8. Station valve solenoid. Connect wire (wire number 21,22,23,24,25 in drawing)
from the output terminal on the PLC (Q1, Q2, Q3, Q4, Q5) to the respective
station valve solenoid. Connect the station valve solenoid to (wire number 2 in
drawing) to terminal number 2 on the terminal block.
9. Units have a molded 7 foot power cable with plug. Install in a dedicated
receptacle.
5.2 Wiring for MCS-405A –24 Volt DC
Dangerous Voltage! Do not put your finger or any object in the program
module/card slot. If the power supply is not connected properly, the plug for the
module/card may carry voltage. The module/card or cover must be in place at all
times. NOTE: the module/card accessory is optional and is not needed for
normal operation.
Keep low voltage wiring separated from higher voltage wires.
1. Mount the MCS-405A control box with power supply box in a secure location.
2. Refer to drawings MCS-405AD1-5.
3. Loosen clamp screws allowing the door to be opened.
4. Open the hinged door.
Note: Wire number 2 is the negative wire.
5. Motor Starter. Connect wire (wire number 27 in drawing) from the normally
closed contact of overload for the vacuum power unit to the output terminal
Q7 on the PLC (Typical Novatec motor starters are shown on drawing SK-
836A). Connect the motor starter coil to terminal number 2 on the terminal
block (wire number 2 in drawing).
6. VBV (vacuum breaker valve). Connect wire (wire number 26 in drawing) from
the VBV solenoid to the output terminal Q6 on the PLC. Connect the VBV
solenoid to terminal number 2 on the terminal block (wire number 2 in
drawing).
7. Level switch. Connect wire (wire number 11,12,13,14,15 in drawing) from the
on/off switch to the level switch (green screw of twist-lock plug) on the
respective station. Connect the level switch (copper screw of twist-lock plug)
to terminal number 3 on the terminal block (wire number 3 in drawing). If
using photoelectric switch, connect wire (wire number 2 in drawing) from
terminal 2 on the terminal block to silver screw on twist-lock plug.
Note: If using a capacitance type proximity switch, install resistor kit part
number 10467, as shown on drawing.
8. Station valve solenoid. Connect wire (wire number 21,22,23,24,25 in drawing)
from the output terminal on the PLC (Q1, Q2, Q3, Q4, Q5) to the respective
station valve solenoid. Connect the station valve solenoid to (wire number 2
in drawing) to terminal number 2 on the terminal block.
9. Connect supply voltage (240vac models only) to wires at the bottom of the
power supply box. (Refer to drawing MCS-405AD4). Voltage (or Hot) to the
red wire, Neutral (or Common) to the white wire, and ground to the green
wire. 120VAC powered units have a molded 7 foot power cable with plug
attached. Install in a dedicated receptacle.