MEES19K180
PURY-HP-T(S)NU-A, Y(S)NU-A
5
1. SPECIFICATIONS Hyper Heating Inverter R2-Series
Outdoor Model PURY-HP144TSNU-A
Indoor Model Non-Ducted Ducted
Power source 3-phase 3-wire 208-230 V ±10% 60 Hz
Cooling capacity *1 BTU/h 144,000
(Nominal) kW 42.2
Power input kW 11.92
(208-230) Current input A 36.7-33.2
(Rated) BTU/h 138,000
kW 40.4
Power input kW 10.73 11.34
(208-230) Current input A 33.0-29.9 34.9-31.6
Temp. range of Indoor W.B. 59~75°F (15~24°C)
cooling Outdoor D.B. 23~126°F (-5~52°C)
Heating capacity *2 BTU/h 160,000
(Nominal) kW 46.9
Power input kW 12.50
(208-230) Current input A 38.5-34.8
(Rated) BTU/h 152,000
kW 44.5
Power input kW 11.22 11.91
(208-230) Current input A 34.6-31.2 36.7-33.2
Temp. range of Indoor D.B. 59~81°F (15~27°C)
heating Outdoor W.B. -22~60°F (-30~15.5°C)
Indoor unit Total capacity 50~150% of outdoor unit capacity
connectable Model/Quantity P04~P96/1~36
Sound pressure level (measured in anechoic room) *3 dB <A> 59.5/61.0
Sound power level (measured in anechoic room) *3 dB <A> 78.5/80.0
Refrigerant High pressure in. (mm) 7/8 (22.2) Brazed
piping diameter Low pressure in. (mm) 1-1/8 (28.58) Brazed
Set Model
Model PURY-HP72TNU-A PURY-HP72TNU-A
Minimum Circuit Ampacity A 38-35 38-35
Maximum Overcurrent Protection A 60-50 60-50
FAN Type x Quantity Propeller fan x 2 Propeller fan x 2
Airflow rate cfm 7,400 7,400
m3/min 210 210
L/s 3,500 3,500
Control, Driving mechanism Inverter-control, Brushless DC motor Inverter-control, Brushless DC motor
Motor output kW 0.46+0.46 0.46+0.46
*4 External static press. 0 in.WG (0 Pa) 0 in.WG (0 Pa)
Compressor Type x Quantity Inverter scroll hermetic compressor x 1 Inverter scroll hermetic compressor x 1
Manufacture AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter Inverter
Motor output kW 4.0 4.0
Case heater kW - -
Lubricant MEL46 MEL46
External finish Pre-coated galvanized steel sheet Pre-coated galvanized steel sheet
<MUNSELL 5Y 8/1> <MUNSELL 5Y 8/1>
External dimension H x W x D in. 71-5/8 x 49-1/4 x 29-3/8 71-5/8 x 49-1/4 x 29-3/8
mm 1,818 x 1,250 x 745 1,818 x 1,250 x 745
Protection High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601
psi)
High pressure sensor, High pressure switch at 4.15 MPa (601
psi)
devices Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Fan motor - -
Refrigerant Type x original charge R410A x 17 lbs + 10 oz (8.0 kg) R410A x 17 lbs + 10 oz (8.0 kg)
Control Indoor LEV and BC controller
Net weight lbs (kg) 609 (276) 609 (276)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) - -
Pipe between unit and High pressure in. (mm) 5/8 (15.88) Brazed 5/8 (15.88) Brazed
distributor Low pressure in. (mm) 3/4 (19.05) Brazed 3/4 (19.05) Brazed
Defrosting method Auto-defrost mode (Reversed refrigerant cycle)
Drawing External KB94C0GZ
Wiring KE94G811 KE94G811
Standard Document Installation Manual
attachment Accessory Details refer to External Drw
Optional parts Outdoor Twinning kit: CMY-R100NCBK
joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-R160-J1,CMY-R201,202,203,204,306S-G,CMY-R302,303,304,305S-G1
Main BC controller: CMB-P108,1012,1016NU-JA1,CMB-P1016NU-KA1
Sub BC controller: CMB-P104,108NU-KB1
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Notes: Unit converter
1.Nominal cooling conditions (Test conditions are based on AHRI 1230)
Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)
2.Nominal heating conditions (Test conditions are based on AHRI 1230)
Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
3.Cooling mode/Heating mode
4.External static pressure option is available (0.12 in.WG, 0.24 in.WG, 0.32 in.WG/30 Pa, 60 Pa, 80 Pa).
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg/0.4536
*Above specification data is
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
0000005744.BOOK 5 ページ 2020年2月25日 火曜日 午後5時19分