... 16
10.1. Displaying the control signal.................................................................................... 16
10.2. Manual mode........................................................................................................... 16
10.3. Defaults Settings ..................................................................................................... 16
11. RS-485 interface with MODBUS protocol................................................................... 16
11.1. Introduction ............................................................................................................. 16
11.2. Error codes.............................................................................................................. 17
11.3. Register map........................................................................................................... 17
12. Error signaling.............................................................................................................. 20
13. Technical data............................................................................................................... 21
14. Controller ordering code ............................................................................................. 22

RE70-09-R1 User's Manual 3
1. Application
The RE70 controller is destined for the temperature control. Controller works
directly with the resistance sensors or thermoelectric sensors.
The controller is equipped with one output that allows for dual-point control
and alert signalization. Dual-point control is based on the PID or ON/OFF
algorithm. Relay output is equipped with a switchable contact and allows for
indirect control of the low-power objects.
The innovative SMART PID algorithm has been implemented in the
controller.
2. Controller set
1
1234
OUTST
SP
5
RE70
2
3
4
Complete set of the controller includes:
1. controller ...................................... 1 pc
2. plug with 6 screw terminals .......... 1 pc
3. plug with 8 screw terminals .......... 1 pc
4. holders to fix the meter in the panel 4 pcs
5. seal............................................... 1 pc
6. user’s manual............................... 1 pc
3. Basic requirements, operational safety
In terms of operational safety the controller meets the requirements
of the EN 61010-1 standard.
Comments concerning safety:
Assembly and installation of the electrical connections should conducted
only by people authorised to perform assembly of electric devices.
Always check the state of connections before turning the controller on.
Prior to taking the controller housing off, always turn the supply off
and disconnect measuring circuits.
Removal of the controller housing during the warranty period voids the
warranty.
The device is designed to installation and usage in the industrial
electromagnetic environment.

RE70-09-R1 User's Manual 4
The installation should have a switch or a circuit-breaker installed. This
switch should be located near the device, easy accessible by the operator
and suitably marked.
4. Installation
4.1. Controller installation
Fix the controller to the board with four screw brackets as shown
in the fig. 1. A slot in the panel must have the dimensions 45+0,6 x 45+0,6 mm.
The thickness of the panel material cannot exceed 15 mm.
12
Fig. 1. Controller installation.
Dimensions of the controller are presented on the fig. 2.
70
8max. 93
max.15
48
48
Fig. 2. Controller dimensions.
4.2. Electrical connections
The controller has two separate connectors with screw terminals. One strip
enables the connection of the supply and outputs by a wire of 2,5 mm2,
the second strip enables input signal connections by a wire of 1,5 mm2.

RE70-09-R1 User's Manual 5
Fig. 3. View of the controller's connection strips.
5
4
3
Pt100
5
4
3
Pt100
5
4
3
Pt1000
2
1
+
-
thermoresistor Pt100
in 2-wire system
thermoresistor Pt100
in 3-wire system
thermoresistor
Pt1000 thermocouple
Fig. 4. Input signals
suppl
y
13
14
Fig. 5. Supply
supply
9
11
10
load
Fig. 6. Control/Alarm output
A (+)
B(-)
8
7
Fig. 7. RS-485 interface (only for configuration)
4.3. Recommendations for installation
To achieve full electromagnetic resistance of the controller, it is necessary
to follow the rules described below:
─do not supply the controller from the network in the proximity of devices
generating high pulse noises and do not apply common earthing circuits,
─apply network filters,

RE70-09-R1 User's Manual 6
─wires leading measuring signals should be twisted in pairs, and for
resistance sensors in 3-wire connection, twisted of wires of the same
length, cross-section and resistance, and led in a shield,
─all shields should be one-side earthed or connected to the protection
wire, the nearest possible to the controller,
─as a rule of thumb, wires transmitting different signals should be spaced
as far as it is possible (at least 30 cm) and should be crossed only at the
right angle of 90.
5. Starting work
Controller description
self-tune indicator
display for
measured value,
set point, menu
active output
indicator
manual mode indicator
keys
display set point
indicator
Fig. 8. Overview of the controller's front panel.
Switching a supply on
After powering on, the controller performs the display test, displays re70
text, software version and the measured value.
Display may also show an error message (see table 11).
The ON-OFF control algorithm with hysteresis given in the table 2 is set by
the defaults.
Change of the set point
Set point is displayed after ? or > buttons are pressed, this is
accompanied by SP diode switching on. To change the set point, press ? or
> buttons again (fig. 9). The beginning of the change is signaled by pulsing
dot symbol on the display. New set point must be accepted with a @ button
within 30 seconds after the ? or > button have been pressed, otherwise
regulator will display set point with previously set point.

