M-2060 Series
© 2015 Magnaflux
Page 3 Magnaflux-SRVC-IG011
Issued: Apr 2015
Rev. 2
Duty Cycle:
At full output: 30 seconds “ON” – 6 minutes “OFF”
At 1000 amps: 30 seconds “ON” – 3 minutes “OFF”
The equipment can be fused based on less than the maximum amperage draw due to the duty
cycle. Refer to NEC Code Section 630.31 Ampacity of Supply Conductors and Table 630.31
(A) (2) Duty Cycle Multiplication Factors for Resistance Welders (NPFA National Electric Code
2011). Some areas refer to 2 phase instead of 1 phase. The incoming power goes directly to
an isolation transformer so the unit will operate identically on 1 or 2 phase power.
Electrical Input:
Input Volts AC Phase
Full Load
(Amps)
Recommended
Line Fuse (Amps)
Recommended
Wire Size (AWG)
208 N/A N/A N/A N/A
230 N/A N/A N/A N/A
380 1300 250 #0
415 1275 225 #0
460 1250 200 #1
575 1200 150 #2
Note: To obtain full rated output the following conditions must be met:
1. Two sets of thirty (30’) feet long 4/0 cables (connected in parallel) attached to the Output
Lugs on the front of the unit.
2. A power source of the proper voltage, frequency and phase (as designated on the Mag-
naflux Data Plate) capable of providing current per the nameplate for the power pack. It is
highly recommended that an electrical fused disconnect be installed either on the wall be-
hind the unit or on a pedestal near the unit.