Mikster INDU WRC-2010H User manual

ver. 1.07
INDU WRC-2010H Controller
User’s Manual
Sp. z o.o.
41-250 Czeladź, ul. Wojkowicka 21
Tel. 0 32 763–77–77
Fax: 0 32 763–75–94
www.mikster.pl e-mail: [email protected]
v1.07 29.05.2008

INDU WRC-2010H Controller – User’s Manual ver. 1.07
- 2-
29.05.2008
TABLE OF CONTENTS
page
1.
STRUCTURE,
APPLICATIONS,
POTENTIAL.....................................................................................................4
2.
“INDU
WRC-2010H”
-
CONTROL
PANEL............................................................................................................4
3.
“INDU
WRC-2010H”
-
START
OF
OPERATION..................................................................................................6
4.
PROCESS
PROGRAMS......................................................................................................................................6
4.1. Manufacturing process programming............................................................................................................6
4.2. Execution of program stored in memory .......................................................................................................8
4.3. Program execution interruption .....................................................................................................................9
4.4. Automatic process activation.........................................................................................................................9
4.5. Editing of parameters set during controller operation..................................................................................11
5.
CONTROLLER
CONFIGURATION....................................................................................................................12
5.1. User’s functions...........................................................................................................................................13
5.1.1. Time and date setting ...........................................................................................................................13
5.1.2. Setting menu language.........................................................................................................................13
5.2. Service functions 1......................................................................................................................................15
5.2.1. Controller parameter setting .................................................................................................................15
5.2.2. Setting of step parameters....................................................................................................................20
5.2.3. Alarm setting.........................................................................................................................................22
5.2.4. Parameter setting for pause mode, stop mode and key functions F1..F4............................................26
5.2.5. I/O output parameter setting.................................................................................................................27
5.2.6. Washing parameter setting...................................................................................................................31
5.3. Service functions 2......................................................................................................................................31
5.3.1. Test for digital outputs...........................................................................................................................31
5.3.2. Key test.................................................................................................................................................32
5.3.3. Diode test..............................................................................................................................................32
5.4. Washing ......................................................................................................................................................33
5.4.1. Washing programming .........................................................................................................................33
5.4.2. Washing activation................................................................................................................................33
6.
ADDITIONAL
INFORMATION............................................................................................................................34
6.1. Display of additional measurements............................................................................................................34
7.
HOW
TO
CONNECT
THE
CONTROLLER
TO
PC
COMPUTER.......................................................................34
8.
TECHNICAL
DATA.............................................................................................................................................35
II
INDU
WRC
CPU-01
MODULE............................................................................................................................36
1.
MODULE
ASSEMBLING....................................................................................................................................36
2.
MODULE
FUNCTION.........................................................................................................................................36
3.
FIGURE..............................................................................................................................................................36
4.
TECHNICAL
DATA.............................................................................................................................................37
III.
INDU
WRC
AI-01/6
MODULE ...........................................................................................................................38
1.
MODULE
ASSEMBLING....................................................................................................................................38
2.
MODULE
FUNCTION.........................................................................................................................................38
3.
FIGURE..............................................................................................................................................................38
4.
TECHNICAL
DATA.............................................................................................................................................39
IV.
INDU
WRC
DI-01MODULE..............................................................................................................................40
1.
MODULE
ASSEMBLING....................................................................................................................................40
2.
MODULE
FUNCTIONS......................................................................................................................................40
3.
FIGURE..............................................................................................................................................................40
4.
TECHNICAL
DATA.............................................................................................................................................41