RE70-09-R1 User's Manual 7
to change set-point press and hold one of the button
accept new
set-point
set-point
change
indicator
measured
value
or
Fig. 9. Change value of the set point.
6. Service
The controller service is presented on the fig. 10.
Fig. 10. Menu of controller service
6.1. Programming Controller Parameters
Pressing and holding down during ca 2 seconds the button @ causes the
entry to the programming matrix. The programming matrix can be protected by
an access code. In case when giving a wrong value of the code, it is only
possible to see settings through - without possibility of changes.
p
arameter
p
rogramming
mode
2sec.
2sec.
+
+
+
to change press
to cancel press
o
r
press and hold
to increase
the value
press and hold
to decrease
the value
to accept press
3sec.
2 sec.
correct
code?
N
Y
N
Y
active
access
code
display control
signal
locking of change
normal working mode change set point
mode
+
measured
value
h___
tune
set point
code
err
manual
mode
self-tune
mode

RE70-09-R1 User's Manual 8
Fig. 11 presents the transition matrix in the programming mode.
The transition between levels is carrying out by using the buttons ? or >
and the level selection by using the button @ . After selecting the level, the
transition between parameters is carried out by using the buttons ? or > .
In order to change the parameter setting proceed acc. to the section 6.3. In
order to exit from the selected level, transit between parameters until appears
the symbol [. . .] and press the button @ . In order to exit from the
programming matrix to the normal working mode, transit between levels until
appears the symbol [. . .] and press the button @ .
Some controller parameters can be invisible – it depends on the current
configuration. The description of parameters shows the table 1. The return
to the normal working mode follows automatically after 30 seconds since
the last button pressure.
6.2. Programming matrix
inp unit iNty t-li sHif dp . . .
Input
parameters
Unit Input type Type of line
Shift of
measured
value
Position of
decimal
point
Transition
to the higher
level
outp out . . .
Output
parameters
Output
configuration
Transition
to the higher
level
ctrl alg type Hy sTlo sTHi . . .
Control
parameters
Control
algorithm
Type of
control Hysteresis
Lower
threshold for
self-tuning
Upper
threshold for
self-tuning
Transition
to the higher
level
pid pb ti td y0 to . . .
PID
Parameters
Proportional
band
Integral time
constant
Derivative
time
constant
Correction
of control
signal, for P
or PD
control
Pulse period
Transition
to the higher
level
alar aLsp aLdu aLHy . . .
Alarms
parameters
Set point for
the absolute
alarm
Deviation
from the set
point of the
relative
alarm
Alarm
hysteresis
Transition
to the higher
level
spp spl spH . . .
Set point
parameters
lower
limitation of
the set point
setting
upper
limitation of
the set point
setting
Transition
to the higher
level
seru seCU sTfn . . .
Service
parameters
Access code Self-tuning
function
Transition
to the higher
level
. . .
Exit from
the menu
Fig. 11. Programming matrix

RE70-09-R1 User's Manual 9
6.3. Setting Change
The change of parameter setting begins after pressing the button @ during
the display of the parameter name. The setting selection is carried out through
the buttons ? and > and accepted by the button @ . The change
cancellation follows after the simultaneous pressure of the buttons ? and >
or after 30 seconds since the last button pressure. The way to change the
setting is shown on the fig. 12.
1234
to change
press cancel
increment
value
decrement
value
accept new
value
+
oNof
to change
press cancel
next text
value
previous
text value
accept new
value
+
Fig. 12. Setting change of number and text parameters.

