Microm MIX-4000 Series User manual

Installation and Operation Manual
Fire Alarm Control Panel
LT-6670 Rev 2
Nov 2022
FX-401
All MGC MIX-4000 Series Detectors are not FM Approved


3
Table of Contents
1.0 Industry Canada and FCC Notice 7
1.1 Notice for all FX-400 Series Built-In UDACTs Sold in Canada ...................................... 7
1.2 Industry Canada Notice ................................................................................................. 7
1.3 Notice for all FX-400 Series Built-in UDACTs Sold in the U.S.A. .................................. 7
1.4 FCC Notice .................................................................................................................... 8
2.0 Introduction 9
2.1 The FX-401 Addressable Fire Alarm Control Panel ....................................................... 9
3.0 FX-401 Overview 11
3.1 FX-401 Fire Alarm Control Panel Model ........................................................................ 11
3.2 FX-401 System Components ......................................................................................... 12
4.0 Installation 17
4.1 UB-1024DS Mechanical Installation .............................................................................. 17
4.2 Installation Tips .............................................................................................................. 18
4.3 Connections and Jumpers ............................................................................................. 19
4.4 Installing Adder Modules ................................................................................................ 21
4.5 Installing the ALC-480 Dual Loop Adder ........................................................................ 24
5.0 Operation 25
5.1 Addressable/Analog Devices ......................................................................................... 25
5.2 Configurable Input Types ............................................................................................... 27
5.3 Output Types ................................................................................................................. 31
5.4 NAC Circuit Operation ................................................................................................... 33
5.5 Single Stage Operation .................................................................................................. 33
5.6 Two-Stage Operation ..................................................................................................... 34
5.7 Evacuation Codes .......................................................................................................... 35
5.8 Positive Alarm Sequence ............................................................................................... 35
5.9 Remote Annunciator Operation ..................................................................................... 37
5.10 Dialer Operation ............................................................................................................. 39
5.11 Using the Operation Menu from the Control Panel ........................................................ 39
6.0 Indication & Controls 52
6.1 Indication and Controls .................................................................................................. 52

4
6.2 LCD Display ................................................................................................................... 52
6.3 Common LED Indicators and Control Buttons ............................................................... 54
7.0 Wiring 58
7.1 Wiring Tables ................................................................................................................. 58
7.2 Wire Routing .................................................................................................................. 60
7.3 Addressable Loop Wiring ............................................................................................... 61
7.4 NAC Circuit Wiring ......................................................................................................... 62
7.5 TS1 SPECIAL APPLICATION Power Source ................................................................ 65
7.6 Module and Devices Wiring ........................................................................................... 66
7.7 Power Supply Wiring ...................................................................................................... 71
7.8 Placement of Ferrites for FCC Standard ........................................................................ 74
7.9 System Checkout ........................................................................................................... 75
7.10 Troubleshooting ............................................................................................................. 75
8.0 Appendix A - Compatible Receivers 76
9.0 Appendix B - Manual Panel Configuration 77
10.0 Appendix C - Reporting 82
10.1 Ademco Contact-ID FX-400 Series Event Codes .......................................................... 82
10.2 Security Industries Association SIA Format Protocol FX-400 Series Event Codes ....... 83
11.0 Appendix D - Specifications And Features 84
11.1 FX-401 Fire Alarm Control Panel ................................................................................... 84
11.2 FX-401 System Module and Annunciator Specifications ............................................... 85
12.0 Appendix E - Battery Calculations 86
13.0 Warranty and Warning Information 88

