Mitsubishi MELSEC-Q Q64TCTT User manual

Temperature Control Module
MITSUBISHI
General-Purpose PROGRAMMABLE LOGIC CONTROLLER
User’s Manual
(Hardware)
Q64TCTT
Q64TCTTBW
Thank you for purchasing the Mitsubishi general-purpose
programmable logic controller MELSEC-Q series.
Prior to use, please read this manual thoroughly and
familiarize yourself with the product
MODEL Q64TCTT-U-H-JE
MODEL
CODE 13JQ97
IB(NA)-0800120-B(0603)MEE
© 2000 MITSUBISHI ELECTRIC CORPORATION

A - 1
SAFETY PRECAUTIONS
(Read these precautions before using.)
When using Mitsubishi equipment, thoroughly read this manual and the
associated manuals introduced in this manual. Also pay careful attention to
safety and handle the module properly.
These SAFETY PRECAUTIONS classify the safety precautions into two
categories: “DANGER” and “CAUTION”.
DANGER
CAUTION
Procedures which may lead to a dangerous condition and
cause death or serious injury, if not carried out properly.
Procedures which may lead to a dangerous condition and
cause superficial to medium injury, or physical damage
only, if not carried out properly.
Depending on circumstances, procedures indicated by CAUTION may also
be linked to serious results.
In any case, it is important to follow the directions for usage.
Store this manual in a safe place so that you can take it out and read it
whenever necessary. Always forward it to the end user.
[DESIGN PRECAUTIONS]
DANGER
Do not write data to the "read-only area" in the buffer memory of the
intelligent function module.
Do not turn on/off the "reserved" signals among the I/O signals to/from the
PLC CPU.
Doing so can malfunction the PLC system.
Depending on the malfunction of the external output transistor, there may
be cases where the output is ON or OFF status. Install external monitoring
circuitry for output signals that may lead to major accidents.
CAUTION
Do not bunch the control wires or communication cables with the main
circuit or power wires, or install them close to each other.
They should be installed 100 mm(3.94 inch) or more from each other.
Not doing so could result in noise that may cause malfunction.

A - 2
[INSTALLATION PRECAUTIONS]
CAUTION
Use the PLC in an environment that meets the general specifications
contained in the CPU user's manual.
Using this PLC in an environment outside the range of the general
specifications may cause electric shock, fire, malfunction, and damage to
or deterioration of the product.
When installing the module, securely insert the module fixing tabs into the
mounting holes of the base module while pressing the installation lever
located at the bottom of the module downward.
Improper installation may result in malfunction, breakdown or the module
coming loose and dropping. Securely fix the module with screws if it is
subject to vibration during use.
Tighten the screws within the range of specified torque.
If the screws are loose, it may cause the module to fallout, short circuits, or
malfunction.
If the screws are tightened too much, it may cause damage to the screw
and/or the module, resulting in fallout, short circuits or malfunction.
Switch all phases of the external power supply off when mounting or
removing the module.
Not ding so may cause electric shock or damage to the module.
Do not directly touch the conductive area or electronic components of the
module.
Doing so may cause malfunction or failure in the module.
[WIRING PRECAUTIONS]
CAUTION
Be careful not to let foreign matters such as sawdust or wire chips get
inside the module.
They may cause fires, failure or malfunction.
The top surface of the module is covered with protective film to prevent
foreign objects such as cable offcuts from entering the module when wiring.
Do not remove this film until the wiring is complete.
Before operating the system, be sure to remove the film to provide
adequate heat ventilation.
Be sure to fix communication cables or power supply cables leading from
the module by placing them in the duct or clamping them.
Cables not placed in the duct or without clamping may hang or shift,
allowing them to be accidentally pulled, which may cause a module
malfunction and cable damage.