INDU WRC-2010H Controller – User’s Manual ver. 1.07
- 3-
29.05.2008
V.
INDU
WRC
RO-01
MODULE............................................................................................................................42
1.
MODULE
ASSEMBLING....................................................................................................................................42
2.
MODULE
FUNCTIONS......................................................................................................................................42
3.FIGURE...............................................................................................................................................................42
4.
TECHNICAL
DATA.............................................................................................................................................43
5.
C
ARDS ADDRESSING IN THE SYSTEM
:.....................................................................................................................43
VI.
INDU
WRC
TO-01
MODULE............................................................................................................................44
1.
MODULE
ASSEMBLING....................................................................................................................................44
2.
MODULE
FUNCTION.........................................................................................................................................44
3.
FIGURE..............................................................................................................................................................44
4.
TECHNICAL
DATA.............................................................................................................................................45
5.
C
ARDS ADDRESSING IN THE SYSTEM
:.....................................................................................................................45
VII.
INDU
WRC
COM-01
MODULE........................................................................................................................46
1.
MODULE
ASSEMBLING....................................................................................................................................46
2.
MODULE
FUNCTION.........................................................................................................................................46
3.
FIGURE..............................................................................................................................................................46
4.
TECHNICAL
DATA.............................................................................................................................................47
VIII.
INDU
WRC
PS-01
MODULE...........................................................................................................................48
1.
MODULE
ASSEMBLING....................................................................................................................................48
2.
MODULE
FUNCTION.........................................................................................................................................48
3.FIGURE...............................................................................................................................................................48
4.
TECHNICAL
DATA.............................................................................................................................................49

INDU WRC-2010H Controller – User’s Manual ver. 1.07
- 4-
29.05.2008
1. STRUCTURE, APPLICATIONS, POTENTIAL
The INDU WRC-2010H Controller is a unit designed to control those industrial processes, in which temperature is
the most important element, such as: smoke-chambers, brewing boilers, defrosting chambers, etc. Smoke-
chamber control is the main purpose, for which this controller has been built, and this is reflected in the type of data
being shown, controller operation procedure, etc. The controller consists of modules - users may fit their number
and type to their own needs. The main module is the “Control Panel”, indispensable in any controller, which allows
to:
-configure the whole controller
-set parameters controlling the process
-observe current measurements
Other modules, which may be added to the controller (in brackets: maximum number of modules of a given type):
-analog input module (2 modules – 12 input lines) – temperature measurements using the PT100
-digital input module (1 module – 11 input lines) – inputs signaling alarm, or additional external control signals
-relay output modules (6 modules – 32 output lines [1 module has 6 lines]) - relays to control executive
equipment
-communication module (1 module) – allows to communicate with the PC computer, and stores recordings of
process course parameters
-power supply module (1 module) – the controller power supply – indispensable
Modules may be put together in any configuration.
2. “INDU WRC-2010H” - CONTROL PANEL
All operations related to the controller activation, programming, etc., are executed through the control panel.
Keys on the control panel are arranged in the following keypads:
-numeric display keypad (1) – displays process preset parameters [green], and current measurements [red]
-graphic display (2) - displays all information related to the panel configuration and operation
-NUMERIC keys with FUNCTION keys (3) – allow to operate the controller
-diodes signaling OUTPUT EQUIPMENT STATUS (4) – show status of output relays
Process control is divided into stages referred to as process cycles, each process may consist of 30 cycles, and
each cycle is characterized by:
-currently executed process step
-preset chamber temperature
-preset bar temperature
-preset humidity
-preset cycle duration time
Process step is the information stored in the controller stating which outputs are to be active, and what is the
condition for particular cycle termination. 16 process steps may be stored in the INDU WRC-2010H memory.
Information regarding status of working controller, as process number and name, or process step number and
name, is shown on graphic display.