5
List of Figures
Figure 1 FX-401 with DOX-1024DSR .......................................................................................... 11
Figure 2 UB-1024DS Backbox Installation Instructions and Dimensions ..................................... 17
Figure 3 Port and Jumper Locations on Main Board .................................................................... 19
Figure 4 Jumper on back of display ............................................................................................. 21
Figure 5 Main Board with all Adder Modules Installed ................................................................. 22
Figure 6 Installing the PR-300 Polarity Reversal and City Tie Module ........................................ 23
Figure 7 Installing the ALC-480 Dual Loop Adder ........................................................................ 24
Figure 8 MGC-400 Configurator Date and Time Settings ............................................................ 26
Figure 9 Enabling the Positive Alarm Sequence .......................................................................... 37
Figure 10 Operation Menu ............................................................................................................. 40
Figure 11 LED Indicators and Control Buttons ............................................................................... 52
Figure 12 Numeric Keypad ............................................................................................................ 53
Figure 13 Wire Routing .................................................................................................................. 60
Figure 14 Addressable Loop Wiring - Class B (DCLB) .................................................................. 61
Figure 15 Addressable Loop Wiring - Class A (DCLA) .................................................................. 61
Figure 16 Addressable Loop Wiring - Class X (DCLC) .................................................................. 62
Figure 17 NAC Circuit – Class B Wiring ......................................................................................... 63
Figure 18 NAC Circuit – Class A Wiring ......................................................................................... 63
Figure 19 RTI-1 Common Remote Trouble Indicator Wiring .......................................................... 64
Figure 20 TS1 SPECIAL APPLICATION Power Source Wiring ..................................................... 65
Figure 21 Wiring the Dialer ........................................................................................................... 66
Figure 22 Connecting an FX-401 FACP to a 3G4010 Interface Device in Canada ....................... 67
Figure 23 Connecting a FACP to a 3G4010CF Interface Device outside Canada ........................ 68
Figure 24 Connecting a FACP to a SLE-LTEV or SLE-LTEA Interface Device outside Canada ... 69
Figure 25 Wiring the PR-300 Polarity Reversal and City Tie Module ............................................ 70
Figure 26 Main Power Supply Wiring and Connections ................................................................. 72
Figure 27 Supervision of Auxiliary Supplies ................................................................................... 73

6
List of Tables
Table 1 FX-401 System Components ......................................................................................... 12
Table 2 MIX-4000 MGC Addressable Devices ........................................................................... 16
Table 3 Main Board Connectors and Jumpers ............................................................................ 20
Table 4 Core Board Jumpers ...................................................................................................... 20
Table 5 PR-300 Polarity Reversal and City Tie Module Connectors and Jumpers ..................... 23
Table 6 ALC-480 Dual Loop Adder Connector ........................................................................... 24
Table 7 Settings Permitted in UL864 .......................................................................................... 25
Table 8 Settings Permitted in CAN/ULC-S527and CAN/ULC-S559 ........................................... 25
Table 9 Configurable Input Types ............................................................................................... 27
Table 10 Configurable Output Types ............................................................................................ 32
Table 11 Annunciator Address DIP Switch Settings ..................................................................... 37
Table 12 List Bypass Special Characters ..................................................................................... 48
Table 13 LED Indicators and Control Buttons ............................................................................... 54
Table 14 MGC Devices Addressable Loop Wiring Table .............................................................. 58
Table 15 NAC and Auxiliary Power Circuits Wiring Table ............................................................. 59
Table 16 Conventional Zone Module Input Circuit Wiring Table ................................................... 59
Table 17 Power Supply Electrical Ratings .................................................................................... 71
Table 18 Compatible DACR Receivers ......................................................................................... 76
Table 19 Contact-ID Event Codes ................................................................................................ 82
Table 20 SIA-DCS Event Codes ................................................................................................... 83
Table 21 FX-401 Specifications .................................................................................................... 84
Table 22 FX-401 Modules and Annunciator Specifications .......................................................... 85
Table 23 Recommended Batteries ................................................................................................ 87

