MerCs Strider M6 User manual

02 4047 0777 www.mercs.com.au02 4047 0788
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
• Measures kWh Kvarh, KW, Kvar, KVA, P, F, PF, Hz, dmd, V, A, THD, etc.
• Bi-directional measurement IMP & EXP
• Two pulse outputs
• RS485 Modbus
• Din rail mounting 35mm
• 1/5A CT connection
• Better than Class 1 / B accuracy
• 2pcs 3p4w meters and 6pcs 1p2w
Features
MerCs Strider M6
User Manual
ME-PM-63OMCT-2C
A pulse output indicates real-time energy measurement. An RS485 output allows remote monitoring from another display or a computer.
The Unit can measure and display electronic information of
multi-channels:
The unit has password-protected set-up screens for:
Unit Characteristics
• L-N voltage and THD% (total harmonic distortion) of all phases
• Line Frequency
• Currents, Current demands and current THD% of all phases
• Power, maximum power demand and power factor
• Active energy imported and exported
• Reactive energy imported and exported
• Changing password
• Supply system selection 1phase2wire, 3phase 4wires
• CT Ratio (1 to9999 )
• PT ratio (1 to 9999)
• Demand Interval time
• Reset for demand measurements
• Pulse output duration
Introduction
SDM630MCT-2C measures and displays the characteristics of two three phase four wires circuits
or 6 single phase circuits, including voltage, frequency, current, power and active and reactive
energy, imported or exported. Energy is measured in terms of kWh, kVArh. Maximum demand
current can be measured over preset periods of up to 60minutes. In order to measure energy, the
unit requires voltage and current inputs in addition to the supply required to power the product.
The requisite current input(s) are obtained via current transformers (CT).
This meter can be congured to work with a wide range of CTs, giving the unit a wide range of
operation. Built-in interfaces provide pulse and RS485 Modbus RTU outputs. Conguration is
password protected.

02 4047 0777 www.mercs.com.au02 4047 0788
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
MerCs Strider M6 ME-PM-63OMCT-2C
Current Transformer Primary Current
Pulse output
RS485 Serial – Modbus RTU
The unit can be congured to operate with CT ratio between Pri-
mary Current and Secondary Current. The secondary CT has two
options: 1A / 5A
This provides 2 pulse outputs referring the energy consumption of two circuits. Both pulse outputs are congurable. The pulse width for active
energy can be set from the Set-up menu.
This uses an RS485 serial port with Modbus RTU protocol to pro-
vide a means of remotely monitoring and controlling the Unit.
Set-up screens are provided for setting up the RS485 port.
1 2 3
The rst screen lights all display
segments and can be used as a display
check
The second screen indicates the rmware
installed in the unit and its build number.
Next the unit performs a self-test and in-
dicates if the test passes.
Start-up Screens
After a short delay, the screen will display active energy measurements.
1 2 3 4
Selects the Voltage and Current
display screens
In Set-up Mode, this is the “Left”
or “Back” button.
Select the Frequency and Pow-
er factor display screens
In Set-up Mode, this is the “Up”
button
Select the Power display
screens
In Set-up Mode, this is the
“Down” button
Select the Energy display
screens
In Set-up mode, this is the “En-
ter” or “Right” button
Measurements
The SDM630MCT-2C measures all important electrical parameters, which is shown on the LCD display and approachable via RS485. On the front
panel there are four sensitive buttons and four LED indicators.
The buttons operate as follows:

02 4047 0777 www.mercs.com.au02 4047 0788
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
MerCs Strider M6 ME-PM-63OMCT-2C
There are four LED indicators on the front panel , namely C1, C2, Pulse1 and Pulse2.
The unit can measures and displays data of two three phase circuits: C1 circuit and C2 circuit. If C1 LED shows, that means the reading on the LCD
are for C1 circuit. While C2 is there, it means the measurements on the LCD are for C2 circuit.
The default display after the meter is power on, the LCD show “C1” circuit information. The way to shift “C1” circuit information to “C2” circuit in-
formation is by pressing the “Down” button. If the meter are showing “C2”, and the user want to shift it to be “C1” circuit, Then he shall keep
pressing the “UP” button.
(Circuit 1) (Circuit 2)
Voltage and Current
Each successive pressing of the button selects a new range:
1 Phase to neutral voltages
2Current on each phase
3Phase to neutral voltage THD%
4Current THD% for each phase

02 4047 0777 www.mercs.com.au02 4047 0788
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
MerCs Strider M6 ME-PM-63OMCT-2C
1 2 3 4
Frequency
Power factor (total) Power factor of each phase Max. Power demand Max. Current demand
Frequency and Power Factor and Demand
Each successive pressing of the button selects a new range:
Power
Each successive pressing of the button selects a new range:
1-1 nstantaneous active power (kW)
1-2 Instantaneous reactive power (kVAr)
1-3 Instantaneous Volt-amps (KVA)
2Total kW, kVAr, kVA

