manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Mighty Module
  6. •
  7. Security System
  8. •
  9. Mighty Module MM1420 User manual

Mighty Module MM1420 User manual

DESCRIPTION
TheMM1420SeriesRTDinputalarmsmoni-
tor an RTD (resistance thermometer) input
and provide two sets of SPDT, 5A alarm
relays with two independently adjustable
setpoints. Each setpoint has a set of red/
greenLEDs toindicate alarmsstatus. When
theinput is betweenthesetpoints, therelays
arenormally de-energized. When thesignal
exceeds a particular setpoint, the relay be-
comes energized.
EachmodulecanbesuppliedasaHI/HI,HI/
LO, or LO/LO alarm (HI/LO supplied if not
specified). Toprovidea“fail-safe” operation
(loss of power resulting in an alarm state),
select Option R.
Standard deadband on both alarms is fixed
at 0.5% of span. (Option A provides adjust-
able deadband of 0.5% to 100% span.)
Option D, latching alarms, has no deadband
control. Oncethelimithasbeenreachedthe
alarmlatchesand power to the modulemust
bemomentarilyinterruptedtoresetthealarm.
The modules include filtering and condition-
ing to reduce susceptibility to transients and
noisy operations.
MODELNUMBERS
These instructions cover the following
setpoint styles:
MM1420 RTDInputDualAlarm
(25 turn screwdriver adj)
MM1421 RTDInputDualAlarm
(Single turn dials)
MM1424 RTDInputDualAlarm
(Ten turn precision dials)
OPTIONS
These instructions cover the following op-
tions on the MM1420. Options installed are
listed on the label attached to the side of the
module.
AProvides top accessed screwdriver ad-
justable deadbands from 0.5% to 100%
of span, instead of the normal fixed 0.5%
deadbands.
DLatching alarms. Reset by momentary
interruption of line power.
DC Power Inverter isolated 12 or 24 VDC
power.
E11-pin header instead of standard 20-
pin. Available only on MM1420, MM1421
and MM1424 without Option T.
RThe Normal condition for the relays is
de-energized. They energize for alarm
conditions. Option R (Reverse sense)
reverses this logic (Failsafe).
UAll circuit boards conformal coated for
protection against moisture.
CONTROLS
TheMM1420,MM1421andMM1424modules
contain two setpoint controls, plus zero and
span adjustments. The setpoint controls in
the MM1420 are 25-turn blind trimpots.
MM1421andMM1424contain1-turnand10-
turn calibrated dials, respectively. Option A,
adjustable deadband, adds two deadband
trimpots.
CALIBRATION
Modules are shipped with ZERO and SPAN
precalibrated. The user needs only adjust
theSETPOINTSandoptionalDEADBANDS
for the desired levels.
MM1420, MM1421 &
MM1424
RTD INPUT
DUAL ALARMS
Refer to the instrument’s label to determine
your instrument’s supply voltage and input
and output ranges. Refer to the “Block
Diagram and Pin Connections” for connec-
tions. 20-pin and 11-pin styles both are
shown.
Connect a precision decade resistance,
potentiometer or RTD simulator to the input.
To avoid errors due to the resistances of the
connecting wires, use a three-wire connec-
tionas showninthe “BlockDiagram andPin
Connections”.
(Note: When calibrating latching alarms,
OptionD, it willbe necessary tomomentarily
interrupt power to reset the alarm after each
trip.)
To calibrate the alarm setpoints, begin with
theoptionalDEADBANDcontrolsturnedfully
ccw. Adjust the input resistance to the
desiredalarm1setpoint. AdjusttheSETPOINT
1 control until its LED just turns red (ccw for
a high alarm, cw for low).
Change the input resistance to the desired
alarm 2 setpoint and similarly adjust the
SETPOINT2control.
The MM1421 (single turn dial) and MM1424
(10-turn dial) may be set using their 0-100%
dials.
Adjust the optional DEADBAND controls for
the desired amount of deadband. Vary the
input signal up and down to check the levels
at which the relay trips and resets. The
setpoint will remain approximately centered
in the middle of the deadband.
If there is a need to recalibrate ZERO and
SPAN,turntheoptionalDEADBAND controls
fully ccw and proceed as follows:
Set the resistance to the low end of the input
range. Turn the SETPOINT 1 control fully
ccw. Adjust the ZERO control until the
SETPOINT1LEDjust changes color.
Changetheresistancetothehighendofthe
input range. Turn the SETPOINT 2 control
fully cw. Adjust the SPAN control until the
SETPOINT2LEDjust changes color.
Repeat until the ZERO and SPAN settings
both are correct.
After adjusting the ZERO and SPAN con-
trols, the SETPOINT and DEADBAND con-
trols should be reset as described above.
RELAYCONTACTPROTECTION
When inductive loads such as motors, relays
or transformers are switched, voltage tran-
sients may be generated which exceed the
ratings of the relay contacts. The resulting
arcing can quickly destroy the contacts.
(RefertotheSPECIFICATIONSbelowforthe
relay contact ratings.)
Surge suppression is required across induc-
tive loads to guard against premature relay
failure. Figure 1 illustrates diode surge sup-
pressionforaDCload. Thediode’soperating
(peak inverse) voltage should exceed the
load’s supply voltage by at least 50% and
should have a current rating of at least one
ampere.
Figure 2 shows surge suppression for an AC
load, using an MOV (Metal Oxide Varistor)
and a capacitor. The breakdown voltage
ratings of both the MOV and the capacitor
must exceed the peak AC voltage.
Withnormal sine-wavepower, PEAK= 1.414
xRMSvoltage. For115VACpowera200volt
peak rating is recommended.
ALARM TYPE HI/LO HI/HI LO/LO
SETPOINT1 HI HI LO
SETPOINT 2 LO HI LO
1 2
SPECIFICATIONS
RTD INPUT
3-Wire or 2-Wire,
10 ohms to 2000 ohms
INPUT RANGE
select any range within RTD limit
[min span 25°F/14°C
(100°F/55°C with 10 ohms RTD)]
EXCITATION CURRENT
10 ohms 10 mA
100 ohms 5 mA
1000 ohms 0.5 mA
2000 ohms 0.2 mA
SETPOINT
each alarm 0 to 100% of span
DEADBAND
Standard
fixed 0.5% of span
(Option A)
0.5% to 100% of span
(Option D)
Latching. Interrupt power to reset.
OPEN SENSOR OUTPUT
³full scale
ACCURACY
±0.1% of span or 0.02 ohms,
whichever is greater
COMMON MODE REJECTION
120 dB, DC to 60 Hz
RELAY CONTACTS (spdt)
Resistive Load:
5 A max, 150 W max, 240 VAC max,
30 VDC max
Inductive Load:
1/8 HP max at 120/240 VAC
OPERATING TEMPERATURE
14°F to 140°F/–10°C to 60°C
TEMPERATURE STABILITY
±0.02% of span or 0.025°C/°C,
whichever is greater
POWER
115 VAC ±10%, 50 or 60 Hz
(2.5 W max)
230 VAC ±10%, 50 or 60 Hz
(2.5 W max)
(DC Power Option)
12 VDC (limits 10 VDC to 15 VDC)
(2.5 W max)
24 VDC (limits 21 VDC to 32 VDC)
(2.5 W max)
Isolation, DC power supply to input
common: 10 megohms
* Within specified range limits.
CASEDIMENSIONSINCHES(mm)
WARRANTY
Contact the factory 1-800-234-1343.
MOUNTING
MM1420, MM1421 and MM1424 are designed to plug into a standard 20-pin relay socket.
(Option E requires an 11-pin socket.) MP020 and MP011 are 20-pin and 11-pin sockets
suitable for mounting on a flat surface. MP011 may also be mounted in a piece of PVC track.
A DIN-rail mounted socket, DMP011, is available for 35mm symmetrical rail.
Specifications are subject to change without notice. ©2008 Wilkerson Instrument Co., Inc. DWG#101034C 3/15
3 4