A - 3
[WIRING PRECAUTIONS]
CAUTION
Do not grab on the cable when removing the communication or power
cable connected to the module.
When disconnecting a cable without a connector, first loosen the screws on
the part that is connected to the module.
Pulling the cable when it is still connected to the module may cause
damage to the module or cable, or misoperation due to cable contact
failure.
Always ground the shielded cable for the PLC.
There is a risk of electric shock or malfunction.
When wiring, be sure to verify the rated voltage of the product as well as
the terminal layout. Fire or failure may result if incorrect voltage is input or
incorrect wiring is performed.
Connecting terminals with incorrect voltage may result in malfunction or
mechanical failure.
REVISIONS
The manual number is given on the bottom right of the top cover.
Print Date Manual Number Revision
Jun.
,
2000 IB
(
NA
)
-0800120-
A
First edition
Mar.,2006 IB (NA)-0800120-B Partial correction
Chapter 3, 4
This manual confers no industrial property rights or any rights of any other kind, nor
dose it confer any patent licenses. Mitsubishi Electric Corporation cannot be held
responsible for any problems involving industrial property rights which may occur as
a result of using the contents noted in this manual.
© 2000 MITSUBISHI ELECTRIC CORPORATION

A - 4
CONTENTS
SAFETY PRECAUTIONS............................................................................... A-1
REVISIONS .................................................................................................... A-3
About the Manuals.......................................................................................... A-4
Conformance to the EMC Directive/Low Voltage Directive............................. A-4
1. OVERVIEW ....................................................................................................1
2. SPECIFICATIONS..........................................................................................1
2.1 Performance Specifications ......................................................................1
2.2 Types, Measured Temperature Ranges and Data Resolutions
of Usable Thermocouples ........................................................................3
3. LOADING AND INSTALLATION ....................................................................4
3.1 Handling Instructions ................................................................................4
3.2 Installation Environment ...........................................................................4
4. NAMES AND SETTINGS OF THE PARTS ....................................................4
5. WIRING ..........................................................................................................7
5.1 Wiring Instructions ....................................................................................7
5.2 External Wiring .........................................................................................7
6. SETTING FROM GPPW.................................................................................9
7. OUTLINE DRAWINGS .................................................................................10
About the Manuals
The following manuals are related to this product.
Referring to this list, please request the necessary manuals.
Detailed manual
Manual Name Manual Number
(Model Code)
Q64TCTT, Q64TCTTBW, Q64TCRT, Q64TCRTBW
type Temperature Control Module User's Manual
(details)
SH-080108
(13JT11)
Conformance to the EMC Directive/Low Voltage Directive
When incorporating a Mitsubishi PLC that is compliant with the EMC and low
voltage directives into any other product and ensuring compliance with these
directives, refer to Chapter 3 "EMC and Low Voltage Directives" of the User's
Manual (Hardware) for the PLC CPU included with the CPU module or base
unit.
A module compliant with the EMC and low voltage directives bears a CE mark
logo printed on the rating plate.
To make this product compliant with the EMC and low voltage directives, refer
to "CC-Link module" in Chapter 3 "EMC and Low Voltage Directives" of the
User's Manual (Hardware) for the CPU module.

1
1. OVERVIEW
This user's manual provides the specifications, handling, part names and
others of the following temperature control modules used with the MELSEC-Q
series CPU modules.
•Q64TCTT temperature control module
•Q64TCTTBW temperature control module with wire break detection feature
2. SPECIFICATIONS
The specifications of the Q64TCTT(BW) are indicated below.
2.1 Performance Specifications
Specifications
Item Q64TCTT Q64TCTTBW
Control output Transistor output
Number of temperature input points 4 channels/module
Usable thermocouple Refer to Section 2.2
Ambient
temperature:
25°C ±5°C
Input range width × (±0.3%)
Accuracy Ambient
temperature:
0°C to 55°C
Input range width × (±0.7%)
Ambient
temperature:
0°C to 55°C
Within ±1.0°C
Ambient
temperature:
-100°C to -150°C
Within ±2.0°C
Cold junction
temperature
compensatio
n accuracy Ambient
temperature:
-150°C to -200°C
Within ±3.0°C
Sampling period 0.5s/4 channels
(constant independently of the number of channels used)
Control output period 1 to 100s
Input impedance 1M
Input filter 0 to 100s (0: Input filter OFF)
Sensor correction value setting -50.00 to 50.00%
Operation at sensor input wire
break Upscale processing
Temperature control system PID ON/OFF pulse or 2-position control
PID constant setting Setting by auto tuning enabled
Proportional band
(P) 0.0 to 1000.0% (0: 2-position control)
Integral time (I) 1 to 3600s
PID constant
range
Differential time (D) 0 to 3600s (Set 0 for PI control.)
Set value setting range Temperature range set with the thermocouple used
Dead zone setting range 0.1 to 10.0%

