MerCs STRIDER M3 V2 User manual

1
02 4047 0777 www.mercs.com.au02 4047 0788
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
Two pulse output indicates real-time energy measurement. An RS485 output allows remote monitoring from another display or a computer.
The Unit can measure and display: The unit has password-protected set-up screens for:
Unit Characteristics
• Line voltage and THD% (total harmonic distortion) of all phases
• Line Frequency
• Currents, Current demands and current THD% of all phases
• Power, maximum power demand and power factor
• Active energy imported and exported
• Reactive energy imported and exported
• Changing password
• Supply system selection 1p2w, 3p3w,3p4w
• Demand Interval Time (DIT)
• Reset for demand measurements
• Pulse output duration
• Measures kWh Kvarh, KW, Kvar, KVA, P,
• F, PF, Hz, dmd, V, A, etc.
• Bi-directional measurement IMP & EXP
• Two pulse outputs
• RS485 Modbus
• Din rail mounting 35mm
• 100A direct connection
• Class: 0.5S accuracy
User Manual
Introduction
Features
The Strider M3 V2 (Part No.: ME-PM-M3) measures and displays the characteristics of single
phase two wires (1p2w), three phase three wires (3p3w,) and three phase four wires(3p4w)
supplies, including voltage, frequency, current, power ,active and reactive energy, imported
or exported. Energy is measured in terms of kWh, kVArh. Maximum demand current can be
measured over preset periods of up to 60 minutes. In order to measure energy, the unit requires
voltage and current inputs in addition to the supply required to power the product.
ME-PM-M3 supports max. 100A direct connection, saves the cost and avoid the trouble of
connecting external CTs, giving the unit a cost-eective and easy operation. Built-in interfaces
provides pulse and RS485 Modbus RTU outputs. Conguration is password protected.
STRIDER M3 V2
Multifunction Power Analyser With RS485 Port modbus RTU
and Pulse Outputs (ME-PM-M3-5) V1.0

02 4047 0777 www.mercs.com.au02 4047 0788 2
STRIDER M3 V2 ME-PM-M3: User Manual
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
1 2 3
The rst screen lights up all display seg-
ments and can be used as a display check.
The second screen indicates the rmware
installed in the unit and its build number.
The interface performs a self-test and in-
dicates the result if the test passes.
1 2 3 4
Selects the Voltage and Cur-
rent display screens in Set-
up Mode, this the “Left” or
“Back” button.
Select the frequency and
Power factor display screens.
In Set-up Mode, this is the
“Up” button
Select the Power display
screens.
In Set-up Mode, this is the
“Down” button.
Select the Energy display
screens.
In Set-up Mode, this is the
“Enter” or “Right” button.
Start-up Screens
Measurements
The buttons operate as follows:
After a short delay, the screen will display active energy measurements.
RS485 Serial–Modbus RTU Pulse output
This uses an improved RS485 serial port with Modbus RTU protocol
to provide a means of remotely monitoring and controlling the Unit.
Set-up screens are provided for setting up the RS485 port.
This provides two pulse outputs that clock up measured active and
reactive energy. The constant of pulse output 2 for active energy is
400imp/kWh (uncongurable), its width is xed at 100ms.
The default constant of congurable pulse output 1 is 400imp/
kWh, default pulse width is 100ms.The congurable pulse output 1
can be set from the set-up menu.

02 4047 0777 www.mercs.com.au02 4047 0788 3
STRIDER M3 V2 ME-PM-M3: User Manual
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
Voltage and Current
Each successive pressing of the button selects a new range:
1-1 Phase to neutral voltages (3p4w)
1-2 Phase to neutral voltages (3p3w)
2Current on each phase
3-1 Phase to neutral voltage THD% (3p4w)
3-2 Phase to neutral voltage THD% (3p3w)
4Current THD% for each phase

02 4047 0777 www.mercs.com.au02 4047 0788 4
STRIDER M3 V2 ME-PM-M3: User Manual
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
1-1 Imported active energy in kWh
1-2 Exported active energy in kWh
1 2 3 4
Frequency and Power Factor
(total) Power Factor of each phase Maximum Power Demand Maximum Current Demand
1 2 3 4
Instantaneous Active Power
in kW
Instantaneous Active Power
in kVAr
Instantaneous Volt-amps
in KVA Total kW, kVArh, kVA
Frequency and Power Factor and Demand
Power
Energy Measurements
Each successive pressing of the button selects a new range:
Each successive pressing of the button selects a new range:
Each successive pressing of the button selects a new range:

