Mannesmann HYQUIP VT-SWKA-1 Training manual

Company Registered in England No: 4167649 VAT Registration No: 732 5692 25 BS EN ISO 9001:2008 No: LRQ 0964389
+44 (0)1204 699959
Hyquip Limited New Brunswick Street Horwich Bolton Lancashire BL6 7JB UK
www.hyquip.co.uk/web/index
Analog Command Value Card VT-SWKA-1
Product Description and Commissioning Instructions
RE 30 255-B/05.00

Company Registered in England No: 4167649 VAT Registration No: 732 5692 25 BS EN ISO 9001:2008 No: LRQ 0964389
+44 (0)1204 699959
Hyquip Limited New Brunswick Street Horwich Bolton Lancashire BL6 7JB UK
www.hyquip.co.uk/web/index
3
RE 30 255-B/05.00
Product description and commissioning instructions VT-SWKA-1
Table of contents
Table of contents
1. General
1.1 Features 4
1.2 Technical data 5
2. Block circuit diagram 6
3. Functional description / commissioning notes
3.1 General 7
3.2 Command value preselection 7
3.3 Current input 7
3.4 Command value call-ups 7
3.5 External command value potentiometer 7
3.6 Command value inversion 7
3.7 Enable function 7
3.8 Ramp generator 8
3.9 External ramp time adjustment 8
3.10 Ramp status signal 8
3.11 Ramp time selection logic 9
3.12 Characteristic curve generator 9
3.13 Amplitude limiter 10
3.14 Fault recognition 10
3.15 Measuring points 10
4. Indicator / adjustment elements 11
5. Adjustment recommendation 12
6. Pin assignment 13
7. Engineering / maintenance notes / supplem. information 13

Company Registered in England No: 4167649 VAT Registration No: 732 5692 25 BS EN ISO 9001:2008 No: LRQ 0964389
+44 (0)1204 699959
Hyquip Limited New Brunswick Street Horwich Bolton Lancashire BL6 7JB UK
www.hyquip.co.uk/web/index
RE 30 255-B/05.00
4
1. General
1.1 Features – Analog command value card (without power part) for controlling valves with integral
electronics
→For controlling valves without integral electronics, a suitable additional amplifier
is required.
– Suitable for generating, combining and normalizing command value signals
– Configuration and parameterization of the command value card by means of
potentiometers
– Command value inputs:
• Differential input ±10 V
• 4 callable command value inputs ±10 V
• Current input 4 to 20 mA (standard 0 to 100 %; can be changed over ±100 %)
– Control variable output:
• Voltage ±10 V
• Current 4 to 20 mA (standard 0 to 100 %; can be changed over ±100 %)
– Inversion of internal command value signal using 24V input or jumper
– Ramp time selection by quadrant recognition (24V input) or
ramp time call-ups (24V inputs)
– Ramp time range can be changed over by means of jumpers
– Characteristic curve correction by means of separately adjustable step-change heights
and maximum values
– Enable input
– Output signal “ramp ready“ as auxiliary process variable
– Output signal “ready for operation“
– Switchable measuring socket
– Reverse voltage protection for voltage supply
Suitable card holders:
– 19“ rack types VT 19101, VT 19102, VT 19103 and VT 19110 (see RE 29 768)
– Closed card holder VT 12302 (see RE 30 103) with blind plate insert 4TE/3HE
(material no. 00021004)
– Open card holder VT 3002-2X/48 (see RE 29 928)
For control cabinet installation only!
Power supply units:
– Type VT-NE30-1X, see RE 29 929
Compact power supply unit 115/230 VAC →24 VDC, 70 VA
– Type VT-NE31-1X, see RE 29 929
Compact power supply unit 115/230 VAC →24 VDC, 7 VA
– Type VT-NE32-1X, see RE 29 929
Compact power supply unit 115/230 VAC →24 VDC, 60 VA (smoothed) and
24 VDC, 25 VA (regulated)
Product description and commissioning instructions VT-SWKA-1
1. General