INDU WRC-2010H Controller – User’s Manual ver. 1.07
- 5-
29.05.2008
Fig. 1
The INDU WRC-2010H Controller “control panel”
1. Numeric
display keypad
2. Graphic
display
3. Numeric keys
with function
keys
4. Signaling
diodes

INDU WRC-2010H Controller – User’s Manual ver. 1.07
- 6-
29.05.2008
3. “INDU WRC-2010H” - START OF OPERATION
As soon as power is turned on, all numeric displays and diodes will light, and graphic display will show “WRC 2000
Init”. After some time displays and diodes will be switched off, which proves correct work of the system. The
controller will switch to stand-by mode. Graphic display will show request to enter operator’s number, and then
password. Before operators are entered, it is enough to press “Enter” key twice.
4. PROCESS PROGRAMS
4.1. Manufacturing process programming
Do the following in order to create a new program or edit an already existing one:
-press the “Configuration” key
-using arrows “left” - “right”, position the cursor so as to make the figure blink and to have the word
“Programowanie” [“Programming”] displayed
press the “Enter” key
-password will be requested
******
enter the code “003011” and press “Enter”
-program selection list will be displayed
-using arrows “up” - “down”, select the program you wish to enter or modify

INDU WRC-2010H Controller – User’s Manual ver. 1.07
- 7-
29.05.2008
-selected program blinks
-press “Enter” key to edit the program
-first enter program name
(enter letter in position by pressing key with selected letter as many times as required, move to next position by
pressing right arrow )
-press “Enter” key
-start process cycle editing
-enter the number of cycle you wish to edit and press “Enter”
-select step number to be executed during the cycle
1
(using arrows “up” - “down”), and press “Enter”
-enter the cycle duration,
first hours, press “Enter” , then minutes, and press “Enter” again
-enter preset chamber temperature
1
and press “Enter”

INDU WRC-2010H Controller – User’s Manual ver. 1.07
- 8-
29.05.2008
-enter preset bar temperature
1
and press “Enter”
-enter preset humidity
1
and press “Enter”
-shift between data you are entering with arrows
-this ends editing of a single process; if you wish to edit another cycle, enter its number and then proceed as
before, whereas if all cycles in a given program have been edited, then press “Stop” key
-thus you have completed program editing, now you can select another program for editing, or:
-press “Stop” key and thus end manufacturing process programming
4.2. Execution of program stored in memory
Do the following in order to execute any program previously saved in the controller memory:
-press “Start” key
-select the process using arrows “up” - “down”
to be executed and press “Enter”

INDU WRC-2010H Controller – User’s Manual ver. 1.07
- 9-
29.05.2008
-enter product identification data by using numeric keys and arrows
1
4
7
0
2
5
8
3
6
9
-
-press “Start” key again
4.3. Program execution interruption
We are able to interrupt program execution any time without possibility to resume it; in order to do that press “Stop”
key .
It is also possible to interrupt currently executed program, and then return to its execution; follow the procedure
below to do that:
-press ”Pause” key
-the controller will interrupt program execution and diode at ”Pause” key will go on
-the program will be resumed when ”Pause” key is pressed again, or when pause time passes (value set
during controller configuration, which is described later in this Manual).
4.4. Automatic process activation
The INDU WRC-2010H Controller allows to activate a program at any previously set hour. Follow the procedure
below to allow for automatic activation of the controller:
-press “Clock” key
-select program, which is to be activated
and press “Enter”
-enter process start hour

INDU WRC-2010H Controller – User’s Manual ver. 1.07
- 10-
29.05.2008
-enter process start date (current date is prompted by default)
-press “Start”
-graphic display will show program name, date and program activation time, as well as current date and time,
the lamp at “Clock” key will go on
At specified hour the controller will automatically start execution of appropriate program from the first step. While
the controller waits for process start, it is impossible to introduce any modification of settings.
You may cancel automatic process start by pressing “Stop” key .

INDU WRC-2010H Controller – User’s Manual ver. 1.07
- 11-
29.05.2008
4.5. Editing of parameters set during controller operation
It is possible to correct previously set parameters while the controller executes a program. Follow the procedure
below (during program execution) to do that:
-press “Configuration” key
-using arrows “up” - “down”, select parameter that you wish to change (selected parameter blinks)
-enter the new value using numeric keys
1
4
7
0
2
5
8
3
6
9
-
and confirm with “Enter” key
-if it is necessary, modify next parameters
-press “Start” key after having introduced all changes
ATTENTION !!!
Alterations introduced during controller operation are valid only until the end of manufacturing
process. After closing the program, the controller “remembers” program with data set during the
programming process.
During the program data edition the time count as well as the control of
condition of the cycle end – are stopped. The controller automatically returns to the normal mode of
operation if no key was pressed for one minute.