RE70-09-R1 User's Manual 10
6.4. Parameters description
The list of parameters is presented in the table 1.
List of configuration parameters Table 1
Symbol
of
parameter Parameter description Default setting Range of parameter change
inp – Input parameters
unit
Unit qC qC: degrees Celsius
qf: degrees Fahrenheit
iNty
Input type pt1
pt1: Pt100
pt10: Pt1000
t-,: J type thermocouple
t-t: T type thermocouple
t-k: K type thermocouple
t-s: S type thermocouple
t-r: R type thermocouple
t-b: B type thermocouple
t-n: N type thermocouple
t-li
Line type for the sensor Pt100 2-p 2-p: 2-wire
3-p: 3-wire
dp Position of the decimal point 1-dp 0_dp: without a decimal place
1_dp: 1 decimal place
shif
Shift of measured value 0.0 °C
(0.0 °F)
-100.0100.0 °C
(-180.0180.0 °F)
outp – Output parameters
out
Output configuration y
off: control off
Y: control signal
AHi: upper absolute alarm
Alo: lower absolute alarm
dwHi: upper relative alarm
dwlo: lower relative alarm
dwin: internal relative alarm
dwou: external relative alarm
ctrl – Control parameters 1)
alg
Control algorithm oNof oNof: ON-OFF control algorithm
pid: PID control algorithm
type
Type of control inu dir: direct control (cooling)
inu: reverse control (heating)
Hy Hysteresis 4) 2.0 °C
(3.6 °F)
0.2100.0 °C
(0.2180.0 °F)
sTlo
Lower threshold for self-tuning 0.0 °C
(32.0 °F) MIN…MAX 6)
sTHi
Upper threshold for self-tuning 800.0 °C
(1,472.0 °F) MIN…MAX 6)

RE70-09-R1 User's Manual 11
pid – PID parameters 2)
pb Proportional band 30.0 °C
(540.0 °F)
0.1550.0 °C
(0.1990.0 °F)
ti Integral time constant 300 09999 s
td Derivative time constant 60.0 0.02500 s
y0 Correction of control signal,
for P or PD control 0.0 0100.0 %
to Pulse period 20.0 0.599.9 s
alar – Alarms parameters 3)
aLsp
Set point for the absolute alarm 0.0 °C
(32.0 °F) MIN…MAX 6)
aLdu
Deviation from the set point of
the relative alarm
0.0 °C
(0.0 °F)
-200,0200,0 °C
(-360.0360.0 °F)
aLHy
Hysteresis for the alarm 2.0 °C
(3.6 °F)
0.2100.0 °C
(0.2180.0 °F)
spp – Set point parameters
spl
Lower limitation of the set point
setting
-200.0 °C
(-3,280.0 °F) MIN…MAX 6)
spH
Upper limitation of the set point
setting
1,767.0 °C
(3,212.6 °F) MIN…MAX 6)
serp – Service parameters
seCU
Access code 5) 0 0…9999
sTfn
Self-tuning function on off: locked
on: available
1) Group of parameters visible only when setting the output on the control signal.
2) Group of parameters visible only when setting the control algorithm on PID.
3) Group of parameters visible only when setting the output on one of the alarm.
4) Parameter visible only when setting the control algorithm on ON-OFF.
5) Parameter hidden in the monitoring mode of parameters only for readout.
6) See table 2.
Range limits for inputs Table 2
Input / sensor MIN MAX
°C °F °C °F
Thermoresistor Pt100 -200 °C -328 °F 850 °C 1,562 °F
Thermoresistor Pt1000 -200 °C -328 °F 850 °C 1,562 °F
J type thermocouple -50 °C -58 °F 1,200 °C 2,192 °F
T type thermocouple -50 °C -58 °F 400 °C 752 °F
K type thermocouple -50 °C -58 °F 1,372 °C 2,501.6 °F
S type thermocouple 0 °C 32 °F 1,767 °C 3,212.6 °F
R type thermocouple 0 °C 32 °F 1,767 °C 3,212.6 °F
B type thermocouple 0 °C 32 °F 1,767 °C 3,212.6 °F
N type thermocouple -50 °C -58 °F 1,300 °C 2,372 °F

