MM7010 &
MM7010 ISO
FREQUENCY INPUT
TRANSMITTERS
DESCRIPTION
The MM7010 is used to provide a DC
output voltage or current proportional to
the frequency of the input signal. It is
useful for measuring speed of motor,
conveyors, or other devices that can
createaperiodicsignalproportionaltothe
desired function. The wide range of input
sensitivityallowstheMM7010tobedriven
from low level magnetic pickups as well
as logic level signals.
A threshold adjustment sets the minimum
input amplitude the module will process.
Thisallows theuser totrade offsensitivity
versus noise rejection. An optional pullup
resistor (Option P) permits use with
contact-closure or open-collector inputs.
OPTIONS
The following options are available on
theMM7010&MM7010ISO:
P10 kilohm pullup resistor for use
with open-collector or contact-
closure inputs.
UAll circuit boards conformal coated
for protection against moisture.
DCPower
Inverter-isolated 12 V or 24 VDC
power.
CONTROLS
Three controls, ZERO, SPAN and
THRESHOLD,areaccessiblefromthetop
of the module.
CALIBRATION
The MM7010 is shipped with ZERO and
SPAN pre-calibrated. The user need only
adjust the THRESHOLD for the desired
sensitivity.
The THRESHOLD adjustment allows the
module to be made insensitive to the line
frequency pickup or other noise signals
whose levels are below the threshold
setting.Turningthiscontrolfullyclockwise
reduces the threshold to zero and makes
the input most sensitive.
Toadjust, settheinput atabout half-scale
frequency and at about 25% of its normal
amplitude.Turnthe THRESHOLDcontrol
fully clockwise then, while monitoring the
output, turn the control counterclockwise
until the output drops (suddenly) to its
low-end value. NOTE: If the output does
not drop, leave the control fully
counterclockwise.
Tore-calibrateZEROandSPAN,proceed
as follows:
Refer to the instrument's label to determine
your instrument's supply voltage and input
andoutputranges.Refertothe“BlockDiagram
and Pin Connections” for pin connections.
Connect a calibrated frequency source to
theinputoftheinstrument.(OptionP,ifnoted
on the label, indicates a pullup resistor has
been added for use with switch-closure or
open-collectorinput(SeeBlockDiagramand
Pin Connections).
Set the input frequency to the low end of the
input range and adjust the ZERO control for
thelow-end oftheinput rangeandadjust the
ZERO control for the low-end output voltage
or current. Increase the input frequency to
fullscaleand adjusttheSPANcontrolfor the
full-scale output. Repeat until both readings
are correct.
CASE DIMENSIONS INCHES [mm]
MOUNTING
Themoduleisdesignedtoplugintoastandard
8-pin relay socket. (MP008) is a molded
plastic socket suitable for mounting on a flat
surface or snap into a 2¾ inch wide PVC
track (TRK48).
A spring hold-down clip (CLP1) is available
for installation where vibration may be a
problem.
A DIN rail mounted socket (DMP008) is
available for 35mm symmetrical DIN rail.
A Killark HK Series explosion-proof housing
with dome and 8-pin socket is available
(HKB-HK2D-8).
WARRANTY
TheMightyModuleSeries of productscarry
a limited warranty of 10 + 5 years. In the
event of a failure due to defective material
or workmanship, during the 10 year period,
the unit will be repaired or replaced at no
charge. For a period of 5 years after the
initial 10 year warranty, the unit will be
repaired, if possible, for a cost of 10 % of
the original purchase price. Relays are not
covered by the warranty.
1 2
SPECIFICATIONS
INPUTRANGE
select any range from
0 to 10 Hz min
to 0 to 60 kHz max
INPUTSENSITIVITY
any voltage from 50 mV
to 100 V peak
INPUTIMPEDANCE
100 kilohms
OUTPUTRANGE
Voltage
select any range from
–10 V to +15 V,
10 mA max load
(min span 0.2 V)
Current
select any range from
0 to 20 mA max
24 V compliance*
(min span 1 mA)
ACCURACY
±0.1% of span
LINEARITY
±0.1% of span
COMMONMODEREJECTION
120 dB, DC to 60 Hz
ISOLATION (ISO OPTION)
Output/Input
>500 megohms
Breakdown Voltage
>1000 VAC rms
BREAKDOWN,
PWR/CIRCUITRY
>1500 VAC rms
OPERATINGTEMPERATURE
14°F to 140°F
–10°C to 60°C
TEMPERATURESTABILITY
±0.02% of span/°C max
OPTION P
Pullup resistor to + input
10 kilohms to +5 VDC
Open-circuit voltage
+5 VDC
POWER
115 VAC ±10%,
50 or 60 Hz
(2.5 W max)
230 VAC ±10%,
50 or 60 Hz
(2.5 W max)
(DC Power Option)
12 VDC
(limits 10 VDC to 15 VDC)
(2.5 W max)
24 VDC
(limits 21 VDC to 32 VDC)
(2.5 W max)
Isolation, DC power
supply to input
common: >500 megohms
* Compliance: The sum of all
voltage drops in the output loop
cannot exceed 24 V at rated
current (1200 ohms @ 20 mA).
Specifications are subject to change without notice. ©2007 Wilkerson Instrument Co., Inc. DWG#W101041D 3/07
3 4

