
User’s Manual for ‘INDU-52’ v1.1
17.01.2006
4
3. Controller Operating Modes
The controller can run in the following modes:
START: in this mode the process control is carried out according to the measured
temperate and the preset START mode time is counted down. Output 1 (Re1) is
controlled according to measurements made in Channel 1 (Ch1). Similarly, Output
2 (Re2) is controlled with measurements made in Channel 2 (Ch2). When the
START mode is running the SET TIME LED is flashing and the time to the end of
the START mode counted down from the set value to zero is shown in the upper
display. After the set time is elapsed the controller is switched into the STOP
mode.
STOP: the end of the START mode is indicated by “STOP” appearing on the
upper display and by an audible signal. Press the STOP key to switch into the
STANDBY mode.
STANDBY: in this mode the controller is waiting for the next operation in the
START mode. The set START mode duration is displayed on the upper display.
The current temperature measurement is shown on the bottom display.
4. Process Parameter Changing
START MODE DURATION
The START mode duration setting (hours and minutes) is shown on the upper
display. Press the SET TIME key to change the time setpoint.. Both the parameter
being edited and the SET TIME LED flash. Press the SET TIME key once again to
confirm the setting and continue. Use the PLUS / MINUS keys to change the setting.
CHANNEL 1 TEMPERATURE SETPOINT
The temperature measurement made in Channel 1 is shown on the bottom display.
Press the SET TEMP key to display and change Channel 1 temperature setpoint.
Press the SET TEMP key once again to confirm the changes. Use the PLUS /
MINUS keys to change the setting.
MOTE:
Channel 2 temperature setpoint is available in F06 in the SETUP menu.