RE70-09-R1 User's Manual 12
7. Inputs and outputs of the controller
7.1. Inputs
Input is the source of the measured value used for control or for alarms.
The input is universal and the sensors Pt100, Pt1000 or thermocouples can be
connected to it.
Start by using a unit parameter to set the temperature display unit.
Unit change resets the value to the factory settings, with a different value
ranges for Celsius and Fahrenheit scale.
Input signal is selected with a iNty parameter.
For the Pt100 thermoresistor, choose the t-li connection type - 2-wire
or 3-wire. In the 3-wire Pt100 connection, resistance compensation is
automatic.
For thermocouples, a cold terminal compensation is automatic.
Position of the decimal point is a additional parameter that determines
display format of measured value and set point; it is set by the dp parameter.
Correction of the indicated measured value is determined by the shif
parameter.
7.1. Output
The controller has one output. It is possible to choose the following output
options: on-off control, proportional control (PID) or alert. It is necessary to set
the pulse period for the proportional control.
Pulse period is a time between two subsequent input engagements during
proportional control. Pulse period length should be adjusted for the dynamic
properties of the object and characteristics of the output device. It is
recommended to use SSR transmitter for quick processes. Relay output is
used for a contactor control in the slow-changing processes. Long pulse
periods for quick-change processes may cause unnecessary oscillation. In
theory, the shorter pulse period is, the better the control, however for the relay
output a period should be as large, as possible to optimize lifespan of the relay.
Pulse period setting recommendations Table 3
Output Pulse period is Load
electromagnetic transmitter
recommended >20s
min. 10 s
5 A/230 VAC
or a contactor
min. 5 s 2 A/230 VAC

RE70-09-R1 User's Manual 13
8. Control
8.1. ON-OFF algorithm
When high accuracy of a temperature control is not required, especially
for the high time constant and small delay, it is possible to use ON-OFF control
with hysteresis. Disadvantage of this method is the occurrence of oscillations,
even at small hysteresis values.
Fig. 13. Operation way of the heating type output for the ON-OFF control.
8.2. Innovative SMART PID algorithm
When high precision of the temperature control is necessary,
it is recommended to use PID algorithm. Innovative SMART PID algorithm
ensures increased precision in the extended range of the control object
classes.
Tuning of the controller to object is achieved by automatically selected PID
parameters using the self-tuning function or manual setting the value of the
proportional element, integral element and derivative element.
8.2.1. Self-tuning
The controller has the function to select PID settings. In most cases these
settings ensure an optimal control.
To begin the self-tuning, transit to the tune message (acc. to the fig. 10)
and hold down the button @ during at least 2 sec. If the control algorithm is
set on ON-OFF or the self-tuning function is locked, then the tune message
tune is hidden.
For a correct realization of the self-tuning function, it is required to set the
parameters sTlo and sTHi. The parameter sTlo should be set on the
value corresponding to the measured value at the switched off control.
For object temperature control, you can set 0ºC. The parameter sTHi should
on
off
setpoint
value measured
value
h
y
steresis
out
p
ut

RE70-09-R1 User's Manual 14
be set on the value corresponding to the maximum measured value when
the control is switched on the full power.
The flickering AT symbol informs about the activity of the self-tuning
function. The duration of self-tuning depends on dynamic object properties
and can last maximally 10 hours. During self-tuning or directly after it,
over-regulations can occur and because of this, one must set a smaller set
point if possible.
The self-tuning is composed of following stages:
self-tuning process
- calculation of PID settings and stored
them in the non-volatile memory
- start control with new PID settings
- enter to manual mode
- the error code is on the display until
confirmation
self-tuning
ended
with success
YES NO
The self-tuning process will be stopped without counting PID settings,
if a supply decay occurs or the button @ will be pressed. In this case, the
control with current PID settings will be started.
If the self-tuning experiment does not end with success, then an error code will
be displayed, acc. to the table 4.
Error codes for self-tuning function Table 4
Error code Reason Procedure
eS01 P or PD control was selected. One must choose PI, PID control, i.e.
the TI unit must be higher than zero.
eS02 The set point is incorrect. Change temperature set point or the
parameters sTlo, sTHi.
eS03 The button @ was pressed.
eS04 The maximal self-tuning duration time
has been exceeded.
Check, if the temperature sensor is
correctly situated, if the set point value
is not set too higher for the given
object.
eS05 The waiting time of switching has been
exceeded.
eS06 The input range limit has been
exceeded.
Take note of the way to connect the
sensor. Do not allow that the overflow
results in exceeding of the input range
limit.
eS20 Very non-linear object, enabling to obtain
correct values of PID parameters, or an
interference has occurred.
Carry out the self-tuning again. If that
does not help, choose PID parameters
manually.