02 4047 0777 www.mercs.com.au02 4047 0788 5
STRIDER M3 V2 ME-PM-M3: User Manual
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
2-1 Imported reactive energy in kVArh
2-2 Exported reactive energy in kVArh
3-1 Total active energy in kWh
3-2 Total reactive energy in KVArh
Set Up Pass Word
To enter set-up mode, pressing the button for 3 seconds, until the password screen appears.
Setting up is a password-protected so you must enter the correct password (default ‘1000’) before processing. If an incorrect password is entered,
the display will show: Err

02 4047 0777 www.mercs.com.au02 4047 0788 6
STRIDER M3 V2 ME-PM-M3: User Manual
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
To exit setting-up mode, press repeatedly until the measurement screen is restored.
Some menu items, such as password, require a four-digit number entry while others, such as supply system, require selection from a number of
menu options.
When setting up the unit, some screen require the entering of a number. In particular, on entry to the setting up section, a password must be entered.
Digits are set individually, from left to right. The procedure is as follows:
1. Use the and buttons to select the required item from the menu. Selection does not roll over between bottom and top of list.
2. Press to conrm your selection.
3. If an item ashes, then it can be adjusted by the and buttons. If not, there maybe a further layer.
4. Having selected option from the current layer, press to conrm your selection. The SET indicator will appear.
5. Having completed a parameter setting, press to return to a higher menu level. The SET indicator will be removed and you will be able
to use the and buttons for further menu selection.
6. On completion of all set-up, press repeatedly until the measurement screen is restored.
1. The current digit to be set ashes and is set using the and buttons.
2. Press to conrm each digit setting. The SET indicator appears after the last digit has been set.
3. After setting the last digit, press to exit the number setting routine. The SET indicator will be removed.
Set-up Entry Methods
Menu Option Selection
Number Entry Procedure

02 4047 0777 www.mercs.com.au02 4047 0788 7
STRIDER M3 V2 ME-PM-M3: User Manual
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
Change Password
1Use the and to choose the change
password option
2-1
Press the to enter the change password routine.
The new password screen will appear with the rst
digit ashing.
2-2
Use and to set the rst digit and
press to conrm your selection. The next
digit will ash.
2-3 Repeat the procedure for the remaining three digits.
2-4 After setting the last digit, SET will show.
Press to exit the number setting routine and return to the Set-up menu. SET will be removed

02 4047 0777 www.mercs.com.au02 4047 0788 8
STRIDER M3 V2 ME-PM-M3: User Manual
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
DIT Demand Integration Time
1
From the set-up menu, use and but-
tons to select the DIT option. The screen will show the
currently selected integration time.
2-1
Press to enter the selection routine.
The current time interval will ash.
2-2 Use and buttons to select the time
required.
2-3 Press to conrm the selection. SET indicator
will appear.
Press to exit the DIT selection routine and return to the menu.
This sets the period in minutes over which the current and power readings are integrated for maximum demand measurement. The options are: 0,
5, 8, 10, 15, 20, 30, 60 minutes.

02 4047 0777 www.mercs.com.au02 4047 0788 9
STRIDER M3 V2 ME-PM-M3: User Manual
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
1 2
The backlit lasting time is settable. Default lasting time is 60 min-
utes. For example, if it’s set as 5, the backlit will be o in 5 minutes
from the last time operation on the meter
Press to enter the selection routine. The current time interval
will ash.
The options can be: 0 (always on), 5, 10, 30, 60, 120 minutes
Use and buttons to select the time required. Press to conrm the set-up.
12-1 2-2 2-3
From the set-up menu, use
and
buttons to select the System
option. The screen will show
the currently selected power
supply.
Press to enter the selec-
tion routine. The current selec-
tion will ash.
Use and buttons to
select the required system op-
tion: 1P2(W), 3P3(W), 3P4(W)
Press to conrm the se-
lection. SET indicator will
appear.
Press to exit the system selection routine and return to the menu. SET will disappear and you will be returned to the main Set-up Menu.
Backlit set-up
Supply System
Use this section to set the type of power supply being monitored.

02 4047 0777 www.mercs.com.au02 4047 0788 10
STRIDER M3 V2 ME-PM-M3: User Manual
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
1 2
From the Set-up menu, use and buttons to select the
Pulse Rate Option.
Press to enter the selection routine. The current setting will
ash.
Note: When it’s dFt, it means 2.5Wh/VArh
Use and buttons to choose pulse rate. On completion of the entry procedure, press to conrm the setting and press
to return to the main set up menu.
12-1 2-2
From the Set-up menu, use and
buttons to select the
Pulse output option.
Press to enter the selection routine.
The unit symbol will ash.
Use and buttons to choose
kWh or kVArh
On completion of the entry procedure, press to conrm the setting and press to return to the main set up menu.
Pulse output
Pulse rate
This option allows you to congure the pulse output 1. The output can be set to provide a pulse for a denes amount of energy active or reactive.
Use this section to set up the pulse output for:
Total kWh/Total kVArh
Import kWh/Export kWh
Import KVArh/Export KVArh
Use this to set the energy represented by each pulse. Rate can be set to 1 pulse per dFt/0.01/o.1/1/10/100kWh/kVArh.
(It shows 1 impulse = 10kWH/kVArh)