Company Registered in England No: 4167649 VAT Registration No: 732 5692 25 BS EN ISO 9001:2008 No: LRQ 0964389
+44 (0)1204 699959
Hyquip Limited New Brunswick Street Horwich Bolton Lancashire BL6 7JB UK
www.hyquip.co.uk/web/index
5
RE 30 255-B/05.00
1.2 Technical data
For applications outside these parameters, please consult us!
Product description and commissioning instructions VT-SWKA-1
1. General
Operating voltage UB24 VDC + 40 % – 20 %
Operating range: – Upper limit value UB(t)max 35 V
– Lower limit value UB(t)min 18 V
Power requirement PS< 7 VA
Current consumption I< 0.3 A
Fuse Thermal overload protection; auto-activating when triggered
Inputs:
– Analog
• command values 1 to 4 (potentiometer inputs) Ue0 to ±10 V; Re= 100 kΩ(reference is M0)
• command value 5 (differential input) Ue0 to ±10 V; Re> 50 kΩ
• command value 6 (current input) Ie4 to 20 mA; load RB= 100 Ω(zero point can be changed over)
• ramp time external Ue0 to +10 V; Re= 10 kΩ
(internally raised to +15 V; reference is M0)
– Digital
• command value call-ups U8.5 V to UB→call-up activated
U0 to 6.5 V →no call-up
• ramp call-ups U8.5 V to UB→call-up activated
U0 to 6.5 V →no call-up
• quadrant recognition U8.5 V to UB→ON
U0 to 6.5 V →OFF
• command value inversion U8.5 V to UB→ON
U0 to 6.5 V →OFF
• enable U8.5 V to UB→ON
U0 to 6.5 V →OFF
Adjustment ranges:
– Zero point adjustment (potentiometer “Zw“) ±30 %
– Command values (potentiometers “w1“ to “w4“) 0 to 110 %
– Ramp times (potentiometers “t1“ to “t5“) 20 ms to 5 s (can be changed over using J3)
– Step-change height (potentiometers “S+“ and “S–“)
0 % to 50 % (step-change height reached at ca. 2 % command value injection)
– Amplitude attenuator (potentiometers “G+“ and “G–“) 0 % to 110 % (valid when step-change height is set to 0 %)
Outputs:
– Analog signals
•
control variable
voltage U±10 V ±2 %; Imax = 2 mA
current I
4 mA to 20 mA ±2 %; R
B
max
= 500 Ω(zero point can be changed over)
• measuring signal U±10 V ±2 %; Imax = 2 mA
– Digital signals
• ramp ready U> 16 V; 50 mA →ready
U< 1 V; Ri= 10 kΩ→ramp active
• ready for operation U> 16 V; 50 mA (in the event of a fault: U< 1 V; Ri= 10 kΩ)
– Regulated voltages U±10 V ±2 %; 25 mA
– Measuring sockets
•
measur. signal “v“ (dep. on position of measur. point selector switch)
U±10 V ±2 %; Imax = 2 mA
Type of connection 48-pin blade connector, DIN 41 612, form F
Card dimensions Euro-card 100 x 160 mm, DIN 41 494
Front panel dimensions: – Height 3 HE (128.4 mm)
– Width soldering side 1 TE (5.08 mm)
– Width component side 3 TE
Permissible operating temperature range
ϑ
0 to + 50 °C
Storage temperature range
ϑ
– 25 °C to + 85 °C
Weight m0.15 kg
Note:
For details regarding environment simulation tests in the fields
of EMC (electromagnetic compatibility), climate and mechanical stress,
see RE 30 255-U (declaration on environmental compatibilty).