RE70-09-R1 User's Manual 15
8.2.2. Proceeding in case of a unsatisfactory PID control
It is recommended to choose PID parameters, changing the value in a twice
higher or twice less. During the change, one must respect following principles.
a) Free jump response:
decrease the proportional band,
decrease the integral and derivative time.
b) Over-regulations
increase the proportional band,
increase the derivative time,
c) Oscillations
increase the proportional band,
increase integral time,
decrease the derivative time,
d) Instability
increase the integral time.
9. Alarms
The controller output can be configured as an alarm output. For this, set the
parameter out as one of alarms. Available types of alarms are given on the
figure 14.
aLsp
absolute high
(out = AHi)
aLsp
absolute lower
(out = Alo)
SP
aLdu
(+)
relative high
(out = dwHi)
SP
aLdu
(-)
relative high
(out = dwHi)
SP
aLdu
(+)
relative lower
(out = dwlo)
SP
aLdu
(-)
relative lower
(out = dwlo)
SP
aLdu
aLdu
relative internal
(out = dwin)
SP
aLdu
aLdu
relative external
(out = dwou)
Fig.14. Types of alarms
The set point for absolute alarms is the value defined by the parameter
aLsp, and for relative alarms, it is the deviation from the set point -
the parameter aLdu. Alarm hysteresis, the zone around the set point in which
the input state is not changed is defined by the aLHy parameter.

RE70-09-R1 User's Manual 16
10. Additional functions
10.1. Displaying the control signal
After pressing the button @ the value of the control signal (0100%)
is displayed on the display. On the first digit the h mark is displayed. Control
signal can be displayed when the out parameter is set on y.
10.2. Manual mode
The manual mode gives the possibility to identify, test the object,
or control it after a sensor damage.
The entry to the manual mode follows after holding down the button @
during the control signal is display. The manual mode is signaled by the
pulsation of the diode with the symbol . The controller interrupts the automatic
control and begins the manual mode of the output. The control signal value is
on the display, preceded by the symbol h.
For the ON-OFF control – the control signal can be set up by the buttons ?
and > at 0% or 100%.
For the PID control – the control signal can be set up by the buttons ?
and > at any optional value from the 0.0100% range.
The exit to the normal work mode follows after pressing simultaneously the
buttons ? and > .
10.3. Defaults Settings
Defaults settings can be restored during the supply connection by holding
down the buttons ? and > till the moment when the inscription fabr
appears on the display.
11. RS-485 interface with MODBUS protocol
11.1. Introduction
RE70 controller is equipped with RS-485 serial interface with implemented
MODBUS asynchronous communication protocol. The interface is designed for
controller configuration prior to using it.
Summary of the RE70 controller serial interface:
device address: 1,
baud rate: 9600 bit/s,
operation modes: RTU,

RE70-09-R1 User's Manual 17
information unit: 8N2,
data format: integer (16 bits)
maximum response time: 500 ms,
maximum number of registers read/written in one command: 32.
RE70 controller uses following protocol functions:
Table 5
Code Meaning
03 n-registers read
06 1 register write
16 n-registers write
17 slave device identification
11.2. Error codes
If the controller receives query with the transmission error or checksum
error, then such query will be ignored. When a query with correct syntax and
invalid values is found, the controller returns an error code.
Table 6 shows error codes and their meaning.
Error codes Table 6
Code Meaning Reason
01 illegal function function is not handled by the controller
02 illegal data address register address out of range
03 illegal data value register value out of range or register is readout only
11.3. Register map
In the controller, data are placed in 16-bit registers. The list of registers for
write and readout is presented in the table 7. Operation "R-" – means
the possibility of readout, and the operation "RW" means the possibility
for readout and write.
Map of the registers from address 4000 Table 7
Register
address Marking Opera
tion Parameter range Description
4000 -W 1
Command register
1 – revert to defaults settings (except for
interface settings and defined programs)
4001 R- 100…999 Program version number [x100]
4002 R- 1301…9999 Older 4 digits of the serial number
4003 R- 1…9999 Younger 4 digits of the serial number
4004 R- 0…0xFFFF Controller status – description in the table 8
4005 R- 0…0xFFFF Error status – description in the table 9
4006 R- acc. to the table
10 Measured value PV
4007 R- acc. to the table
10 Current set point SP
4008 R- 0…1000 Control signal [% x10]