This manual suits for next models

2

Other Mighty Module Security System manuals

Mighty Module MM1520 User manual

Mighty Module

Mighty Module MM1520 User manual

Mighty Module MM1200 User manual

Mighty Module

Mighty Module MM1200 User manual

Mighty Module MM1820 User manual

Mighty Module

Mighty Module MM1820 User manual

Mighty Module MM1700 User manual

Mighty Module

Mighty Module MM1700 User manual

Popular Security System manuals by other brands

Fire-Lite BG-12LAO operating instructions

Fire-Lite

Fire-Lite BG-12LAO operating instructions

Heath Zenith SL-7001 Installation

Heath Zenith

Heath Zenith SL-7001 Installation

Homeguard LS100 user manual

Homeguard

Homeguard LS100 user manual

Blackline Safety 102140 Setup guide

Blackline Safety

Blackline Safety 102140 Setup guide

Q-See Premium QC5416-16E3-1 Specifications

Q-See

Q-See Premium QC5416-16E3-1 Specifications

Abus TVVR30004 quick guide

Abus

Abus TVVR30004 quick guide

Silvercrest 91276 operating instructions

Silvercrest

Silvercrest 91276 operating instructions

Q-See QTT442266--88003 Quick installation guide

Q-See

Q-See QTT442266--88003 Quick installation guide

Berger + Schröter 20319 user manual

Berger + Schröter

Berger + Schröter 20319 user manual

HIK VISION EKI-K41B44W quick start guide

HIK VISION

HIK VISION EKI-K41B44W quick start guide

Watchguard DVR4ENTPACK Quick installation guide

Watchguard

Watchguard DVR4ENTPACK Quick installation guide

Paradox MG5000 user guide

Paradox

Paradox MG5000 user guide

Gocontrol WNK01-21KIT Quick programming guide

Gocontrol

Gocontrol WNK01-21KIT Quick programming guide

GSM Activate ADRV11 quick start guide

GSM Activate

GSM Activate ADRV11 quick start guide

Q-See QR4074-411 Quick installation guide

Q-See

Q-See QR4074-411 Quick installation guide

Q-See QR4174-418 quick start guide

Q-See

Q-See QR4174-418 quick start guide

Safety Link GO Trek quick start guide

Safety Link

Safety Link GO Trek quick start guide

Metasys IFC-1010 Technical Manual Programming Section

Metasys

Metasys IFC-1010 Technical Manual Programming Section

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.