2
Specifications
Item Q64TCTT Q64TCTTBW
Output signal ON/OFF pulse
Rated load voltage DC10 to 30V
Max. load current 0.1A/1 point 0.4A/common
Max. inrush current 0.4A 10ms
OFF-time leakage
current 0.1mA max.
ON-time max.
voltage drop DC1.0V(TYP) 0.1A DC2.5V(MAX) 0.1A
Transistor
output
Response time OFF∏ON: 2ms max. ON∏OFF: 2ms max.
Insulation system Across input and earth : Transformer insulation
Across input and channel : Transformer insulation
Dielectric withstand voltage Across input and earth : 500VAC for 1 minute
Across input and channel : 500VAC for 1 minute
Insulation resistance Across input and earth : 500VDC 20M or more
Across input and channel : 500VDC 20M or more
Current sensor*1
The following current sensor
made by URD Co., Ltd.
Input accuracy
• CTL-12-S36-8(0.0 to 100.0A)
• CTL-6-P-H(0.00 to 20.00A)
Input accuracy Input range width × (±1.0%)
Heater wire
break
detection
specificatios
Alarm delay count
———
3 to 255
Number of occupied I/O points*2
16 points/1 slot
(I/O assignment:
16 intelligent points)
32 points/2 slots
(Default I/O assignment:
16 empty points + 16 intelligent
points)
Connection terminals 18-point terminal block 18-point terminal block ×2
Applicable wire size (mm) 0.3 to 0.75
Applicable crimping terminals R1.25-3,1.25-YS3,RAV1.25-3,V1.25-YS3A
Internal current consumption (A) 0.55 0.64
Weight (kg) 0.20 0.30
Outline dimensions (mm) 27.4 (W) × 98 (H) × 112 (D) 55.2 (W) × 98 (H) × 112 (D)
*1 : Only the current sensor of URD Co., Ltd. may be used.
*2 : When using the Q64TCTTBW, the device numbers of the I/O signals are
incremented by 16 points due to the empty points of the left-hand side slot.
In this manual, therefore, read the I/O signals as indicated below
depending on the module used.
Example) When the signal is indicated as Yn1
When using Q64TCTT: Y1 When using Q64TCTTBW: Y11
*3 : For the noise immunity, withstand voltage, insulation resistance and others
in the PLC system using this module, refer to the power supply module
specifications given in the used CPU module user's manual.

3
2.2 Types, Measured Temperature Ranges and Data Resolutions of Usable
Thermocouples
°C °F
Thermocouple
Type Measured
temperature range Data resolution Measured
temperature range Data resolution
R 0 to 1700 1 0 to 3000 1
0 to 500
0 to 800
0 to 1300
10 to 1000
0 to 2400 1
K-200.0 to 400.0
0.0 to 400.0
0.0 to 500.0
0.0 to 800.0
0.1 0.0 to 1000.0 0.1
0 to 500
0 to 800
0 to 1200
1
0 to 1000
0 to 1600
0 to 2100
1
J0.0 to 400.0
0.0 to 500.0
0.0 to 800.0
0.1 0.0 to 1000.0 0.1
-200 to 400
-200 to 200
0 to 200
0 to 400
10 to 700
-300 to 400 1
T
-200.0 to 400.0
0.0 to 400.0 0.1 0.0 to 700.0 0.1
S 0 to 1700 1 0 to 3000 1
B 0 to 1800 1 0 to 3000 1
0 to 400
0 to 1000 1 0 to 1800 1
E
0.0 to 700.0 0.1 ——— ———
N 0 to 1300 1 0 to 2300 1
0 to 400
-200 to 200 10 to 700
-300 to 400 1
U
0.0 to 600.0 0.1 ——— ———
0 to 400
0 to 900 10 to 800
0 to 1600 1
L0.0 to 400.0
0.0 to 900.0 0.1 ——— ———
PL II 0 to 1200 1 0 to 2300 1
W5Re/W26Re 0 to 2300 1 0 to 3000 1

