This guide is divided into sections. Each section deals with a particular feature or set of features
of the Energi Savr NodeTM unit and the equipment connected to it. Depending on the connected
equipment and the intended use of your Energi Savr NodeTM unit, some sections may not apply.
See below to determine which sections should be read.
0-10VOutputs l Salidas l Sorties
4X50 mA
(SinkingOnlylRecepcion solamente l Récepteur de courant seulement)
QSN-4T16-S-347
120-277V~
50/60Hz 500 mA
0-10V / Softswitch
®
24/7Help|Ayuda | Aide www.lutron.com
U.S.A.CanadáCaribbean| E.U.A. Caribe | É.-U.,Caraïbes 1.800.523.9466
México +1.888.235.2910
Others|Otros| Autres +1.610.282.3800
Coopersburg,PA18036,U.S.A.
500-14444Rev.A
savingenergy since1961
Energi Savr Node
TM
Type1
Enclosure
243C
LISTED
Ind.
Cont.Eq.
4Softswitch
®
CircuitslCircuitos
CapacitylCapacidad l Capacité :
IECPELV/ NEC®Class 2
InputGroups| Grupos de entrada
Groupesd’entreés:
20V-4 X 65 mA
QSLink| Elance | Liaison :
24V-462 mA
WARNING
RiskofElectricShock. May Result in serious injury or death.
Morethanonedisconnect may be required to de-energize
thisdevice.Disconnectall power sources before servicing
unit.
ADVERTENCIA
Riesgochoqueeléctrico.Puede resultar en lesiones graves o
muerte.Puedenecesitarsemás de una desconexión para
desenergizarestedispositivo.Desconecte todas las fuentes
dealimentaciónantesde prestar servicio a la unidad.
AVERTISSEMENT
Risqued'électrocution.Peutcauserle décès de la personne
oudegraveslésions. Plus d’un débranchement peut être
Débranchertouteslessources d’énergie avant de procéder
àl’entretiendecette unité.
®
4x16 A 120-277V~
4x0,5 HP 120V~
4x1,5 HP 277V~
4x16 A 347V~
All Energi Savr NodeTM units
Read:
»Load Setup
Energi Savr NodeTM with Softswitch®unit
(QSN-4S16-S, QSN-4S16-S-347, QSN-4S20-S)
Energi Savr NodeTM for 0-10 V unit
(QSN-4T16-S, QSN-4T16-S-347, QSN-4T20-S)
Type1
Enclosure
4Softswitch
®
CircuitslCircuitos
CapacitylCapacidad l Capacité :
QSN-4S16-S-347
120-277V
50/60Hz 500 mA
Softswitch
®
Coopersburg,PA18036,U.S.A.
500-14445Rev.A
savingenergy since1961
Energi Savr Node
TM
WARNING
RiskofElectricShock. May Result in serious injury or death.
Morethanonedisconnect may be required to de-energize
thisdevice.Disconnectall power sources before servicing
unit.
ADVERTENCIA
Riesgochoqueeléctrico.Puede resultar en lesiones graves o
muerte.Puedenecesitarsemás de una desconexión para
desenergizarestedispositivo.Desconecte todas las fuentes
dealimentaciónantesde prestar servicio a la unidad.
AVERTISSEMENT
Risqued'électrocution.Peutcauser le décès de la personne
oudegraveslésions. Plus d’un débranchement peut être
Débranchertouteslessources d’énergie avant de procéder
àl’entretiendecette unité.
®
24/7Help|Ayuda | Aide www.lutron.com
U.S.A.CanadáCaribbean| E.U.A. Caribe | É.-U.,Caraïbes 1.800.523.9466
México +1.888.235.2910
Others|Otros| Autres +1.610.282.3800
243C
LISTED
Ind.
Cont.Eq.