Company Registered in England No: 4167649 VAT Registration No: 732 5692 25 BS EN ISO 9001:2008 No: LRQ 0964389
+44 (0)1204 699959
Hyquip Limited New Brunswick Street Horwich Bolton Lancashire BL6 7JB UK
www.hyquip.co.uk/web/index
RE 30 255-B/05.00
6
uu
∑
b20
d10
d12
d14
d16
d24
d28
b14
b16
b22
b24
b8
b6
b4
b2
d2
d4
d6
d8
b10
d18
z30
z32
d26
d30
d32
d22
b32
b30
b26
b28
z20
+15 V
w3
4
L0
J5
5
Zw
– 1
UL
t1 t2
t3 t4
t
7
DC
DC
Gw+
S+ S–
+15 V
+7,5 V
M0
–5 V
–7,5 V
–15 V
v
J7
26
1
1
2
3
4
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
15
iu
3
3
w4
w2 2
w1 1
4
+
–
+
–
24 V
0 V
t1
A
t2
B
t3
C
t4
D
t5
E
0123456789A CBDEF
10
4Q
F
7
6J1
v
8
UL
∑
9
J2, J3
Gw–
12
13
J6
ui
UL
14
5
11
1
2
3
4
J4
0
+/–
max
ϑ+100 μF
Product description and commissioning instructions VT-SWKA-1
2. Block circuit diagram
2. Block circuit diagram
Operating
voltage
Inversion
Enable
Com. value 5:
0 to ±
10
V
Quadrant
operation
Contr. variable
0 to ±10 V
Measuring signal
M0
For explanations regarding the jump-
ers as well as the position and assign-
ment of indicator and adjustment
elements, see page 11
1Power supply unit
2Differential amplifier
3Current input
4
Command value selection logic
5Zero point adjustment
Ramp
call-ups
6Command value summation
7Command value inversion
8Enable function
9Ramp generator
10 Ramp time selection logic
11 Ramp status function
12 Characteristic curve generator
13 Amplitude limiter
14 Fault recognition
15 Measuring point changeover
Com. value
call-ups
Ramp time
external
Com. value 6:
4 to 20 mA
Com. value 4
Com. value 3
Com. value 2
Com. value 1
Ramp ready
Control variable
4 to 20 mA
“Ready for
operation“
+ 10 V/25 mA
– 10 V/25 mA
System ground
Measuring points
1)
UP/DOWN
1)
Measuring points 8 and 9
are not assigned.

Company Registered in England No: 4167649 VAT Registration No: 732 5692 25 BS EN ISO 9001:2008 No: LRQ 0964389
+44 (0)1204 699959
Hyquip Limited New Brunswick Street Horwich Bolton Lancashire BL6 7JB UK
www.hyquip.co.uk/web/index
7
RE 30 255-B/05.00
R
5 kΩ< R < 20 kΩ
Product description and commissioning instructions VT-SWKA-1
3. Functional description / commissioning notes
3. Functional description /
commissioning notes
[ ] = Reference to the block circuit diagram
3.1 General
The command value card is designed as printed circuit board in Euro-format 100 x 160 mm
and is suitable for installation in a rack. A power supply unit [1] provides the internally
required positive and negative supply voltages. As soon as the power supply unit is in opera-
tion and no error is present, the green LED on the front panel lights up and the “ready for
operation” signal is set.
3.2 Command value preselection
The internal command value signal is generated from the sum (command value summation
[6]) of the external command value signal applied to differential input [2] and to current
input [3], called-up signal [4] and zero point offset [5] (zero point potentiometer "Zw”).
3.3 Current input [3]
There is no changeover between current and voltage input. Both inputs are permanently
available (see terminal allocation). The input signals are internally normalized and added.
The zero point and the range of values of the current input can be changed over by means of
jumper J5.
3.4 Command value call-ups [4]
Four command value signals, “w1“ to “w4“, can be called up. External command value
voltages (command values 1 to 4) are preselected either directly via the regulated voltage
inputs + 10 V and – 10 V or via external potentiometers. If the command value inputs are
connected directly to the regulated voltages, the command values are adjusted by means of
potentiometers “w1“ to “w4“. If external potentiometers are used, the internal potentiom-
eters act as attenuators or limiters.
Only one call-up is possible at a time. If several call-ups are selected simultaneously, call-up
“1” has lowest priority, call-up “4” highest priority.
A yellow LED on the front panel indicates, which call-up is active.
3.5 External command value potentiometer
3.6 Command value inversion [7]
The command value that is generated internally from input signals, command value call-ups
and zero point offset signals can be inverted by means of an external signal or jumper J1.An
LED (“– 1“) on the front panel signals whether an external inversion signal is applied.
3.7 Enable function [8]
The enable function cuts the enable signal of the ramp generator in or out.When the enable
is cut in or out, the control variable changes at any command value according to the set ramp
time. This prevents a controlled valve from opening or closing suddenly. If an error signal is
present, the input signal of the ramp generator is also set to 0 %.An LED on the front panel
signals that an enable signal is applied.
b2, b4, b6 or b8
b32 b30 b32
(+10V) (–10V) (+10V)
b28 b28 b30
(0V) (0V) (–10V)
Range of command values
0 to 0 to –100% to
+100% –100% +100%