02 4047 0777 www.mercs.com.au02 4047 0788
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
MerCs Strider M6 ME-PM-63OMCT-2C
Energy Measurements
Each successive pressing of the button selects a new range:
1Total active energy in kWh
2-1 C1-L1 kwh
2-2 C1-L2 kwh
2-3 C1-L3 kwh
3-1 Imported active energy in kWh
3-2 Exported active energy in kWh

02 4047 0777 www.mercs.com.au02 4047 0788
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
MerCs Strider M6 ME-PM-63OMCT-2C
4Total reactive energy in kVAh
5-1 C1-L1 kVarh
5-2 C1-L2 kVarh
5-3 C1-L3 kVarh
6-1 Imported reactive energy in kVArh
6-2 Exported reactive energy in kVArh

02 4047 0777 www.mercs.com.au02 4047 0788
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
MerCs Strider M6 ME-PM-63OMCT-2C
Setting Up
To enter set-up mode, pressing the button for 3 seconds, until the password screen appears.
Setting up is password-protected so you must enter the correct password (default ‘1000’) before processing. If an incorrect password is entered, the
display will show: PASS Err
To exit setting-up mode, press repeatedly until the measurement screen is restored.
Set-up Menu Structure
Change password
CT Set the value of the CT ratio
nnnn
nnnn
4-digit number – default ‘1000’
4-digit number 0001~9999.

02 4047 0777 www.mercs.com.au02 4047 0788
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
MerCs Strider M6 ME-PM-63OMCT-2C
PT set the value of PT Ratio
DIT Demand Integration Time
This is the period in minutes over which the current and power readings are integrated for maximum demand measurement. Options are:
5 , 10, 15, 30 and 60minutes.
Nnnn 4-digit number 0001~9999
Some menu items, such as password and CT, require a four-digit number entry while others, such as supply system, require selection from a number
of menu options.
Set-up Entry Methods
1. Use the and buttons to select the required item from the menu shown in section 4.1. selection does not roll over between bottom
and top of list
2. Press to conrm your selection
3. If an item ashes, then it can be adjusted by the and buttons. If not, there maybe a further layer.
4. Having selected an option from the current layer, press to conrm your selection. The SET indicator will appear.
5. Having completed a parameter setting, press to return to a higher menu level. The SET indicator will be removed and you will be able
to use the and buttons for further menu selection.
6. On completion of all setting-up, press repeatedly until the measurement screen is restored.
Menu Option Selection
When Setting up the unit, some screens require the entering of a number. In particular, on entry to the setting up section, a password must be
entered. Digits are set individually, from left to right. The procedure is as follows:
Number Entry Procedure

02 4047 0777 www.mercs.com.au02 4047 0788
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
MerCs Strider M6 ME-PM-63OMCT-2C
1. The current digit to be set ashes and is set using the and buttons
2. Press to conrm each digit setting. The SET indicator appears after the last digit has been set.
3. After setting the last digit, press to exit the number setting routine. The SET indicator will be removed.
Change Password
1Use the and to choose the change
password option
2-1
Press the to enter the change password routine.
The new password screen will appear with the rst
digit ashing.
2-2
Use and to set the rst digit and
press to conrm your selection. The next
digit will ash.
2-3 Repeat the procedure for the remaining three digits.
3After setting the last digit, SET will show.
Press to exit the number setting routine and return to the Set-up menu. SET will be removed

02 4047 0777 www.mercs.com.au02 4047 0788
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
MerCs Strider M6 ME-PM-63OMCT-2C
DIT Demand Integration Time
1
From the set-up menu, use and buttons
to select the dIT option. The screen will show the cur-
rently selected integration time.
2-1 Press to enter the selection routine. The current
time interval will ash
2-2 Use and buttons to select the time
required.
3Press to conrm the selection. SET indicator
will appear.
This sets the period in minutes over which the current and power readings are integrated for maximum demand measurement. The options are: 5,
10,15 30,60 minutes
Press to exit the dIT selection routine and return to the menu.
DIT Demand Integration Time