7
1.0 Industry Canada and FCC Notice
1.1 Notice for all FX-400 Series Built-In UDACTs Sold in Canada
Mircom's FX-400 SERIES BUILT-IN UDACT Communicator described in this manual is listed
by Underwriters Laboratories Canada (ULC) for use in slave application under Standard ULC-
S527 (Standard for Control Units for Fire Alarm Systems) and ULC-S559 (Equipment for Fire
Signal Receiving Centres and Systems). These Communicators should be installed in
accordance with this manual; the Canadian / Provincial / Local Electrical Code; and/or the
local Authority Having Jurisdiction (AHJ).
1.2 Industry Canada Notice
Repairs to certified equipment should be made by an authorized Canadian maintenance
facility designated by the supplier. Any repairs or alteration made by the user to this
equipment, or equipment malfunctions, may give the telecommunications company cause to
request the user to disconnect the equipment. Users should ensure for their own protection
that the Earth Ground connections of the power utility, telephone lines and internal metallic
water pipe system, if present, are connected together. This is necessary both for proper
operation and for protection.
1.3 Notice for all FX-400 Series Built-in UDACTs Sold in the U.S.A.
Mircom's FX-400 SERIES BUILT-IN UDACT Digital Communicator described in this manual is
listed by Underwriters Laboratories Inc. (ULI) for use in slave application in conjunction with a
Listed Fire Alarm Control Panel under Standard 864 (Control Units for Fire Protective
Signalling Systems). These Communicators comply with the National Fire Protection
Association (NFPA) performance requirements for UDACTs and should be installed in
accordance with NFPA 72 (Supervising Station Fire Alarm System). These Communicators
should be installed in accordance with this manual; the National Electrical Code (NFPA 70);
and/or the local Authority Having Jurisdiction (AHJ).
Attention: Users should not attempt to make such connections themselves, but
should contact the appropriate electric inspection authority, or
electrician, as appropriate.
Notes: The Ringer Equivalence Number (REN) assigned to each terminal device
provides an indication of the maximum number of terminals allowed to be
connected to a telephone interface. The termination on an interface may consist
of any combination of devices subject only to the requirement that the sum of the
Ringer Equivalence Numbers of all the devices does not exceed 5.
The Label Identification Number for this product is US:1M8AL01BFX3500. The
01B represents the REN without a decimal point (for example, 01B is a REN of
0.1B).
!
i

8
1.4 FCC Notice
This equipment complies with Part 68 of the FCC rules and the requirements adopted by the
ACTA. On the telco transformer of this equipment is a label that contains, among other
information, a product identifier in the format US:1M8AL01BFX3500. If requested, this number
must be provided to the telephone company. This equipment is capable of seizing the line.
This capability is provided in the hardware.
Type of Service
The Communicator is designed to be used on standard device telephone lines. It connects to
the telephone line by means of a standard jack called the USOC RJ-11C (or USOC FJ45S).
Connection to telephone company provided coin service (central office implemented systems)
is prohibited. Connection to party lines service is subject to state tariffs.
Telephone Company Procedures
The goal of the telephone company is to provide you with the best service it can. In order to do
this, it may occasionally be necessary for them to make changes in their equipment,
operations or procedures. If these changes might affect your service or the operation of your
equipment, the telephone company will give you notice, in writing, to allow you to make any
changes necessary to maintain uninterrupted service. In certain circumstances, it may be
necessary for the telephone company to request information from you concerning the
equipment which you have connected to your telephone line. Upon request of the telephone
company, provide the FCC registration number and the ringer equivalence number (REN);
both of these items are listed on the equipment label. The sum of all of the REN’s on your
telephone lines should be less than five in order to assure proper service from the telephone
company. In some cases, a sum of five may not be usable on a given line.
If Problems Arise
If any of your telephone equipment is not operating properly, you should immediately remove it
from your telephone line, as it may cause harm to the telephone network. If the telephone
company notes a problem, they may temporarily discontinue service. When practical, they will
notify you in advance of this disconnection. If advance notice is not feasible, you will be
notified as soon as possible. When you are notified, you will be given the opportunity to correct
the problem and informed of your right to file a complaint with the FCC. Contact your
telephone company if you have any questions about your phone line. In the event repairs are
ever needed on the Communicator, they should be performed by Mircom Technologies Ltd. or
an authorized representative of Mircom Technologies Ltd. For information contact Mircom
Technologies Ltd. at the address and phone numbers shown on the back page of this
document.