02 4047 0777 www.mercs.com.au02 4047 0788 11
STRIDER M3 V2 ME-PM-M3: User Manual
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
1-1 1-2
From the Set-up menu, use and buttons to select the
Pulse width Option.
Press to enter the selection routine. The current setting will
ash.
Use and buttons to choose pulse width. On completion of the entry procedure, press to conrm the setting and press
to return to the main set up menu.
Pulse Duration
Communication
The energy monitored can be active or reactive and the pulse width can be selected as 200, 100 (default) or 60ms.
There is a RS485 port can be used for communitcation using Modbus RTU protocol. For Modbus RTU, parameters are selected from Front panel.
(It shows pulse width of 200ms)
Pulse Duration
RS485 Address
(The range is from 001 to 247)

02 4047 0777 www.mercs.com.au02 4047 0788 12
STRIDER M3 V2 ME-PM-M3: User Manual
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
12-1 2-2
From the Set-up menu, use and
buttons to select the
Address ID
Press button to enter the selection
routine. The current setting will be ashing.
Use and buttons to choose
Modbus Address (001 to 247)
On completion of the entry procedure, press to conrm the setting and press button to return to the main set up menu.
12-1 2-2
From the Set-up menu, use and
buttons to select the
Baud Rate option.
Press button to enter the selection
routine. The current setting will be ashing.
Use and buttons to choose
Baud rate 2.4k, 4.8k, 9.6k, 19.2k, 38.4
On completion of the entry procedure, press to conrm the setting and press to return to the main set up menu.
12-1 2-2
From the Set-up menu, use and
buttons to select the
Parity option.
Press to enter the selection routine.
The current setting will ash.
Use and buttons to choose
Parity (EVEN / ODD / NONE)
On completion of the entry procedure, press to conrm the setting and press to return to the main set up menu.
Baud Rate
Parity

02 4047 0777 www.mercs.com.au02 4047 0788 13
STRIDER M3 V2 ME-PM-M3: User Manual
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
12-1 2-2
From the Set-up menu, use and
buttons to select the
Stop Bit option.
Press button to enter the selection
routine. The current setting will be ashing.
Use and buttons to choose
Baud rate 2.4k, 4.8k, 9.6k, 19.2k, 38.4
On completion of the entry procedure, press to conrm the setting and press to return to the main set up menu.
Stop Bits
CLR
Specications
Measured Parameters
Note: Default is 1, and only when the parity is NONE that the stop bit can be changed to 2.
The meter provides a function to reset the maximum demand value of current and power.
The unit can monitor and display the following parameters of a single phase two wire (1p2w) three phase three wire (3p3w) or four phase four
wire (3p4w) supply.
1 2
From the Set-up menu, use and buttons to select the
reset Option. Press to enter the selection routine. The MD will ash.
Press to conrm the setting and press to return to the main set up menu.