02 4047 0777 www.mercs.com.au02 4047 0788
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
MerCs Strider M6 ME-PM-63OMCT-2C
DIT Demand Integration Time
DIT Demand Integration Time
1
From the Set-up menu, use and buttons to
select the CT option. The screen will show the current
CT primary current value.
C1.CT2 →Circuit 1 C2.CT2→Circuit 2
2
Secondary CT setting
Press to enter the CT secondary current selec-
tion routine. 5A/1A
3
Set CT Ratio Value
Press to enter the CT Ratio
The range is from 0001~9999.
1
From the Set-up menu, use and buttons
to select the PT option. The screen will show the volt-
age PT secondary voltage value.
2
Secondary PT setting
The setting method is same as Primary voltage set-
ting PT1
Max PT2 value is 500V
The CT option sets the current ratio (1~9999) and secondary current (CT2 1A/5A) of the current transformer (CT) that wires to the meter.
The PT option sets the secondary voltage (PT2 100~500V) of the Voltage transformer (PT) that wires to the meter and the PT ratio between PT1 to
PT2. The default value is 400V for Secondary PT (L-L), and the ratio between PT1 and PT2 is 1.
Example: if set the ratio to be 100, that means the primary current is secondary current x100.
CT
PT

02 4047 0777 www.mercs.com.au02 4047 0788
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
MerCs Strider M6 ME-PM-63OMCT-2C
3
Set PT Ratio Value
Press to enter the PT Ratio
The range is from 0001~9999.
Press to exit the system selection routine and return to the menu. SET will disappear and you will be returned to the main Set-up Menu
On completion of entry procedure, press to conrm the setting and press to return to the main set up menu.
1From the Set-up menu, use and buttons
to select the Pulse output option.
2Press to enter the selection routine. The unit
symbol will ash.
3Use and buttons to choose kWh or
kVArh.
This option allows you to congure the pulse output. The output can be set to provide 2 pulses, Pulse 1 is lock to C1, and Pulse 2 is lock to C2. The
setting will be eective for both pulse outputs.
Use this section to set up the pulse output (Units: kWh, kVarh)
Pulse output

02 4047 0777 www.mercs.com.au02 4047 0788
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
MerCs Strider M6 ME-PM-63OMCT-2C
On completion of entry procedure, press to conrm the setting and press to return to the main set up menu.
DIT Demand Integration Time
DIT Demand Integration Time
1From the Set-up menu, use and buttons
to select the Pulse Rate option.
2
Press to enter the selection routine. The current
setting will ash
Use and buttons to choose pulse rate.
Use this to set the energy represented by each pulse. Rate can be set to 1 pulse per
0.01/0.1/1/10/100/1000kWh/KVArh.
The energy monitored can be active or reactive and the pulse width can be selected as 200, 100 or 60ms.
(It shows 1 impulse = 10kWh/kVArh)
(It shows pulse width of 200ms)
Pulse rate
Pulse Duration

02 4047 0777 www.mercs.com.au02 4047 0788
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
MerCs Strider M6 ME-PM-63OMCT-2C
On completion of the entry procedure, press to conrm the setting and press to return to the main set up menu.
1From the Set-up menu, use and buttons
to select the Pulse width option.
2-1 Press to enter the selection routine. The current
setting will ash.
2-2 200/100/60ms
Use and buttons to choose pulse width.
DIT Demand Integration Time
DIT Demand Integration Time
There is a RS485 port can be used for communication using Modbus RTU protocol. For Modbus RTU, parameters are selected from Front panel.
Communication
RS485 Address
(The range is from 001 to 247)
1From the Set-up menu, use and buttons
to select the Address ID

02 4047 0777 www.mercs.com.au02 4047 0788
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
MerCs Strider M6 ME-PM-63OMCT-2C
On completion of the entry procedure, press button to conrm the setting and press button to return the main set-up menu.
2-1 Press button to enter the selection routine.The
current setting will be ashing.
2-2 Use and buttons to choose Modbus
Address(001 to 247)
Baud Rate
On completion of the entry procedure, press to conrm the setting and press to return to the main set up menu.
1From the Set-up menu, use and buttons
to select the Baud Rate option.
2-1 Press to enter the selection routine. The current
setting will ash.
2-2 Use and buttons to choose Baud rate
2.4k. 4.8k, 9.6k, 19.2k, 38.4k

02 4047 0777 www.mercs.com.au02 4047 0788
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
MerCs Strider M6 ME-PM-63OMCT-2C
Parity
Stop bits
On completion of the entry procedure, press to conrm the setting and press to return to the main set up menu.
1
From the Set-up menu, use and buttons
to select the Parity option.
2-1 Press to enter the selection routine. The current
setting will ash.
2-2
Use and buttons to choose Parity
(EVEN / ODD / NONE)
Default is NONE
1From the Set-up menu, use and buttons
to select the Stop Bit option.
2-1 Press to enter the selection routine. The current
setting will ash.