This manual suits for next models

1

Other Mighty Module Transmitter manuals

Mighty Module MM4431 User manual

Mighty Module

Mighty Module MM4431 User manual

Mighty Module MM4300A User manual

Mighty Module

Mighty Module MM4300A User manual

Mighty Module MM4130 User manual

Mighty Module

Mighty Module MM4130 User manual

Mighty Module MM6010 User manual

Mighty Module

Mighty Module MM6010 User manual

Mighty Module MM4410 User manual

Mighty Module

Mighty Module MM4410 User manual

Mighty Module MM4010 User manual

Mighty Module

Mighty Module MM4010 User manual

Mighty Module MM4001 User manual

Mighty Module

Mighty Module MM4001 User manual

Popular Transmitter manuals by other brands

logika WL-ZTPCNPB-I020-01 product manual

logika

logika WL-ZTPCNPB-I020-01 product manual

Sony WRT-822B Service manual

Sony

Sony WRT-822B Service manual

Siemens SITRANS F MASS 6000 Ex d operating instructions

Siemens

Siemens SITRANS F MASS 6000 Ex d operating instructions

Tigo TS4-A-F quick start guide

Tigo

Tigo TS4-A-F quick start guide

Vaisala PTU200 Series user guide

Vaisala

Vaisala PTU200 Series user guide

AYAMA SAHARA user manual

AYAMA

AYAMA SAHARA user manual

WisyCom MTP40 user manual

WisyCom

WisyCom MTP40 user manual

zisa ZS-TX1000 user guide

zisa

zisa ZS-TX1000 user guide

Altinex MT318-101 user guide

Altinex

Altinex MT318-101 user guide

Campbell ST21 Information

Campbell

Campbell ST21 Information

M-system CTS2 instruction manual

M-system

M-system CTS2 instruction manual

GE VT4930WDM Installation/operation instructions warranty information

GE

GE VT4930WDM Installation/operation instructions warranty information

Monacor JTS PT-920B/2 instruction manual

Monacor

Monacor JTS PT-920B/2 instruction manual

Endress+Hauser iTEMP TMT82 Brief operating instructions

Endress+Hauser

Endress+Hauser iTEMP TMT82 Brief operating instructions

Honeywell SLN 700 user manual

Honeywell

Honeywell SLN 700 user manual

Halemeier S-Mitter basic MultiWhite2 quick start guide

Halemeier

Halemeier S-Mitter basic MultiWhite2 quick start guide

Moore Inductries IPH2 user manual

Moore Inductries

Moore Inductries IPH2 user manual

Gelec PIT70000 User's & technical manual

Gelec

Gelec PIT70000 User's & technical manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.