RE70-09-R1 User's Manual 18
Register
address Marking Opera
tion Parameter range Description
4009 UNIT RW 0…1
Unit
0 – degrees Celsius
1 – degrees Fahrenheit
4010 INPT RW 0…8
Type of main input:
0 – thermoresistor Pt100
1 – thermoresistor Pt1000
2 – J type thermocouple
3 – T type thermocouple
4 – K type thermocouple
5 – S type thermocouple
6 – R type thermocouple
7 – B type thermocouple
8 – N type thermocouple
4011 T-LI RW 0…1
Type of line
0 – 2-wire
1 – 3-wire
4012 DP RW 0…1
Position of the decimal point of the main
input
0 – without a decimal place
1 – 1 decimal place
4013 SHIF RW
-1000...1000
[x10 C]
-1800…1800
[x10 F]
Shift of the measured value of the main input
4014 OUT RW 0…7
Output function
0 – no function
1 – control signal
2 – upper absolute alarm
3 – lower absolute alarm
4 – upper relative alarm
5 – lower relative alarm
6 – internal relative alarm
7 – external relative alarm
4015 ALG RW 0…1
Control algorithm
0 – ON-OFF
1 – PID
4016 TYPE RW 0…1
Type of control
0 – direct control – cooling
1 – reverse control – heating
4017 HY RW 2…1000 [x10 C]
2…1800 [x10 F] Hysteresis HY
4018 STLO RW acc. to the table
10 Lower threshold for self-tuning
4019 STHI RW acc. to the table
10 Upper threshold for self-tuning
4020 PB RW 1…5500 [x10 C]
1…9900 [x10 F] Proportional band PB
4021 TI RW 0…9999 Integral time constant TI [s]
4022 TD RW 0…25000 Derivative time constant TD [s x10]
4023 Y0 RW 0…1000 Correction of control signal Y0 (for P or PD
control) [% x10]

RE70-09-R1 User's Manual 19
Register
address Marking Opera
tion Parameter range Description
4024 TO RW 5…999 Pulse period of output [s x10]
4025 ALSP RW acc. to the table
10 Set point for the absolute alarm [x10]
4026 ALDV RW
-1800…1800
[x10 C]
-3600…3600
[x10 F]
Deviation from the set point of the relative
alarm
4027 ALHY RW 2…1000 [x10 C]
2…1800 [x10 F] Hysteresis for the alarm
4028 SPL RW acc. to the table
10 Lower limitation of the fast set point change
4029 SPH RW acc. to the table
10 Upper limitation of the fast set point change
4030 SECU RW 0…9999 Access code to the menu
4031 STFN RW 0…1
Self-tuning function
0 – locked
1 – unlocked
Register 4002 – controller status Table 8
bit Description
0-11 Reserved
12 Automatic/Manual mode: 0 – automatic, 1 – manual
13 State of alarm: 0 – active, 1 – inactive
14 Measured value beyond the range limits
15 Controller error – check the error register
Register 4003 – error register Table 9
bit Description
0-14 Reserved
15 Input discalibrated
Input range limits Table 10
Sensor type Range
UNIT = °C [x10] UNIT = °F [x10]
Pt100 -2000…8500 -328015620
Pt1000 -2000
8500 -328015620
Fe-CuNi (J) -500
12000 -58021920
Cu-CuNi (T) -500
4000 -5807520
NiCr-NiAl (K) -500
13720 -58025016
PtRh10-Pt (S) 0
17670 32032126
PtRh13-Pt (R) 0
17670 32032126
PtRh30-PtRh6 (B) 0
17670 32032126
NiCrSi-NiSi (N) -500
13000 -58023720

RE70-09-R1 User's Manual 20
12. Error signaling
Character messages signaling the incorrect controller operation. Table 11
Error code Reason Procedure
____
Down overflow of the
range limit or lack of RTD
Check, if input signal values are situated in the
appropriate range – if yes, check if check if there is
no short circuit in the thermoresistor or the
thermocouple is connected inversely.
::::
Upper overflow of the
range limit or break in the
sensor circuit
Check, if input signal values are situated in the
appropriate range – if yes, check if there is no break
in the sensor circuit.
eRad
Input discalibrated Connect the controller supply again and if that is not
effective, contact the nearest service shop.
eRee
Configuration parameters
checksum error
Connect the controller supply again and if that is not
effective, contact the nearest service shop.
Other manuals for RE70
2
Table of contents
Other Lumel Temperature Controllers manuals