– 2 –
2. Product features
The controller described in this manual is a centralized controller that can be operated over the Web.
Air conditioning units connected to this controller can be operated or monitored directly from this controller or over the
Web, using a browser software on the computer.
Refer to the Web browser operation manual (separate volume) for how to use the Web functions.
Function Description
Number of
control unit
Indoor unit or independent OA
processing unit or LOSSNAY Up to 50 units are connectable (including the interlocked units) *2
Number of units
(indoor or independent OA
processing unit or LOSSNAY)
1-16 units (Indoor unit, independent OA processing unit and LOSSNAY can not
register to the same group.)
Number of remote controllers in
one group 1-2
Number of system controllers in
one group 0-4 (including the number of remote controller in one group)
Number of interlocked units
• Number of LOSSNAY units (interlocked unit) that can be interlocked with an
indoor unit (interlocking unit): 1
• Number of indoor units (interlocking unit) that can be interlocked with a
LOSSNAY unit (interlocked unit): 16
User Operations Function
Operation
*1
ON/OFF The ON/OFF operation can be performed as a collective or per group or per block.
Operation mode
The switch operation for the operation mode setting can be performed as a
collective or per group or per block. (Available modes depend on the model.)
[Selectable operation mode for the indoor unit]
COOL/DRY/FAN/AUTO/HEAT
[Selectable operation mode for the independent ventilation]
HEAT RECOVERY/BY-PASS/AUTO
[Selectable operation mode for Hot water supply equipment]
HEATING/HEATING ECO/HOT WATER/ANTI-FREEZE/COOLING
Fan speed
Up to four fan speeds are available, and the fan speed can be changed collectively,
or for each group or block of indoor units. (The number of available fan speeds
depends on the model (2 speeds, 3 speeds, 4 speeds, and Auto). “Auto” is available
only on the models that support that function.)
Temperature setting
Temperature setting can be performed collectively or per group or per block.
[Setting temperature range for air conditioner]
Cool (Dry) operation: 19 ~ 30°C / 67 ~ 87°F
Heat operation: 17 ~ 28°C / 63 ~ 83°F
Auto operation: 19 ~ 28°C / 67 ~ 83°F
[Setting temperature range for Hot water supply equipment]
Heating: 30 ~ 45°C
Heating ECO: 30 ~ 45°C
Hot Water: 30 ~ 70°C
Anti-freeze: 10 ~ 45°C
Cooling: 10 ~ 30°C
Air direction and swing
operation
Vertical air flow directions (5 directions), auto setting, and swing setting can be
changed collectively, or for each group or block of indoor units. (Available air flow
directions depend on the model. [5 air flow directions and AUTO] are available only
on the models that support those settings.
Operating/stopping the
interlocked LOSSNAY units
Interlocked LOSSNAY units (if any) can be operated (at High or Low) or stopped
collectively or for each group or block of indoor units. (Ventilation mode cannot be
selected for the interlocked LOSSNAY units.)
Schedule
Daily, weekly, or annual scheduling of groups or blocks of units is available.
• Twenty-four patterns of operation schedule can be set per day.
• Two types of weekly schedule are available. Starting/ending dates for each
season can be set.
• Five types of operation patterns (P1-P5) are available per year. Up to 50 dates can
be assigned to each pattern.
• Temperature setting, fan speed setting, airflow direction, can be changed and set
back operation can be performed according to the timer setting.
Prohibit local remote control
Operation of certain functions from the local remote controllers can be prohibited
collectively or for each group or blocks of indoor units.
(Applicable functions: ON/OFF, operation mode, temperature setting, filter sign)
Filter sign reset Filter sign can be reset for each group or block of indoor units.
Error reset Resets the display of error.
Error history reset Resets the error history (unit error, communication error).
External input
Connects to an external input/output device that stops the units in an emergency,
run or stop the units, permit or prohibit the operation of units collectively. Requires
an external input/output adapter (sold separately).