INDU WRC-2010H Controller – User’s Manual ver. 1.07
- 12-
29.05.2008
5. CONTROLLER CONFIGURATION
The controller possesses very highly developed configuration functions, which allow to adjust its parameters and
way of working to user’s individual needs. Suitable settings entered through the configuration menu are stored in
the controller memory and used during its work.
Controller configuration has been divided into the following functions:
-user’s functions
-service functions 1
-service functions 2
-access control
Follow the procedure below to start editing selected functions:
-press “Configuration” key
-using arrows “left” - “right”, select functions you wish to edit
-press “Enter” key
-you will see on screen request to enter password for access to selected functions
******
-enter right code and press “Enter”

INDU WRC-2010H Controller – User’s Manual ver. 1.07
- 13-
29.05.2008
5.1. User’s functions
These functions allow to set the following:
-time and date
-menu language
-so far other functions are inactive
5.1.1. Time and date setting
Follow the procedure below to set time and date:
-select function “Set clock”
-press “Enter”
enter time and then date using numeric keys
-as soon as you enter each item, press “Enter”
-press “Stop” key after entering all items
5.1.2. Setting menu language
Follow the procedure below to set language:
-select function “Language”

INDU WRC-2010H Controller – User’s Manual ver. 1.07
- 14-
29.05.2008
-press “Enter”
-select one of 4 languages using arrow keys “left” - “right”
press “Enter”
4 languages are available:
-Polish
-English
-two languages defined by user and transferred to the controller via PC computer – instruction how to do this is
enclosed to the program for PC.

INDU WRC-2010H Controller – User’s Manual ver. 1.07
- 15-
29.05.2008
5.2. Service functions 1
In these functions it is possible to set the following:
-controller parameters
-step parameters
-alarms
-STOP and PAUSE mode parameters, and parameters of key functions F1..F4
-I/O output parameters
-washing parameters
5.2.1. Controller parameter setting
Follow the procedure below to set controller parameters:
-select function “Controller parameters”
-press “Enter”
Now begin editing controller parameters (parameters are stored in cells numbered from F01):
-select cell, which you wish to set using arrow keys “up” - “down”
-press “Enter”
-enter proper value for a given cell
-press “Enter”

INDU WRC-2010H Controller – User’s Manual ver. 1.07
- 16-
29.05.2008
Repeat the procedure shown before until required values are set in each cell. The table below shows the meaning
of individual cells:
CELL
NO. CELL NAME FACTORY-SET
VALUE RANGE DESCRIPTION
F 01 ADDRESS FOR PC 1 1..32 Number in the RS - 485 network, by which
the PC computer recognizes the controller
F 02 V.tr. TO PC 0 0..1 Baud rate RS - 485 – connection with PC: 0
- 9600, 1 – 19200
F 03 MENU INFO 0 0..11 Menu INFO configuration
Display after button INFO press:
0 – 3 temperatures,
1 – channel 3,
2 – channelł 4,
3 – channel 5,
4 – channel 6,
5 – channel 7,
6 – channel 8,
7 – channel 9,
8 – channel 10,
9 – channel 11,
10 – channel 12,
11 – counter
F 04 END COND.TIME 1 0..99 Additional time to process end
F 05 NOT USED 0 0..2 0 - pause from button
1 - pause from program settings (work time
pause time). Cycle time stopped during
pause
2 - pause from program settings (work time
pause time). Cycle time running during
pause
F 06 NOT USED
F 07 TEMP. UNIT 0 0..1 Temperature measurement unit
0 –
0
C
1 –
0
F
F 08 ‘PLATE’ TEMP. 380 -99..999 Smoke temperature
F 09 ‘SMOKE’ TEMP. 250 -99..999 Smoke-generator plate temperature