9
2.0 Introduction
This document provides information for the successful installation and operation of the FX-401
Fire Alarm Control Panel (FACP).
2.1 The FX-401 Addressable Fire Alarm Control Panel
Mircom's FX-401 Addressable Fire Alarm Control Panel provides the following:
•MGC Protocol with up to three addressable (SLC) loops with a maximum of 720 MGC
devices (MIX-4000 series), 240 per loop.
•Compatible with MGC devices (MIX-4000).
•Compatible with conventional detectors using MGC MIX-4042 Conventional Zone
module, refer to document LT-1023 for compatible detectors.
•Four Power Limited Class B, Class A NAC circuits.
•NAC circuits may be configured as silenceable signal, non-silenceable signal,
silenceable strobes, non-silenceable strobes, or relay output. The audible signal may be
Steady, Temporal Code, California Code, or March Time.
•Supports sync strobe protocols from major manufacturers.
•Software configuration.
•Two-stage, alarm verification, and positive alarm sequence operations.
•Configurable Signal Silence Inhibit, Auto Signal Silence, Two-Stage Operation, and One-
Man Walk Test.
•Subsequent Alarm, Supervisory, Monitor and Trouble operation.
•Relay Contacts for Common Alarm, Common Supervisory and Common Trouble all non-
disconnectable and Auxiliary Alarm Relay (disconnectable).
•Built-in Dialer Module.
2.1.1 Optional Items
•Supports up to 2 RAX-1048TZDS Display Adder Modules.
•Semi-flush or surface mountable enclosures for retrofits and new installations.
Note: Installation of the FX-401 Fire Alarm Control panel should be in accordance with
Canadian Electrical Code Part 1, ULC-S524 installation of Fire Alarm System; or
National Electrical Code NFPA 70 and NFPA 72. Final acceptance subject to the
Local Authority Having Jurisdiction (AHJ).
i

10
2.2 General Notes
Circuits
Refers to a physical electrical interface for the analog loop, indicating signals or relays, and
common alarm, supervisory, and trouble relay outputs.
Zone/Group
Is a logical concept for a Fire Alarm Protected Area, and will consist of at least one Circuit. The
FX-401 uses Groups extensively to facilitate annunciation of multiple input and output points
on the RAX-1048TZDS (up to 96 points) and to facilitate the indication of bypass points.
Display Points
The FX-401 LCD display annunciates the status of the system and connected devices. There
are up to two (2) RAX-1048TZDS Display Adder Module Display points that may be configured
to assign LEDs to groups of inputs or outputs. There are two LEDs for every display point; one
single color (yellow) and one dual color (red/yellow).
Wiring Styles
The addressable (SLC) loops can be configured system-wide as Class B (DCLB) or Class A
(DCLA). With the addition of isolators, a Class A (DCLA) loop will become a Class X (DCLC).

11
3.0 FX-401 Overview
This chapter lists all the possible components of an FX-401 system.
3.1 FX-401 Fire Alarm Control Panel Model
The FX-401 Fire Alarm Control Panel has the following features:
•Main Board, Power Supply and Backbox.
•Multi-zone fire alarm control panel
•MAM-3500 Main Display with 4 x 20 LCD display.
•Class A (DCLA), Class X (DCLC), or Class B (DCLB) analog loop(s).
•Four Power Limited Class B, Class A NAC circuits (max 1.5 Amps each - 6.0 Amps
total).
•MGC Protocol with up to three addressable (SLC) loops with a maximum of 720 MGC
devices (MIX-4000 series), 240 per loop.
•Dedicated common alarm, supervisory, trouble, and auxiliary alarm relays.
•Additional RAX-1048TZDS Display Adder Module can be added to provide 48
annunciation points per Adder. Two modules required for 96 annunciation points.
•Additional outputs include connections for a RTI remote trouble indicator, PR-300
Reverse Polarity Module, an RS-485 bus for connection of up to seven RAX-LCD-LITE,
RAM-3500-LCDs, SRM-312s and RA-1000 Series annunciators.
•Auxiliary power is available in the form of 24V FWR unfiltered and unsupervised, 24VDC
filtered and regulated, and resettable auxiliary power supply.
Figure 1 FX-401 with DOX-1024DSR
All MGC MIX-4000 Series Detectors are not FM Approved

12
3.2 FX-401 System Components
The following table describes the components of the FX-401.
Table 1 FX-401 System Components
Model Description
FX-401
Model FX-401, black backbox, red door enclosure
comes complete with main board, power supply,
transformer and main display.
MAM-3500 Main Display
DOX-1024DS White enclosure door
DOX-1024DSR Red enclosure door
ALC-480 480 Point Dual Loop Adder
Visual
IndicatorTest