Company Registered in England No: 4167649 VAT Registration No: 732 5692 25 BS EN ISO 9001:2008 No: LRQ 0964389
+44 (0)1204 699959
Hyquip Limited New Brunswick Street Horwich Bolton Lancashire BL6 7JB UK
www.hyquip.co.uk/web/index
RE 30 255-B/05.00
8
d24
d28
+ 15 V
10 k
R
Utest socket "v" (in V) 53210.50.30.20.10.05 0.03 0.02
J3 →connection 2-3 1) t(in ms; ±20 %) 20 33 50 100 200 333 500 1000 2000 3333 5000
J3 →connection 1-2 t(in s; ±20 %) 0.2 0.33 0,50 1 2 3.33 5 10 20 33 50
1) factory setting
3.9 External ramp time adjustment
The internally set ramp time can be extended by means of an external potentiometer. The
setting can be verified with the help of the measuring socket. In the case of a cable break,
the internal presetting will be validated automatically.
The adjustment range depends on "R".
2) The minimum ramp time can only be achieved, if the internally set ramp time is less, i.e.
the relevant potentiometer is turned to the left-hand stop.
3.10 Ramp status signal [11]
The status signal“ramp ready“ indicates that the control variable has reached the requested
final value. This signal (24V output) facilitates the synchronization of higher-level sequence
controls with the valve function or the controlled hydraulic function.
3.8 Ramp generator [9]
The ramp generator limits the increase of the control variable. Downstream step-functions
and amplitude attenuators do not shorten or extend the ramp time.
Jumper J2 can be used to set the ramp time to minimum (< 2 ms) (ramp off).
The minimum/maximum ramp time can be changed between 20 ms/5 s or 0.2 s/50 s by
means of jumper J3.
5 different ramp times can be set and activated. The ramp times can be pre-set or verified
with the help of test socket “v”.
The following is valid (with factory setting of jumper J3 →connection 2-3):
t= (in ms)
100
U
test socket "v"
(in V)
The following is valid (with factory setting of jumper J3 →connection 2-3):
Adjustment range 2)
RMinimum ramp time Maximum ramp time
Potentiometer to left-hand stop Potentiometer angle of rotation = 95 %
1 kΩ80 ms 1 s
0,5 kΩ150 ms 2 s
0,1 kΩ800 ms 10 s
r
l
Product description and commissioning instructions VT-SWKA-1
3. Functional description / commissioning notes