4
3. LOADING AND INSTALLATION
3.1 Handling Instructions
There are the following instructions for handling the Q64TCTT(BW).
(1) Do not drop the case and connectors of the module and subject them to
hard impact.
(2) Tighten the mounting and terminal screws of the module within the following
ranges.
Screw Location Tightening Torque Range
Module mounting screw (M3 screw) 0.36 to 0.48N m
Terminal block terminal screw (M3 screw) 0.42 to 0.58N m
Terminal block mounting screw (M3.5 screw) 0.66 to 0.89N m
3.2 Installation Environment
Refer to the user's manual of the CPU module used.

5
4. NAMES AND SETTINGS OF THE PARTS
L1
L2
L3
L4
CJ
NC
NC
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
1
CT1
CT2
CT3
CT4
CT5
CT6
CT7
CT8
Q64TCTTBW
NC
RUN ALM
ERR. HBA
L1
L2
L3
L4
CJ
Q64TCTT
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
1
NC
NC
RUN ALM
ERR.
3)
5)
4)
3)
5)5)
1)
2)
1)
2)
6)
6)
CH1
CH2
CH3
CH4
CH1
CH2
CH3
CH4
Number Name and Appearance Description
1) RUN LED
Indicates the operating status of the Q64TCTT(BW).
On : Operating normally.
Off : 5V power switched off, a watchdog timer error
occurred, or a CPU stop error occurred when the
intelligent function module switches of all channels are
set to "CLEAR".
2) ERR LED
Indicates the error status of the Q64TCTT(BW).
On : Hardware fault (including the case where no cold
junction compensation resistor is connected)
Flicker : Write data error occurrence
Off : Operating normally.
3) ALM LED
Indicates the alarm status of the Q64TCTT(BW).
On : Alarm occurrence
Flicker : Process value (PV) is outside the measured
temperature range.
Loop wire break was detected.
Sensor is not connected.
Off : No alarm occurrence
4) HBA LED
Indicates the heater wire break detection status of the
Q64TCTT(BW).
On : Heater wire break was detected.
Off : Heater wire break is not detected.
5) Terminal block* Used for temperature sensor input, transistor output and current
sensor (CT) input.
6) Cold junction temperature
compensation resistor Used for Cold junction temperature compensation.
* : The terminal block layout depends on the module used.
The respective terminal block layouts are shown on the next page.

6
(1) When using Q64TCTT
Terminal Number Signal Name
1L1
2L2
3L3
4L4
5COM-
6 Reserved
7 CH1+
8 CH2+
9 CH1-
10 CH2-
11 Reserved
12 CJ
13 Reserved
14 CJ
15 CH3+
16 CH4+
17 CH3-
18 CH4-
(2) When using Q64TCTTBW
Terminal Number Signal Name
1 Reserved L1
2 CT1+ L2
3 CT1- L3
4 CT2+ L4
5 CT2- COM-
6 CT3+ Reserved
7 CT3- CH1+
8 CT4+ CH2+
9 CT4- CH1-
10 CT5+ CH2-
11 CT5- Reserved
12 CT6+ CJ
13 CT6- Reserved
14 CT7+ CJ
15 CT7- CH3+
16 CT8+ CH4+
17 CT8- CH3-
18 Reserved CH4-

7
5. WIRING
5.1 Wiring Instructions
(1) Use separate cables for the AC control circuit and Q64TCTT(BW)'s external
input signals to avoid the influence of AC side surges and inductions.
(2) Do not run the module cables near, or bundle them with, the main circuit
and high-voltage cables and the load cables from other than the PLC.
Always place the temperature sensors more than 100mm (3.94inch) away
from the main circuit cables and AC control circuit. Fully keep the sensors
away from high-voltage cables and circuits which include high frequencies,
e.g. inverter's main load circuit.
Not doing so can make the sensors more susceptible to noises, surges and
inductions.
(3) Earth the shielded wire or shielded cable to FG of the PLC.
However, depending on the external noise conditions, external earthing
may be recommended.
5.2 External Wiring
(1) When using Q64TCTT
L1
L2
L4
COM
DC24V
R
Internal circuit
Q64TCTT
Controlled
object CH1
CH1
CH2
CH4
CH2
CH4
FilterFilterFilter
Internal circuit
* : Always use shielded wires for cables.