13
RAM-3500-LCD Remote Annunciator with 4-line LCD Display.
PR-300 Polarity Reversal and City Tie Module.
PCS-100
Power Supply Interface Board use for powering
3G4010 or 3G4010CF Universal Wireless Alarm
Communicator.
SRM-312W Smart Relay Module with White Enclosure.
Can support up to 12 relays.
SRM-312R Smart Relay Module with Red Enclosure.
Can support up to 12 relays.
RAM-1032TZDS 32 point Remote Annunciator with 32 Trouble LEDs.
Table 1 FX-401 System Components (Continued)
Model Description

14
RAX-1048TZDS 48 Point adder annunciator display with 48 Trouble
LEDs.
MGD-32 Graphic Annunciator.
RAX-LCD-LITE Remote Annunciator with 4-line LCD Display.
AGD-048 Graphic Annunciator Adder Driver Board.
RTI-1 Common Remote Trouble Indicator, Buzzer and
LED.
BB-1001D White Enclosure for one annunciator.
BB-1001DR Red Enclosure for one annunciator.
BB-1001DS Enclosure for one annunciator with stainless steel
door.
BB-1001WPA White enclosure for one annunciator rated for
outdoor environment, wet location.
BB-1001WPRA Red enclosure for one annunciator rated for outdoor
environment, wet location.
Table 1 FX-401 System Components (Continued)
Model Description

15
BB-1002D White Enclosure for two annunciators.
BB-1002DR Red Enclosure for two annunciators.
BB-1002DS Enclosure for two annunciators with stainless steel
door.
BB-1002WPA White enclosure for two annunciators rated for
outdoor environment, wet location.
BB-1002WPRA Red enclosure for two annunciators rated for
outdoor environment, wet location.
BB-1003D White Enclosure for three annunciators.
BB-1003DR Red Enclosure for three annunciators.
BB-1003DS Enclosure for three annunciators with stainless steel
door.
BB-1008D White Enclosure for eight annunciators.
BB-1008DR Red Enclosure for eight annunciators.
BB-1012D White Enclosure for twelve annunciators.
BB-1012DR Red Enclosure for twelve annunciators.
MP-300 End of line resistor plate. 3K9.
Table 1 FX-401 System Components (Continued)
Model Description

16
3.2.1 Devices
The following tables lists all the devices available for the FX-401.
Table 2 MIX-4000 MGC Addressable Devices
MGC Addressable Detectors and Control Modules
MGC Addressable Detectors
MIX-4010 Photoelectric Smoke Sensor
MIX-4010-ISO Photoelectric Smoke Sensor with Built-in Short Circuit Isolator
MIX-4020 Multi-Sensor Detector
MIX-4020-ISO Multi-Sensor Detector with Built-in Short Circuit Isolator
MIX-4030 Tri-Mode Heat Detector
MIX-4030-ISO Tri-Mode Heat Detector with Built-in Short Circuit Isolator
MGC Addressable Control Modules
MIX-4040 Dual Input Module
MIX-4041 Mini Dual Input Module
MIX-4042 Conventional Zone Module
MIX-4045 Dual Relay Module
MIX-4046 Supervised Output Module
MIX-4070 Short Circuit Isolator Module
MGC Addressable Bases
MIX-4001 6” Diameter Base
MIX-4002 4” Diameter Base
Mircom Addressable Manual Stations
MS-401MP Intelligent Single Stage Manual Station MP
MS-401MPU Intelligent Single Stage Manual Station MP (US)
MS-402MP Intelligent Two Stage Manual Station MP
MS-407MP Intelligent Single Stage Manual Station MP with additional N.C. switch
MS-407MPU Intelligent Single Stage Manual Station MP with additional N.C. switch (US)
MS-702MP Intelligent Key-Resettable Two Stage Manual Station MP
MS-710MP Intelligent Key-Resettable Single Stage Dual Action Manual Station MP
MS-710MPU Intelligent Key-Resettable Single Stage Dual Action Manual Station MP (US)
All MGC MIX-4000 Series Detectors are not FM Approved