IECPELV/ NEC®Class 2
InputGroups| Grupos de entrada
Groupesd’entreés:
20V-4 X 65 mA
QSLink| Elance | Liaison :
24V-462 mA
4x16 A 120-277V~
4x0,5 HP 120V~
4x1,5 HP 277V~
4x16 A 347V~
LED Feedback
LED LED Behavior Description
Occ
(Occupancy Sensor)
Continuous On Sensor detects Vacancy
1 flash per second Sensor detects Occupancy
Off Sensor never detected
Daylight
(Daylight Sensor )
Continuous On Sensor is detected
Flashing Sensor information transmitting on
the QS link
Off Sensor never detected/sensor not
seeing light
IR
(Infrared Receiver)
Continuous On Receiver is detected
Flashing IR button press detected
Off Receiver never detected
Switch
(NEC®Class2 Switch)
Continuous On Switch detected/open
Flashing Switch button press detected
Off Switch never detected
CCI
(Contact Closure Input)
Continuous On Contact detected/open
Flashing Contact closed
Off Contact never detected
Emerg
(Emergency Contact
Closure Input)
Continuous On Normal operation/Contact Closed/
Jumpered
Rapid flash Emergency Mode/Contact Open/
Jumper missing
QS Link
On/Flashing /Device transmitting/receiving on the
QS link
3 quick flashes every
4 seconds Communication error
Off Device not transmitting/receiving on
the QS link
Wired Continuous On Wired sensor
Zone Continuous On Load is on
Off Load is off
Troubleshooting using Symptoms
Symptom Cause Solution
Unable to add daylight
sensor to a zone
Existing daylight sensor
already assigned to the zone
Unassign the existing daylight sensor and
try again.
Unable to add an
occupancy sensor to
a zone
16 sensors have already
been assigned
No more than 16 sensors can be assigned
to one ESN unit. Unassign sensors until
below 16 sensor limit.
Daylight sensor fails to
turn on a zone
Occupancy sensor is
overriding the zone
Daylight sensors will not turn a zone on if
an occupancy sensor assigned to that zone
detects that the room is vacant.
Switched zone daylighting:
incorrect light level set during
Daylighting Setup
Reset the daylighting set point. See
Daylighting Setup.
When associating a
QSM to the Energi Savr
NodeTM unit, the ‘QSM’
LED flutters for 1
second, then turns off
A QSM has already been
associated to the Energi
Savr NodeTM unit.
To clear the QSM association and any
Energi Savr NodeTM unit zone assignments
to any QSM inputs, press and hold the
Input button on the Energi Savr NodeTM unit
for 10 seconds. The ‘Input’ LED will flutter
for 1 second, then turn off.
When associating a
wireless input device
to a QSM, the QSM
responds with 10 short
beeps
Maximum number of
associations to the QSM has
been exceeded for that
wireless input device type.
Unassign any unnecessary wireless inputs of
that device type and try again.
When associating a
wireless input device
to a QSM, the QSM
responds with 5 short
beeps
Input device is already
associated to another QSM
on the QS link.
If you choose to ignore the warning and try
to associate the same input device to the
QSM a second time, the input device will be
removed from association with the previous
QSM and will now be associated with the
new QSM. Note: This will also remove any
Energi Savr NodeTM
programming that the wireless device may
have had through the previous QSM.
QS Link LED quickly
flashes 3 times every 4
seconds
QS Link communication
error.
Check QS Link wiring
Technical Assistance
U.S.A. / Canada: 1.800.523.9466 Mexico: +1.888.235.2910 Other Countries: +1.610.282.3800
IMPORTANT NOTES
Energi Savr NodeTM with Softswitch®unit
(QSN-4S16-S, QSN-4S16-S-347, QSN-4S20-S)
Energi Savr NodeTM for 0-10 V unit
(QSN-4T16-S, QSN-4T16-S-347, QSN-4T20-S)
Energi Savr NodeT
manual programming guide English
1. Manual Programming: This document describes manual
programming via the buttons on the front of the Energi Savr
NodeTM unit. For programming using the Apple iPod touch
or iPhone mobile digital devices, please see the Energi Savr
NodeTM app available from the Apple AppStore online store.
2. Use only compatible Lutron®sensors and controls.
032449 | Rev. C | 05/2014
24/7 Help
U.S.A., Canada and the Caribbean
1.800.523.9466
México
+1.888.235.2910
Others
+1.610.282.3800
Fax
+1.610.282.6311
w
w
w
.
l
u
t
r
o
n
.
c
o
m
If you have wired sensor inputs wired directly to the Energi Savr NodeTM unit input group terminal
blocks, see below to determine which additional sections to read.
www.lutron.com
© 2014 Lutron Electronics Co., Inc.
P/N 032449 Rev. C 05/2014
Apple, iPhone, and iPod touch are trademarks of Apple Inc., registered in the U.S. and other countries.