02 4047 0777 www.mercs.com.au02 4047 0788 14
STRIDER M3 V2 ME-PM-M3: User Manual
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
Voltage and Current
Voltage and Current
Accuracy
Interfaces for External Monitoring
Measured Inputs
Power Factor and Frequency and
Max Demand
• Phase to neutral voltages:
100 to 298V a.c. (not for 3p3w suuplies)
• Voltages between phases: 173 to 500V a.c. (3p supplies only)
• Basic current (lb): 10A
• Max current: 100A
• Min. Current: 5% of lb
• Starting current: 0.4% of lb
• Percentage total voltage harmonic distortion (THD%) for each
phase to N (not for 3p3w supplies)
• Percentage voltage THD% between phase
(three phase supplies only)
• Current THD% for each phase
• Imported active energy: 0 to 999999.99 kWh
• Exported active energy: 0 to 999999.99 kWh
• Imported reactive energy: 0 to 999999.99 kVArh
• Exported reactive energy: 0 to 999999.99 kVArh
• Voltage: 0·5% of range maximum
• Current: 0·5% of nominal
• Frequency: 0·2% of mid frequency
• Power factor: 1% if unity (0.01)
• Active power (W): ±1% of range maximum
• Reactive power (VAr): ±1% of range maximum
• Apparent power (VA): ±1% of range maximum
Three interfaces are provided
• an RS485 communication channel that can be programmed for Modbus RTU protocol
• an Pulse output (Pulse 1) indicating real-time measured energy. (congurable)
• an Pulse output (Pulse 2) 400imp/kWh
The Modbus conguration (Baud rate etc.) and the pulse output assignments (kW/kVArh, import/export etc.) are congured throught the Set-up
screens.
• Active energy (Wh): Class 0.5s IEC 62053-21
• Reactive energy (VARh): ±1% of range maximum
• Total harmonic distortion: 1% up to 31st harmonic
• Temperature co-ecient: Voltage and current = 0.013%/OC typical
Active energy = 0·018%/OC, typical
• Response time to step input: 1s, typical, to > 99% of nal reading,
at 50Hz
Voltage inputs through 4-way xed connector with 25mm2stranded wire capacity. Single phase two wire (1p2w), three phase three wire (3p3w) or
four phase four wire (3p4w) unbalanced. Line frequency measured from L1 voltage or L3 voltage.
• Total active energy: 0 to 999999.99 kWh
• Total reactive energy: 0 to 999999.99 kVArh
• Frequency in Hz
• Instantaneous power:
• Power 0 to 99999 W
• Reactive Power 0 to 99999 VAr
• Volt amps 0 to 99999 VA
• Maximum demanded power since last Demand reset Power
factor
• Maximum neutral demand current, since last Demand reset
(for 3p4w supply only)

02 4047 0777 www.mercs.com.au02 4047 0788 15
STRIDER M3 V2 ME-PM-M3: User Manual
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
Pulse Output
Reference Conditions of Inuence Quantities
RS485 Output for Modbus RTU
Environment
The unit provides two pulse outputs. Both pulse outputs are passive type.
Pulse output 1 is congurable. The pulse output can be set to generate pulses to represent total/import export kWh or kVArh.
The pulse constant can be set to generate 1 pulse per:
Inuence Quantities are variables that aect measurement errors to a minor degree. Accuracy is veried under nominal value (within the specied
tolerance) of these conditions.
For Modbus RTU, the following RS485 communication parameters can be congured from the Set-up menu:
Pulse width: 200/100/60ms
Pulse output 2 is non-congurable. It is xed up with active kWh. The constant is 400imp/kWh.
• dft = 2.5 Wh/VArh
• 0.01 = 10 Wh/VArh
• 0.1 = 100 Wh/VArh
• Ambient temperature: 23OC±1OC
• Input frequency: 50 or 60Hz±2%
• Input waveform: Sinusoidal (distortion factor < 0·005)
• Magnetic eld of external origin: Terrestial ux
• Operating temperature: -25OC to + 55OC*
• Storage temperature: -40OC to + 70OC*
• Relative humidity: 0 to 90%, non-condensing
• Altitude: Up to 2000m
• Warm up time: 1 minute
• Vibration: 10Hz to 50Hz, IEC 60068-2-6, 2g
• Baud rate: 2400, 4800, 9600, 19200, 38400
• Parity: none (default)/odd/even
• Stop bits: 1 or 2
• RS485 network address nnn: 3-digit number, 001 to 247
• ModbusTM Word order: Hi/Lo byte order is set automaticall to normal or reverse. It cannot be congured from the set-up menu.
• 1 = 1 kWh/kVArh
• 10 = 10 kWh/kVArh
• 100 = 100 kWh/kVArh

02 4047 0777 www.mercs.com.au02 4047 0788 16
STRIDER M3 V2 ME-PM-M3: User Manual
MerCs Pty Ltd, 55 Pendlebury Rd, Cardi, NSW, 2285, Australia | 2018 V1.1
Dimensions
Wiring Diagram
• Three Phase Three Wires:• Single Phase Two Wires: • Three Phase Four Wires:
Table of contents
Other MerCs Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

Omron
Omron EQUO Series user manual

Shenzhen Linshang Technology
Shenzhen Linshang Technology LS117 user manual

Apache Technologies
Apache Technologies STORM Operator's manual

Promet
Promet FiBO 200 quick start guide

SATO
SATO PC-7980GTI instruction manual

Precision Digital Corporation
Precision Digital Corporation TRIDENT instruction manual

ENCARDIO RITE
ENCARDIO RITE EDI-53P/L/I user manual

SANKO
SANKO SM-1100 instruction manual

SUTO
SUTO S450 Instruction and operation manual

Endress+Hauser
Endress+Hauser Proline Promag W 300 PROFINET operating instructions

AEMC instruments
AEMC instruments 6550 quick start guide

Emerson
Emerson Rosemount 8800D Series Reference manual