8
(2) When using Q64TCTTBW
L1
L2
L4
DC24V
R
Q64TCTTBW
Filter
Controlled
object
Current sensor
(CT)
Internal circuit
CT input circuit
Connector
CT1
CH1
COM
CH2
CH4
CT2
CT8
CT8
CT2
CT1
CH4
CH2
CH1
Internal circuit
FilterFilter
Connector
*: Always use shielded wires for cables.
POINT
When using the heater wire break detection feature, you need to make CT
input channel assignment setting.
In the above wiring example, as CT1 is used with the loop of channel 1, set 1
(channel 1) to the channel assignment setting buffer memory (108H) of CT1.

9
6. SETTING FROM GPPW
The Q64TCTT(BW) allows you to set the output status at an error stop of the
PLC CPU by making the intelligent function module switch setting.
Make the intelligent function module switch setting using the I/O assignment
setting of GPPW.
You can make setting easily by entering hexadecimal numbers into 4 digits.
Setting Item
Switch 1
CH4 CH3 CH2 CH1
HOutput setting at CPU stop error
0 : CLEAR
Other than 0 : HOLD
Switch 2 Empty
Switch 3 Empty
Switch 4 Empty
Switch 5 Empty

10
7. OUTLINE DRAWINGS
(1) Q64TCTT
L1
L2
L3
L4
Q64TCTT
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
1
RUN ALM
ERR.
CJ
NC
NC
CH1
CH2
CH3
CH4
NC
2 (0.08) 112 (4.41)
5 (0.2)
98 (3.86)
105 (4.14)
2 (0.08)
27.4 (1.08)
Unit: mm (inch)
(2) Q64TCTTBW
L1
L2
L3
L4
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
1
CT1
CT2
CT3
CT4
CT5
CT6
CT7
CT8
Q64TCTTBW
NC
RUN ALM
ERR. HBA
CJ
NC
NC
CH1
CH2
CH3
CH4
NC
2 (0.08) 112 (4.41)
5 (0.2)
98 (3.86)
105 (4.14)
2 (0.08)
55.2 (2.17)
Unit: mm
(
inch
)