02 4047 0777 www.mercs.com.au02 4047 0788
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
MerCs Strider M6 ME-PM-63OMCT-2C
On completion of the entry procedure, press to conrm the setting and press to return to the main set up menu.
The meter provides a function to reset the maximum demand value of current and power.
2-2
Use and buttons to choose Parity
(EVEN / ODD / NONE)
Default is NONE
CLR
1From the Set-up menu, use and buttons
to select the reset option.
2-1 Press to enter the selection routine. The dIt will
ash.
Press to conrm the setting and press to return to the main set up menu.
Specications
Voltage and Current Power factor and Frequency and
Max. Demand
• Phase to neutral voltages 100 to 289V a.c.
• Voltages between phases 173 to 500V a.c.
• Percentage total voltage harmonic distortion (THD%) for each
phase to N
• Percentage voltage THD% between phases
• Current on each phase – 1 to 9999A range, set by external
current transformer(s) (CTs)
• Current THD% for each phase
• Frequency in Hz
• Instantaneous power:
• Power 0 to 3600 MW
• Reactive Power 0 to 3600 MVAr
• Volt-amps 0 to 3600 MVA
• Maximum demanded power since last Demand reset Power
factor
• Maximum neutral demand current, since the last Demand re-
set

02 4047 0777 www.mercs.com.au02 4047 0788
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
MerCs Strider M6 ME-PM-63OMCT-2C
Energy Measurements
• Imported active energy 0 to 9999999.9 kWh
• Exported active energy 0 to 9999999.9 kWh
• Imported reactive energy 0 to 9999999.9 kVArh
• Exported reactive energy 0 to 9999999.9 kVArh
• Total active energy 0 to 9999999.9 kWh
• Total reactive energy 0 to 9999999.9 kVArh
Measured Inputs
Voltage inputs through 4-way xed connector with 2·5mm2 stranded wire capacity. Line frequency measured from L1 voltage or L3 voltage.
Three current inputs (six physical terminals) with 2·5mm2 stranded wire capacity for connection of external CTs. Nominal rated input current 5A
or 1A a.c. Rms.
Accuracy
• Voltage 0·5% of range maximum
• Current 0·5% of nominal
• Frequency 0·2% of mid-frequency
• Power factor 1% of unity (0.01)
• Active power (W) ±1% of range maximum
• Reactive power (VAr) ±1% of range maximum
• Apparent power (VA) ±1% of range maximum
• Active energy (Wh) Class 1 IEC 62053-21
• Reactive energy (VARh) ±1% of range maximum
• Total harmonic distortion 1% up to 31st harmonic
Power Supply
Two-way xed connector with 2·5mm2 stranded wire capacity.
The meter is powered from Phase L1. The user must make sure the meter Phase 1 has power on.
Interfaces for External Monitoring
Three interfaces are provided:
• an RS485 communication channel that can be programmed for Modbus RTU protocol
• an output indicating real-time measured energy.(congurable)
• an pulse output 3200imp/kWh (not congurable)
The Modbus conguration (Baud rate etc.) and the pulse output assignments (kW/kVArh, import/export etc.) are congured through the Set-up
screens.
Pulse Output
The pulse output can be set to generate pulses to represent kWh or kVArh.
Rate can be set to generate 1 pulse per:
0.01 = 10 Wh/VArh
0.1 = 100 Wh/VArh
1 = 1 kWh/kVArh
10 = 10 kWh/kVArh
100 = 100 kWh/kVArh
1000 = 1000 kWh/kVArh
Pulse width 200/100/60 ms.

02 4047 0777 www.mercs.com.au02 4047 0788
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
MerCs Strider M6 ME-PM-63OMCT-2C
RS485 Output for Modbus RTU
For Modbus RTU, the following RS485 communication parameters can be congured from the Set-up menu:
Baud rate 2400, 4800, 9600, 19200, 38400
Parity none/odd/even
Stop bits 1 or 2
RS485 network address nnn – 3-digit number, 00 1 to 247
Modbus™ Word order Hi/Lo byte order is set automatically to normal or reverse. It cannot be congured from the set-up menu.
Reference Conditions of Inuence Quantities
Environment
Inuence Quantities are variables that aect measurement errors to a minor degree. Accuracy is veried under nominal value (within the specied
tolerance) of these conditions.
• Ambient temperature 23°C ±1°C
• Input waveform 50 or 60Hz ±2%
• Input waveform Sinusoidal (distortion factor < 0·005)
• Magnetic eld of external origin Terrestrial ux
• Operating temperature -25°C to +55°C*
• Storage temperature -40°C to +70°C*
• Relative humidity 0 to 90%, non-condensing
• Altitude Up to 3000m
• Warm up time 1 minute
• Vibration 10Hz to 50Hz, IEC 60068-2-6, 2g
• Shock 30g in 3 planes
Dimensions

02 4047 0777 www.mercs.com.au02 4047 0788
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
MerCs Strider M6 ME-PM-63OMCT-2C
Wiring diagram
2 circuits 3p4w 1 Circuit 3p4w+3 circuits 1p2w
6 circuits 1p2w