Company Registered in England No: 4167649 VAT Registration No: 732 5692 25 BS EN ISO 9001:2008 No: LRQ 0964389
+44 (0)1204 699959
Hyquip Limited New Brunswick Street Horwich Bolton Lancashire BL6 7JB UK
www.hyquip.co.uk/web/index
9
RE 30 255-B/05.00
+
2
%+
100
%
–
100
%
S–
G–
S+
G+
–
2
%
Product description and commissioning instructions VT-SWKA-1
3. Functional description / commissioning notes
3.11 Ramp time selection logic [10]
a) Operating mode "4-quadrant operation"
When 4-quadrant operation is activated (24V signal “4Q”), the electronics automatically
recognizes the command value polarity and the direction of change of the command value
and assigns a ramp time to the current signal status. Depending on these signal states, one
of the 4 ramp times is selected.
Ramp up, positive →Ramp potentiometer “t1”
Ramp down, positive →Ramp potentiometer “t2”
Ramp up, negative →Ramp potentiometer “t3”
Ramp down, negative →Ramp potentiometer “t4”
4-quadrant operation has a higher priority than all ramp time call-ups. As long as a signal
changes, the LED (on the front panel, directly next to the associated potentiometer) assigned
to the current ramp time lights up.
Note: In the case of very short ramp times, the LEDs' lighting up can no longer be noticed.
LED “4Q” on the front panel is on when quadrant recognition is active.
b) Ramp time call-ups
When operating mode "4-quadrant operation" is deactivated,4 ramp times can be called up
using an optional call-up signal (24V input). Only 1 call-up is possible at a time. If several
call-ups are activated at the same time, call-up “1” has the lowest priority and call-up “4”
has highest priority. Each called-up ramp time is signaled by a yellow LED (on the front panel,
directly next to the associated potentiometer).
c) 5th ramp time
If neither quadrant recognition nor a call-up is activated, ramp time "t5"
is always valid.
3.12 Characteristic curve generator [12]
The adjustable characteristic curve generator can be used to adjust step-change heights and
maximum values separately for positive and negative signals according to the hydraulic re-
quirements. The actual characteristic curve shape through the zero point is not step-like, but
linear.
The step-change height can be adjusted by means of potentiometers "S+" and "S–".
Jumper J4 can be used to activate the step function. For this, the connection 2-3 of jumper J4
must be plugged (factory setting: connection 1-2 →step function OFF). To prevent a re-
sidual step-change (< 1 %) when the step function is deactivated, the potentiometers “S+”
and S–“ must be turned to the left-hand stop and the connection 1-2 of jumper J4 must be
plugged.
The maximum command value can be adjusted by means of potentiometers “Gw+” and
“Gw–”. The adjustment range is between 0 % and 110 %.
3.13 Amplitude limiter [13]
The control variables (current output and voltage output) are limited to approx. ±110 % of
the nominal range.
← Internal command value →
←Command value preselection →

Company Registered in England No: 4167649 VAT Registration No: 732 5692 25 BS EN ISO 9001:2008 No: LRQ 0964389
+44 (0)1204 699959
Hyquip Limited New Brunswick Street Horwich Bolton Lancashire BL6 7JB UK
www.hyquip.co.uk/web/index
RE 30 255-B/05.00
10
3.14 Fault recognition [14]
This features monitors internal operating voltages, voltage outputs and, if jumper J7 (1-2) is
plugged, the current output for cable break. When no fault is present, the green “ready for
operation” LED lights up and the output “ready for operation” is set to 24 V (operating
voltage).
3.15 Measuring points [15]
A measuring socket is provided on the front panel to allow the verification of the settings of
command value call-ups, ramp times and further, internal signals. The measuring points can
be selected using the measuring point selector switch that is also provided on the front
panel. The signal of the measuring socket is also connected to the blade connector (b26).
Switch position Signal
Measuring signal at "v"
0Internal command value ±10 V Ⳏ100 %
1Command value call-up 1 ±10 V Ⳏ100 %
2Command value call-up 2 ±10 V Ⳏ100 %
3Command value call-up 3 ±10 V Ⳏ100 %
4Command value call-up 4 ±10 V Ⳏ100 %
5Zero point offset “Zw” ±3 V Ⳏ±30 %
6
Summated signal of command values
±10 V Ⳏ100 %
7Ramp generator output ±10 V Ⳏ100 %
8free
9free
ARamp time “t1” 10 mV to 10 V
BRamp time “t2” 10 mV to 10 V
CRamp time “t3” 10 mV to 10 V
DRamp time “t4” 10 mV to 10 V
ERamp time “t5” 10 mV to 10 V
FCurrent ramp time “t” 10 mV to 10 V
Product description and commissioning instructions VT-SWKA-1
3. Functional description / commissioning notes