17
4.0 Installation
This chapter describes the installation of the FX-401.
4.1 UB-1024DS Mechanical Installation
The UB-1024DS is a black backbox suitable for flush or surface mounting with a built-in trim
ring. The DOX-1024DS is the front door of this backbox, which is available in white and red,
DOX-1024DSR. An enclosure consists of the backbox plus the connected front door.
Figure 2 UB-1024DS Backbox Installation Instructions and Dimensions
Dimensions of Enclosure (minus built in trim ring) 14.5” x 4.2” x 26”
Distance between horizontal mounting screws 12”
Distance between vertical mounting screws 23.5”
Complete Dimensions of Enclosures 16.3” x 5.5” x 27.5”
26.0 "
14.5 "
4.2 "
External Dimensions
12.0 "
23.5 "
Mounting Dimensions
1.3 " 1.7 "
2.0 "
Top View
2.1 "
1.3 " 6.0 "
9.5 "
Side View

18
4.2 Installation Tips
1. Group the incoming wires through the top of the enclosure. For easy identification and
neatness use a wire tie to group wires.
2. Be sure to connect a solid Earth Ground (from building system ground / to a cold water
pipe) to the Chassis Earth Ground Mounting Lug, and to connect the Earth Ground Wire
Lugs from the Main Chassis to the ground screw on the Backbox.
Attention: DO NOT install cable through bottom of the box. This space is reserved
for Batteries.
!

19
4.3 Connections and Jumpers
Figure 3 Port and Jumper Locations on Main Board
P2
P3
P4
P5
P8
P9
P13
P10P11P14
JW1
JW2
JW5
JW6
JW10
JW7
Buzzer
JW11
3
2
1
3
2
1
JW4 JW5
Core Board
Main Board
P7
JW12
JW14
1
3
2

20
Table 3 Main Board Connectors and Jumpers
Connector/
Jumper
Description
P2 To Power Supply
P3 To Power Supply
P4 Ribbon Cable connects to P4 of front display
P5 To PC Configurator
P7 Factory Use Only
P8 To PR-300
P9 To Printer
P10 To ALC-480 Loop Adder
P11 Factory Use Only
P13 USB Port to PC Configurator
P14 Future Use
JW1 Must be ON (default) - Allows Configuration Connection
JW2 Must be ON (default) - Annunciator End of Line
JW5 Normally open (default). Place jumper here and power down (AC and batteries) and
power back to restore Master Password. After reset, remove jumper and leave
normally open.
JW6 Normally open (default) to BLOCK remote configuration via modem. Place jumper
here to ALLOW for remote configuration. When jumper is set panel will indicate a
trouble.
JW7 On the Main Fire Alarm Module, this jumper must be removed if a PR-300 Polarity
Reversal and City Tie Module is installed. The default setting is jumper ON.
JW10 Must be in the 1-2 Position (Bottom 2 Pins) - Allows PC Connection through serial port
JW11 Place in the 1-2 Position (Bottom 2 Pins) for Serial Port or Place in the 2-3 Position
(Top 2 Pins) for Keltron Dialer.
JW12 Close pins 2 and 3 to send the debug trace to the printer. Close pins 1 and 2 to send
events to the printer. The printer is supervised when the pins are in position 2 and 3.
The default setting is the 1-2 position.
JW14 Factory set on pins 1 and 2. Do not change.
Table 4 Core Board Jumpers
Jumper Description
JW4 Factory set closed (ON). Leave as is.
JW5 Factory set open (OFF). Leave as is.
Attention: ADVANCED INSTALLER NOTE
Setting JW5 and JW6 on the main board at start-up will revert the panel
to the default configuration.
!
This manual suits for next models
1
Table of contents
Other Microm Control Panel manuals
Popular Control Panel manuals by other brands

Honeywell
Honeywell Fire-Lite Alarms ES-1000X manual

Flybox
Flybox Vigilus Series installation manual

Eaton
Eaton PanelMate 5000 Series Express set-up guide

FuelTech
FuelTech Switch Panel-8 owner's manual

Extron electronics
Extron electronics Decorator-Style Series Setup guide

Fourgroup
Fourgroup DUPLEX-UP Use and installation guide

ADT
ADT Honeywell Domonial QUICK CONSUMER REFERENCE GUIDE

SILENT KNIGHT
SILENT KNIGHT SK-2224 Installation and operation manual

INIM
INIM SmartLoop2080/S Programming manual

SOMFY
SOMFY io homecontrol VSYSTEMPRO Premium installation instructions

Texecom
Texecom Veritas R8 Plus installation manual

AERMEC
AERMEC PCO5 user manual