INDU WRC-2010H Controller – User’s Manual ver. 1.07
- 17-
29.05.2008
F 10 DELTA STATUS 0 0..2 0 - "delta" OFF, 1 - delta bar-chamber,
2 - "delta" temperature rise in time
F 11 REC. FREQ. 1 0..99 Recording frequency
F 12 TIME FOR RESTART 40 0..200
F 13 MAX. SET CHAMBER
TEMP. 200 -99..999 Maximum preset chamber temperature
F 14 MAX. SET BAR TEMP. 200 -99..999 Maximum preset bar temperature
F 15 HUMIDITY
MEASUREMENT TYPE 0 0..1 Moisture measurement type:
0 – psychrometric method
1 – with current detector 4...20 mA
F 16 TIME TO WASHING 40 0..999 Allowable number of hours between
washing processes
F 17 START FROM PC 0 0..1 Process activation from computer
0 – off
1 – on
F 18 ID ON/OFF 0 0..1 Process ID
0 – off
1 – on
F 19 OPERATOR ON/OFF 0 0..1 Operator logging in
0 – off
1 – on
F 20 KEY ”CLICK” 2 0..20 Sound level after pressing the 0 key - audio
signaling off
F 21 MAX.CHAMBER TEMP. 100 -99..999 Maximum allowable chamber temperature
F 22 MAX.BAR TEMP. 90 -99..999 Maximum allowable bar temperature
F 23 MAX.PLATE TEMP. 800 -99..999 Maximum allowable smoke temperature
F 24 MAX.SMOKE TEMP. 800 -99..999 Maximum allowable smoke-generator plate
temperature
F 25 MAX. HUMIDITY1 99 0..99 Maximum allowable moisture
F 26 TCH-OFFSET (D) 0 -200..200 Chamber temperature correction value –
dry sensor
F 27 TCH-OFFSET (W) 0 -200..200 Chamber temperature correction value –
wet sensor
F 28 TCO- OFFSET 0 -200..200 Bar temperature correction value
F 29 TPL- OFFSET 0 -200..200 Smoke temperature correction value
F 30 TSM- OFFSET 0 -200..200 Smoke-generator plate temperature
correction value
F 31 HUMIDITY OFFSET 0 0..99 Humidity correction value

INDU WRC-2010H Controller – User’s Manual ver. 1.07
- 18-
29.05.2008
F 32 TYPE OF DIGIT.INPUT 0 0..1 Type of voltage delivered to control inputs:
0 – constant voltage
1 – variable voltage
F 33 STAT. REL.FOR END 0 0..1 Type of input signal for cycle termination
condition:
0 – input signal from control input
1 - input signal from relay output
F 34 REL. NO. FOR END 1 1..32 Number of control input or relay for cycle
termination condition
F 35
MIN. CHAMB. SET T
0 -99..999 Minimum temperature set for chamber
F 36
MIN CORE SET T
0 -99..999 Minimum core set
F 37
MIN HUMIDITY SET
0 -99..999 Minimum humidity set
F 38
MAX HUMIDITY SET
0 -99..999 Maximum humidity set
F 39
MIN ADDITION1 SET
0
-199..999
Minimum addition set 1
F 40
MAX ADDITION1 SET
0
-199..999
Maximum addition set 1
F 41
MIN ADDITION2 SET
0
-199..999
Minimum addition set 2
F 42
MAX ADDITION2 SET
0
-199..999
Maximum addition set 2
F43 RELAY S.G. ON 0 1..32 Number of smoking relay – the relay for
time count in between consecutive
washings of the chamber
F44 CH6 REG. SET. 0 -99..99 Set value for channel 6
F45 CH7 REG. SET. 0 -200..200 Set value for channel 7
F46 CH8 REG. SET. 0 -200..200 Set value for channel 8
F47 CH9 REG. SET. 0 -200..200 Set value for channel 9
F48 CH10 REG. SET. 0 -200..200 Set value for channel 10
F49 CH11 REG. SET. 0 -200..200 Set value for channel 11
F50 CH12 REG. SET.
0 -200..400 CH12 REG SET
F51
CH6 OFFSET
0 -200..200 Set value for channel 6
F52
CH7 OFFSET
0 -200..200 Set value for channel 7
F53
CH8 OFFSET
0 -200..200 Set value for channel 8
F54
CH9 OFFSET
0 -200..200 Set value for channel 9
F55
CH10 OFFSET
0 -200..200 Set value for channel 10
F56
CH11 OFFSET
0 -200..200 Set value for channel 11
F57
CH12 OFFSET
0 -200..200 Set value for channel 12
F58
DISPLAY TIME TYPE
0 0..1 Display time type
F59
MAN. MODE
0 0..1 Manual work