Company Registered in England No: 4167649 VAT Registration No: 732 5692 25 BS EN ISO 9001:2008 No: LRQ 0964389
+44 (0)1204 699959
Hyquip Limited New Brunswick Street Horwich Bolton Lancashire BL6 7JB UK
www.hyquip.co.uk/web/index
11
RE 30 255-B/05.00
Product description and commissioning instructions VT-SWKA-1
4. Indicator / adjustment elements
4. Indicator / adjustment elements
If the sealed potentiometers are misadjusted, the warranty
will become void !
SWKA
-1
4Q
T
v
Zw
w1
w2
w3
w4
t1
t2
t3
t
4
t5
G–
J5
J1
J3 J2
S–
G+
S+
v0
–
vF
4
12 1
J4
J8
J6 J7
1 1
4
12
1
1 1
1
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
• … Connection made
–… Connection broken
… Factory setting of jumpers
Do not change!
(Internal reference voltage)
Do not change!
(Ramp time symmetry)
Measuring point selector
switch
J6 →current output 1-2 2-3
0 % Ⳏ4 mA • –
0 % Ⳏ12 mA – •
J7 →cable break
monitor 1-2 2-3
ON • –
OFF – •
J5
→current input
1-2 2-3
0 % Ⳏ4 mA • –
0 % Ⳏ12 mA – •
No function!
(Reserve)
J4
→step function
1-2 2-3
OFF • –
ON – •
J2 →ramp function 1-2 2-3
OFF • –
ON – •
J3 →ramp time 1-2 2-3
Ten-fold • –
Single – •
LED lamps:
Readiness for operation (green)
Enable (yellow)
–1 External inversion
4Q Quadrant recognition
TReserved
Potentiometers (some with LED lamp):
Zw Zero point adjustment
w1 Command value 1
w2 Command value 2
w3 Command value 3
w4 Command value 4
t1 Ramp time 1
t2 Ramp time 2
t3 Ramp time 3
t4 Ramp time 4
t5 Ramp time 5
Cannot be adjusted on the front panel:
G+ Amplitude attenuator for positive command values
G– Amplitude attenuator for negative command values
S+ Step-change height for positive direction
S– Step-change height for negative direction
Measuring sockets:
vMeasuring signal
⊥Measurement zero
J1
→inversion
1-2 2-3
inverting • –
not inverting – •

Company Registered in England No: 4167649 VAT Registration No: 732 5692 25 BS EN ISO 9001:2008 No: LRQ 0964389
+44 (0)1204 699959
Hyquip Limited New Brunswick Street Horwich Bolton Lancashire BL6 7JB UK
www.hyquip.co.uk/web/index
RE 30 255-B/05.00
12
Product description and commissioning instructions VT-SWKA-1
5. Adjustment recommendation
5. Adjustment recommendation The system-specific circuit must be provided.
Signal Adjustment
Command value call-up – Select the potentiometer to be adjusted using the
measuring point selector switch
–
Adjust the command value call-up and check it on measuring
socket
"
v
"
Command value zero point
– Do not activate a command value call-up!
– Set external command value preselections to zero
– Turn measuring point selector switch to "6"
– Set the measured value to zero using zero point
potentiometer "Zw"
Ramp times – Select the potentiometer to be adjusted using the
measuring point selector switch
–
Adjust the ramp time according to the formula or table (see
"3.8 ramp generator") and check it on measuring socket "v"
External ramp
potentiometer – Do not activate a ramp time call-up!
– Turn ramp potentiometer "t5" to the left-hand stop
– Turn measuring point selector switch to "F"
–
Adjust the ramp time according to the formula or table (see
"3.8 ramp generator") and check it on measuring socket "v"
Step-change height – Apply enable signal
– Turn measuring point selector switch to "7"
– Adjust the measuring signal to + 0.3 V using zero point
potentiometer "Zw" 1)
– Turn measuring point selector switch to "0"
–
Set the required step-change height using potentiometer "S+"
– Turn measuring point selector switch to "7"
– Adjust the measuring signal to – 0.3 V using zero point
potentiometer "Zw" 1)
– Turn measuring point selector switch to "0"
–
Set the required step-change height using potentiometer "S
–"
– Adjust the zero point
1) In the case of external command value preselection, this
must result in at least + 0.3 V / – 0.3 V at measuring
socket "v" (turn measuring point selector switch to "7").
Maximum values Note: Before the maximum values are matched, the zero
point and step-change heights must be correctly set.
– Adjust the step-change heights first; generate command
value ±100 % externally or by means of a command value
call-up
– Turn measuring point selector switch to "7"
– Check measuring signal 10 V ±0.2 V
– Adjust the required maximum control output using
potentiometers "G+"/"G–"

