CATALOG NUMBER
Description
The System Sensor CO1224T and CO1224TR
(round) Carbon Monoxide (CO) Detectors use a highly
accurate and reliable electrochemical sensing cell to
provide early warning of dangerous CO levels.
With RealTest®technology, the CO gas sensing cell
used in the CO1224T and CO1224TR CO detectors
can be tested using a CO gas agent, fully meeting
the requirements of NFPA 720: 2009. Simply put the
detector into RealTest mode, spray a small amount of
CO into the detector per the installation instructions,
and within seconds the detector will alarm, indicating
successful gas entry. (See the reverse page or the user
manual for complete instructions.)
When dangerous amounts of CO are detected, the
CO1224T and CO1224TR detectors alert residents by
sounding and ashing a temp 4 signal alarm. With 24/7
central station monitoring, residents are guaranteed
protection whether they are away from home, sleeping,
or already suffering from the effects of CO.
The CO1224T and CO1224TR are designed for system
operation. These detectors are fully listed to UL 2075
and offer a code-required trouble relay to send a sensor
failure or end-of-life signal to the control panel and the
central station. The CO1224T and CO1224TR also use
SEMS-type terminal Philips head screws for quicker and
more positive wiring connections and code-required
wiring supervision.
Features
RealTest• ® enables a functional test using canned
CO
Full compliance with UL 2075•
A code-required trouble relay•
Wiring supervision with SEMS terminals•
A six-year end-of-life timer•
12/24 VDC•
A low current draw of 20 mA in standby and 40 •
mA in alarm
Versatile mounting for wall and ceiling•
Accurate and reliable electrochemical sensing •
technology
Optional CO-PLATE CO Detector Replacement •
Plate to upgrade previously installed competitor
detectors to the CO1224T
With a low current draw, these detectors enable more
devices to be connected to the panel, limiting the need
to purchase extra power supplies or more expensive
panels. As 12/24 VDC detectors, the CO1224T and
CO1224TR will operate on most industry security and
re alarm control panels.
Architectural/Engineering Specications
Carbon monoxide detector shall be a System Sensor
model number CO1224T or CO1224TR listed to
Underwriters Laboratories UL 2075 for Gas and Vapor
Detectors and Sensors. The detector shall be equipped
with a sounder and a trouble relay. The detector’s base
shall be able to mount to a single-gang electrical box
or direct (surface) mount to the wall or ceiling. Wiring
connections shall be made by means of SEMS screws.
The detector shall provide dual color LED indication
that blinks to indicate normal standby, alarm, or end-
of-life. When the sensor supervision is in a trouble
condition, the detector shall send a trouble signal to
the panel. When the detector gives a trouble or end-of-
life signal, the detector shall be replaced. The detector
shall provide a means to test CO gas entry into the
CO sensing cell. The detector shall provide this with a
test mode that accepts CO gas from a test agent and
alarms immediately upon sensing CO entry.

Canada
25 Interchange Way
Vaughan, Ontario L4K 5W3
Telephone: (905) 660-4655
Fax: (905) 660-4113
Web page: http://www.mircom.com Email: [email protected]
Distributed by:
CAT. 5172
Rev. 3
NOT TO BE USED FOR INSTALLATION PURPOSES.
U.S.A.
4575 Witmer Industrial Estates
Niagara Falls, NY 14305
Toll Free: (888) 660-4655
Fax Toll Free: (888) 660-4113
Operation Mode Green LED Red LED Sounder
Normal (standby) Blink 1 per minute — —
Alarm — Blink in temp 4 pattern Sound in temp 4 pattern
Operation Modes
RealTest®Feature: The System Sensor CO1224T and CO1224TR Carbon Monoxide Detectors with RealTest enable evaluation of
the functionality of the CO sensing cell using a canned CO test agent.
Push and hold the Test/Hush button
for two seconds to enter RealTest
mode. The green LED will ash once
every second to indicate RealTest
mode has started.
Spray canned CO agent into the
detector.
Verify CO sensing at the control
panel. The detector will automatically
exit RealTest alarm mode after
about 20-60 seconds.
NOTE: Check with local codes and the AHJ to determine whether or not a functional gas test is desired for an installation.
Hush Feature: Pushing the Test/Hush button will silence the sounder for 5 minutes (except in RealTest mode).
Trouble Feature: When the detector is in a trouble condition, it will send a trouble signal to the panel.
End-of-life Timer: After the detector’s internal sensor has reached the end of its life, a trouble
signal will be sent to the panel. This will indicate that it is time to replace
the detector. An electrochemical carbon monoxide detector lifespan is
approximately six years, and the detector must be replaced by the date
marked on the inside of the product.
CO-PLATE: System Sensor also offers the CO-PLATE CO Detector Replacement Plate
to cover the footprint (when necessary) of previously installed competitive
carbon monoxide detectors that require replacement. CO-PLATE
Electrical Specications
Operating Voltage 12/24 VDC
Audible Signal 85 dB in alarm
Standby Current 20 mA
Alarm Current 40 mA (75 mA test)
Alarm Contact Ratings 0.5 A @ 30 VDC
Trouble Contact Ratings 0.5 A @ 30 VDC
Physical Specications
Size CO1224T Length: 5.1˝, Width: 3.3˝, Height: 1.3˝
CO1224TR Diameter: 6”, Height: 1.3”
Approximate Weight CO1224T: 7 oz; CO1224TR: 11 oz
Operating Temperature Range 32° – 104° F (0° – 40° C)
Operating Humidity Range 22 – 90% RH
Input Terminals 14 – 22 AWG
Mounting Single-gang back box; surface mount to wall or ceiling
Model Description
CO1224T 12/24 volt, 4-wire system-monitored carbon monoxide detector with RealTest®Technology
CO1224TR 12/24 volt, 4-wire system-monitored round carbon monoxide detector with RealTest®Technology
CO-PLATE CO detector replacement plate to cover the footprint of previously installed competitive detectors as necessary
Ordering Information
This manual suits for next models
2
Table of contents
Popular Gas Detector manuals by other brands

Brunner
Brunner 3-SICUR Instructions for use

Geotechnics
Geotechnics MultiRAE Plus quick start guide

Gas Detection
Gas Detection GDA 3000 operating manual

United Electric Controls
United Electric Controls Vanguard Installation and maintenance instructions

Cosmos
Cosmos XA-440011 instruction manual

WatchGas
WatchGas UNI Sustainable user manual

Medem
Medem AGDS-2em installation instructions

RKI Instruments
RKI Instruments GD-70D-O3 operating manual

S&S Northern
S&S Northern MERLIN GDPX+ Installation & operation manual

Electronics Line
Electronics Line EL-4762 introduction

LinkAYL
LinkAYL LK-GA502 user guide

Emerson
Emerson Net Safety MLP-A-SC1100 user manual