INDU WRC-2010H Controller – User’s Manual ver. 1.07
- 19-
29.05.2008
F60 ADDITIONAL SET 0 0..1 Additional set1 and additional set2 during
program editing
F61 NOT USED
F62 NOT USED
F63 NOT USED
F64 MAX CARD ERROR 1 0..9 Maximum card error
F65 WEITHT TAR. 0 0..3 0-tare off
1-tare on F4 pressed
2-automatic tare on start every step
3- automatic tare on start every step or F4
pressed
F66 COUNTER TAR. 0 0..5 0- tare off
1- tare on F4 pressed
2- automatic tare on start every step
3- automatic tare on start every step or F4
pressed
4- tare on F3 pressed
5- automatic tare on start every step or F3
pressed
F67 VACUM IMPULSE TIME
(s) 0 Value set for INDU WRC 200
F68 VACUM IMPULSE
DELAY 0 Value set for INDU WRC 200
F69 COUNTER CONST. 0 0…9999 Counter constans
- regulator devider for impulses counter
F70 LOOP PROG STEPS. 0 -1..200 -1 program loop
0 i 1-program executing once
2 do 200 – program loop set

INDU WRC-2010H Controller – User’s Manual ver. 1.07
- 20-
29.05.2008
5.2.2. Setting of step parameters
Each process controlled by INDU WRC-2010H consists of steps executed in a sequence. The controller may store
settings for 16 steps. Define the following elements for each step:
- name
- relay status
- step termination condition
Follow the procedure below in order to set these parameters:
- select function “Step parameters”
- press “Enter”
- the list of all steps will be displayed,
2
select step that you wish to edit and press “Enter”
- enter name – same as at programming, and press “Enter”
- select function “Relay status”
and press “Enter”
- symbols indicating individual relays are displayed
(the symbol informs that in a given step the relay will be on, whereas the symbol informs that the relay will
be off), do the following in order to alter relay status:
- move the arrows “left” - “right” so as to have digit indicating selected relay blink
Table of contents
Other Mikster Controllers manuals
Popular Controllers manuals by other brands

Danfoss
Danfoss FC 300 Operating instruction

MicroImage Video Systems
MicroImage Video Systems PX101EX Operation manual

ACS contsys
ACS contsys MIR-491 operating instructions

Philips
Philips 9290 014 61062 installation guide

SLV
SLV 470810 Quick installation guide

Baier
Baier PROMETHEUS Series instruction manual

Photonic Universe
Photonic Universe AN Series user manual

EasyIO
EasyIO FT Series User reference

S&C
S&C BankGuard PLUS Troubleshooting instructions

Amtrol
Amtrol GUARDIAN CP DC2 Installation and operation manual

Baldor
Baldor VS1GV21-1B Installation & operating manual

TATA Motors
TATA Motors Aquatermic Operation manual