AppStore is a service mark of Apple Inc.
Lutron, GRAFIK Eye, Pico, seeTouch, Softswitch and )are registered trademarks, and Energi Savr
Node and Radio Powr Savr are trademarks of Lutron Electronics Co., Inc.
All Wired Inputs
Read:
»Energi Savr NodeTM
(ESN) Unit Wired Input
Setup
OR
Energi
Savr
NodeTM
Unit
LUTRON
Dry Contact
Closure
Switch
Wires to “Switch”,
“CCI”, or “EMERG”
Input
»Energi Savr
NodeTM (ESN)
Unit Wired
Input Setup
Wired
Occupancy
Sensor
Wires to “Occ” Input
Additional Sections:
»Energi Savr NodeTM (ESN)
Unit Wired Input Setup
»Occupancy Setup
Wired Wallstation
or Infrared (IR)
Sensor
Wires to “IR” Input
»Energi Savr
NodeTM (ESN)
Unit Wired
Input Setup
Wired
Daylight
Sensor
Wires to “Daylight” Input
Additional Sections:
»Energi Savr NodeTM (ESN)
Unit Wired Input Setup
»Daylighting Setup
If you have a QSM wired to the Energi Savr NodeTM unit QS Link terminal block, read sections QS Sensor
Module (QSM) Input Setup and QS Sensor Module (QSM) Zone Assignment. Some parts of the section
may not apply, depending on the devices connected to the QSM. See below to determine which additional sub-
sections to read for each type of connected device.
QSM Wireless Input Devices
Communicates with QSM via Radio Frequency (RF)
Read:
»Subsection: Associating Wireless Input
Devices to a QSM
QS Sensor Module (QSM)
Wires to “QS Link” Terminal Block on
Energi Savr NodeTM unit
Wireless
Occupancy
Sensor
Additional Sections:
»Occupancy Setup
»Subsection: Assign Zones to
QSM Inputs
Wireless
Daylight
Sensor
Additional Sections:
»Daylighting Setup
»Subsection: Assign Zones to
QSM Inputs
Wired
Occupancy
Sensor
Additional Sections:
»Occupancy Setup
»Subsection: Assign Zones to
QSM Inputs
Wired
Daylight
Sensor
Additional Sections:
»Daylighting Setup
»Subsection: Assign Zones to
QSM Inputs
LUTRON
Pico®
Wireless
Controller
Additional Sections:
»Subsection: Assign Zones to Pico®
Wireless Controller (through QSM)
QS Link
Wired Wallstation
or Infrared (IR)
Sensor
Additional Sections:
»Subsection: Assign Zones
to QSM Inputs
OR
Energi
Savr
NodeTM
Unit
QS
Sensor
Module
Read:
»QS Sensor Module (QSM)
Input Setup
»QS Sensor Module (QSM)
Zone Assignment
QSM Wired Input Devices
Wires to Input Terminal Blocks on QSM
Read:
»Subsection: Associating Wired
Input Devices to a QSM
QS Link
If you have other devices wired to the Energi Savr NodeTM unit QS Link terminal block, see below to determine
which additional sections to read.
Energi
Savr
NodeTM
Unit
Wired
seeTouch®QS
Wallstation
Additional Sections:
»Wired seeTouch®QS Wallstations Programming
QSE-IO
Input/Output
Interface
Additional Sections:
»QSE-IO Input/Output Interface Programming
CCI1
CCI2
CCI3
CCI4
COM
CCI5
V
0-24V 1A
0-24V ½A
R
O
N
CCO1NC
CCO1NO
CCO2NC
CCO2NO
1-2COM
CCO3NC
CCO4NO
CCO3NO
CCO4NC
3-4COM
CCO5NC
5COM
CCO5NO
V
R
MUX
COM
V+
MUX
500-13491Rev.B
CCO1
CCO2
CCO3
CCO4
CCO5
STAT
QS
800.523.9466
+1.610.282.3800
www.lutron.com/qs
QSE-IO
24V 100 mA
®
243CIND. CONT. EQ.
02755761323 1
87 6 5 4 3 2 1
4 3 2 1
GRAFIK Eye®QS
Control Unit or
QS Timeclock
Additional Sections:
»GRAFIK Eye®QS Control Unit or QS Timeclock Programming
LUTRON
Zones
Inputs