Company Registered in England No: 4167649 VAT Registration No: 732 5692 25 BS EN ISO 9001:2008 No: LRQ 0964389
+44 (0)1204 699959
Hyquip Limited New Brunswick Street Horwich Bolton Lancashire BL6 7JB UK
www.hyquip.co.uk/web/index
13
RE 30 255-B/05.00
7. Engineering / maintenance
notes / supplem. information
– The command value card may only be withdrawn or plugged in when disconnected
from the power supply!
– Never install cables near power cables!
–
The distance to antenna cables, radio equipment and radar systems must be at least 1 m!
– Use relays with gold-plated contacts for switching command values (small voltages,
small currents)!
– Only carry out measurements on the cards with instruments Ri> 100 kΩ!
– Use a screw driver with a blade width of 4 mm for adjusting potentiometers and
turning the measuring point selector switch.
– Always shield command value cables; connect shield to protective earth (PE) on the
card side!
–Caution: When using the differential input, both inputs must always be
switched on or off simultaneously!
If the sealed potentiometers are misadjusted, the warranty will become void !
Pin Row d Row b Row z
2Command call-up 1 Command value 1 Reserved
(24V input)
(Potentiometer connection ±10 V)
4Command call-up 2 Command value 2 Reserved
(24V input)
(Potentiometer connection ±10 V)
6Command call-up 3 Command value 3 Reserved
(24V input)
(Potentiometer connection ±10 V)
8Command call-up 4 Command value 4 Reserved
(24V input)
(Potentiometer connection ±10 V)
10 Ramp call-up 1 Command value inversion Reserved
(24V input) (24V input)
12 Ramp call-up 2 Reserved Reserved
(24V input)
14 Ramp call-up 3 Command value 5 + (+ 10V ) Reserved
(24V input)
16 Ramp call-up 4 Command value 5 – (– 10V ) Reserved
(24V input)
18 Enable Reserved Reserved
(24V input)
20 Reserved 4-quadrant operation System ground
(24V input)
22
Signal "ready for operation"
Command value 6 + Reserved
(24 V, H-active, 50 mA) (4 to 20 mA)
24 Ramp external Command value 6 – Reserved
(4 to 20 mA)
26 Ramp completed Measuring signal Reserved
28 Ramp external / reference Reference potential for Reserved
outputs (M0)
30 Control output ±10 V – 10 V / 25 mA Operating voltage
(24 V)
32 Control output 4 to 20 mA + 10 V / 25 mA L0 (0 V)
6. Pin assignment
Product description and commissioning instructions VT-SWKA-1
6. Pin assignment 7. Engineering / maintenance notes / supplem. information
Table of contents
Popular Computer Hardware manuals by other brands

Supero
Supero BPN-SAS3-827HQ Backplane user guide

Future Electronics
Future Electronics PSoC 3 quick start guide

Thermaltake
Thermaltake Pacific PR12-D5 Plus quick start guide

StarTech.com
StarTech.com MPEX1394B3 user manual

Cypress Semiconductor
Cypress Semiconductor CY7B991 Specification sheet

Renesas
Renesas R0E521134CFG00 user manual