The AI controller measures temperature and humidity; it also has an alarm capability if the measurement data exceeds
defined setpoints. Historical measurement data can be displayed via only the EB-50GU Web browser, AG-150A LCD/
Web browser, GB-50ADA Web browser, or G(B)-50A Web browser and TG-2000A. Temperature and humidity cannot be
displayed on the G-50A LCD.
Furthermore, an alarm can be output if measurement data exceeds a preset upper or lower limit.
The AI controller also features a function that interlocks M-NET devices for indoor units, etc. set in advance and performs
settings such as temperature control and operation/stoppage using measurement data values.
• The following parts should be included in your shipment:
* In addition to the parts listed above, see your local Mitsubishi Electric dealer to purchase the other parts necessary to operate this device (Refer to
section 6-1). Furthermore, depending on the application, other Mitsubishi Electric parts may be required.
For details, refer to "6. Installation".
4-1. Device Specifications
*1: Supply electric power from a power supply unit for the transmission line or an outdoor unit. Furthermore, the power consumption factor of the M-
NET circuitry of this unit is "1/4" (equivalent to one ME Remote Controller).
*2: Configure the dip switch settings for the analog input method to use while referring to "9. Dip Switch Functions".
*3: The measurement error for the system includes the measurement error for this unit, sensor, and wiring.
a%FS (full scale) = a% × ([measurement range's upper limit value] - [lower limit value])
*4: Settings for the interlock function are performed from the Maintenance Tool. For details, refer to the operation manual for the Maintenance Tool.
(Consult the maintenance provider or dealer for how to set the interlock settings.)
*5: M3 and M3.5 are sizes of the screw on the terminal block (ISO metric screw thread). The number indicates the screw diameter (mm).
2Usage
Caution: Usage Restrictions
• Mitsubishi Electric does not take financial responsibility for damages caused by issues beyond our control or special
circumstances (predicable or unpredictable); and secondary or accidental damages, and damages to other objects. We also
do not take financial responsibility for opportunities lost as a result of device failure, or electrical power failure at the end-
user site.
Mitsubishi Electric does not take financial responsibility caused by end-users' requests including, but not limited to, device
testing, startup, readjustment and replacement.
• Do not use this device in disaster prevention security or "critical to life" applications.
3Parts List
Number Part Name Quantity
1 AI controller 1
2 Installation/instruction manual (this document) 1
4Specifications
Item Description
Power
Supply 24 VDC±10%: 5 W Screw terminal
block (M3) (*5)
Interface
M-NET communication 17 to 30 VDC (*1) Screw terminal
block (M3) (*5)
Input
Ch Sensor Measurement
target
Measurement
range Measurement error External
connection method
Ch1
Pt100
(3-wire system) Temperature -30 to 60°C
[-22 to 140°F]
±0.3%FS ±0.1°C (0.18°F)
(*3)
[at 25°C (77°F)]
Screwless terminal
block (3 poles)
Analog
4 to 20 mADC
Temperature/
humidity
(Set by system
controller)
±0.5%FS ±0.1°C (0.18°F)
(*3)
±0.5%FS ±0.1%RH
[at 25°C (77°F)]
Screwless terminal
block (2 poles)
1 to 5 VDC
0 to 10 VDC
Ch2
Analog
4 to 20 mADC
Temperature/
humidity
(Set by system
controller)
±0.5%FS ±0.1°C (0.18°F)
(*3)
±0.5%FS ±0.1%RH
[at 25°C (77°F)]
Screwless terminal
block (2 poles)
1 to 5 VDC
(*2) 0 to 10 VDC
Output
Upper/lower limit
alarm interlock output
(non-voltage contact)
Applied load
MAX: 24 VDC, 5 W
MIN: 5 VDC, 2 mW
* AC loads cannot be connected.
Screw terminal
block (M3.5) (*5)
Interlock
Function
Interlock M-NET devices according to measurement data values. (*4)
Environment
Conditions
Temperature Operating temperature range 0 to 40°C [32°F to 104°F]
Storage temperature range -20 to 60°C [-4°F to 140°F]
Humidity 30 to 90%RH (no condensation)
Dimensions 200 (W) × 120 (H) × 45 (D) mm / 77/8(W) × 43/4(H) × 125/32 (D) in
Weight 0.6 kg / 13/8lb
Time Backup
During Power
Failure
In the event of power failure or shut-off, the internal capacitor will continue to track time for approximately one week.
(The internal capacitor takes about 24 hours to fully charge; a replacement battery is not necessary.)
Installation
Environment
Inside the metal control panel (indoors)