INSTALLATION
EN / WHISPER 12/16 Ultra - Three phase for mobile applications / October 2008 / Copyright © 2008 Mastervolt 19
2.5.5 AC power system (230 / 400 Volt)
The electric power supplied by the generator
is of a high voltage and dangerous to people.
Before working (installation) on the system
read the sections on safety in the users
manual.
Realise hat people are not used to have
230/400Volt available on a vehicle. Put
warning signs on wall sockets and on junction
boxes. Instruct non-regular users of the
vehicle. Warn maintenance personal of
garages that do service on the vehicle.
Generators used on vehicles that are
operated in a hazardous environment have
often to fulfil special regulations and additional
measures have to be taken accordingly.
Be sure that all electrical installations (including all safety
systems) comply with all required regulations of the local
authorities. All electrical safety/shutdown and circuit
breaking systems have to be installed onboard as the
generating set itself cannot be equipped with such
equipment for every possible variation.
The vehicle’s power supply system should be suitable and
safe for the AC voltage which is applied and the power
that will be generated. Special attention has to be paid on
dividing the system in branches which are fused
individually.
It is absolutely essential that each and every circuit in the
on-board electrical system is properly installed by a
qualified electrician.
The AC wiring of the Whisper 12 Ultra – three phase and
the Whisper 16 Ultra – three phase can be arranged as
STAR configuration (230 / 400 V AC / 50 Hz) or a DELTA
configuration (230 V AC / 50 Hz)
When connected as a STAR configuration, 3x 400 Volt is
available between the phases. At the same time 230 Volt
is available between every phase and neutral. When
connected as a DELTA configuration 3x 230 Volt is
available between the phases. See chapter 4 for electrical
wiring diagrams.
When applying 3 phases the installation should be laid out
in such a way that there is a reasonable balance of load
between the three phases.
1 FUSES
Output fuses (between the generating set and the
electrical installation) should be installed to protect the
installed electrical system. The following maximum output
current applies for each separate phase:
Model Maximum output
current
Whisper 12 Ultra Three Phase 3 x 14 Amp
Whisper 16 Ultra Three Phase 3 x 17 Amp
The fuses must be of the slow reacting type. For electrical
motors connected to the system, a motor protection switch
must be installed
2 GROUNDING
The AC alternator windings are not grounded.
The housing of the alternator and all other metal parts are
grounded
To make a connection between “neutral” and “ground” is
necessary as part of a specific insulation failure protection
system.
It is possible that the electric installation in the vehicle
must be protected against insulation failures. Methods of
protection are subjected to rules that can be different
depending on the use of the vehicle and local standards.
In the standard marine manual is more information, but
this is according CE regulations for boats. Vehicles are
subject to different regulations depending on the
application of the vehicle. Experts in this field should be
consulted
3 CABLE
For the power cable we recommend the use of 3 wire
single phase or 5 wire tri-phase oil resistant cable with a
sufficient cross sectional area. One wire for earth is
included. For long cables it is recommended to apply
cables with a larger cross section (refer to ISO 13297
annex A)
4 TRANSFER SWITCH
A power source selector switch much be installed between
the generating set and the vehicle’s electrical supply
system. This switch must ensure that all AC consumers
can be switched off at once. This switch should also be
installed to keep the generating set and shore (grid) power
systems separate.
Transfer switches - to switch over from shore to vehicle or
from generating set to inverter - should be well designed to
switch over all wires including neutral (and not only phases
or line) and there should be provisions with the aid of
timers to prevent relays from clattering.
WARNING
In all situations the transfer switches between
shore, inverter and generator should switch all
connections, the phase lines (L1, L2, L3) as
wel as neutral (N).