Warranty
Mitsubishi will not be held liable for damage caused by factors found not to be the cause of
Mitsubishi; machine damage or lost profits caused by faults in the Mitsubishi products;
damage, secondary damage, accident compensation caused by special factors
unpredictable by Mitsubishi; damages to products other than Mitsubishi products; and to
other duties.
For safe use
• This product has been manufactured as a general-purpose part for general industries, and
has not been designed or manufactured to be incorporated in a device or system used in
purposes related to human life.
• Before using the product for special purposes such as nuclear power, electric power,
aerospace, medicine or passenger movement vehicles, consult with Mitsubishi.
• This product has been manufactured under strict quality control. However, when installing
the product where major accidents or losses could occur if the product fails, install
appropriate backup or failsafe functions in the system.
U.S.A Mitsubishi Electric Automation Inc.
500 Corporate Woods Parkway Vernon
Hills, IL 60061, U.S.A.
Tel : +1-847-478-2100
Brazil MELCO-TEC Rep. Com.e Assessoria
Tecnica Ltda.
Rua Correia Dias, 184,
Edificio Paraiso Trade Center-8 andar
Paraiso, Sao Paulo, SP Brazil
Tel : +55-11-5908-8331
Germany Mitsubishi Electric Europe B.V. German
Branch
Gothaer Strasse 8 D-40880 Ratingen,
GERMANY
Tel : +49-2102-486-0
U.K Mitsubishi Electric Europe B.V. UK
Branch
Travellers Lane, Hatfield, Hertfordshire.,
AL10 8XB, U.K.
Tel : +44-1707-276100
Italy Mitsubishi Electric Europe B.V. Italian
Branch
Centro Dir. Colleoni, Pal. Perseo-Ingr.2
Via Paracelso 12, I-20041 Agrate Brianza.,
Milano, Italy
Tel : +39-039-60531
Spain Mitsubishi Electric Europe B.V. Spanish
Branch
Carretera de Rubi 76-80,
E-08190 Sant Cugat del Valles,
Barcelona, Spain
Tel : +34-93-565-3131
France Mitsubishi Electric Europe B.V. French
Branch
25, Boulevard des Bouvets, F-92741
Nanterre Cedex, France
TEL: +33-1-5568-5568
South Africa Circuit Breaker Industries Ltd.
Private Bag 2016, ZA-1600 Isando,
South Africa
Tel : +27-11-928-2000
Hong Kong Mitsubishi Electric Automation
(Hong Kong) Ltd.
10th Floor, Manulife Tower, 169 Electric
Road, North Point, Hong Kong
Tel : +852-2887-8870
China Mitsubishi Electric Automation
(Shanghai) Ltd.
4/F Zhi Fu Plazz, No.80 Xin Chang Road,
Shanghai 200003, China
Tel : +86-21-6120-0808
Taiwan Setsuyo Enterprise Co., Ltd.
6F No.105 Wu-Kung 3rd.Rd, Wu-Ku
Hsiang, Taipei Hsine, Taiwan
Tel : +886-2-2299-2499
Korea Mitsubishi Electric Automation Korea
Co., Ltd.
1480-6, Gayang-dong, Gangseo-ku
Seoul 157-200, Korea
Tel : +82-2-3660-9552
Singapore Mitsubishi Electric Asia Pte, Ltd.
307 Alexandra Road #05-01/02,
Mitsubishi Electric Building,
Singapore 159943
Tel : +65-6470-2460
Thailand Mitsubishi Electric Automation (Thailand)
Co., Ltd.
Bang-Chan Industrial Estate No.111
Moo 4, Serithai Rd, T.Kannayao,
A.Kannayao, Bangkok 10230 Thailand
Tel : +66-2-517-1326
Indonesia P.T. Autoteknindo Sumber Makmur
Muara Karang Selatan, Block A/Utara
No.1 Kav. No.11 Kawasan Industri
Pergudangan Jakarta - Utara 14440,
P.O.Box 5045 Jakarta, 11050 Indonesia
Tel : +62-21-6630833
India Messung Systems Pvt, Ltd.
Electronic Sadan NO:III Unit No15,
M.I.D.C Bhosari, Pune-411026, India
Tel : +91-20-2712-3130
Australia Mitsubishi Electric Australia Pty. Ltd.
348 Victoria Road, Rydalmere,
N.S.W 2116, Australia
Tel : +61-2-9684-7777
Country/Region Sales office/Tel
When exported from Japan, this manual does not require application to the Ministry
of Economy, Trade and Industry for service transaction permission.
Specifications subject to change without notice.
Printed in Japan on recycled paper.
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
NAGOYA WORKS : 1-14, YADA-MINAMI 5-CHOME, HIGASHI-KU, NAGOYA, JAPAN
Country/Region Sales office/Tel
This manual suits for next models
1
Table of contents
Other Mitsubishi Temperature Controllers manuals
Popular Temperature Controllers manuals by other brands

YOKOGAWA
YOKOGAWA Green Series user manual

Toho Electronics
Toho Electronics TTM-00BT series instruction manual

dixell
dixell XH360L operating instructions

Siemens
Siemens SITRANS TS100 Compact operating instructions

Keysight Technologies
Keysight Technologies E2307A user guide

ILX Lightwave
ILX Lightwave LDT-5412B user guide

Clint
Clint floyd FVW Series Instructions for installation, use and maintenance manual

SYStronics
SYStronics STH-PR5N-F user manual

Fuji Electric
Fuji Electric PUM Series Instruction

Selec
Selec PID500 operating instructions

Johnson Controls
Johnson Controls A419ABG-3C installation instructions

Siemens
Siemens REA22 Basic documentation