3.6Installation ofdampingdevices
3.6.1Damping devices mustbeprovidedbetweentheunit
and itsfoundation.
Bymeansofthe Φ15mm diameterinstallationholesonthe
steelframeoftheunitbase,theunitcan befastenedon
the foundationthrough the springdamper.See
Fig.3-3(Schematicdiagramofinstallationdimensionofthe
unit)fordetailsaboutcenterdistanceoftheinstallation
holes.The damperdoesnotgowiththeunit,andtheuser
can selectthedamperaccording totherelevant
requirements.Whentheunit isinstalledonthehigh roofor
theareasensitivetovibration,pleaseconsulttherelevant
personsbeforeselectingthedamper.
3.6.2Installation stepsofthedamper
Step 1.Makesurethatthe flatness oftheconcrete
foundationiswithin ±3mm,andthenplacetheunitonthe
cushionblock.
Step 2. Raisethe unittotheheightsuitableforinstallation
of thedampingdevice.
c. Removetheclampnutsofthedamper.
Step 3.Placetheunitonthedamper,andalignthefixing
boltholesofthedamperwiththefixingholeson the unit
base.
Step 4.Returntheclampnutsofthedampertothefixing
holesontheunitbase,andtightenthemintothe damper.
Step 5.Adjusttheoperationalheightofthedamperbase,
andscrewdownthelevelingbolts.Tightentheboltsby
onecircletoensureequal heightadjustmentvarianceof
thedamper.
Step 6.The lockboltscanbetightenedafterthecorrect
operationalheight isreached.
Dampingdevice
Nut
Ferrol
Itisrecommendedthat thedampershouldbefastenedon
thefoundationwiththeprovidedholes.Aftertheunitis
placedonthefoundation, thedamperconnectedwiththe
unitshouldnot bemoved,andthecentral clampnutisnot
allowedtobetightenedbeforethedampersustainsload.
Fig.3-5
4.WATER SYSTEMINSTALLATION
4.1Basicrequirementsofconnection ofchilled
waterpipes
●Aftertheunitisinplace, chilledwaterpipescan belaid.
●Therelevantinstallationregulationsshould beabidedwith
whenconductingconnectionofwaterpipes.
●Thepipelinesshouldbefree ofanyimpurity,andallchilled
waterpipesmustconformtolocalrulesand regulationsof
pipelineengineering.
●Connectionrequirementsof chilledwaterpipes
a.Allchilledwaterpipelinesshouldbethoroughlyflushed,tobe
freeofanyimpurity,beforetheunitisoperated.Anyimpurity
shouldnot beflushedtoorintotheheatexchanger.
b.Watermustentertheheatexchangerthroughthe inlet;
otherwisetheperformanceoftheunit willdecline.
c.The inletpipeoftheevaporatormustbeprovidedwitha
targetflowcontroller,torealizeflow-breakprotectionforthe
unit.Bothendsofthetargetflowcontrollermustbesupplied
withhorizontalstraightpipesectionswhosediameteris5times
that of theinletpipe. Thetargetflowcontrollermustbeinstalled
instrictaccordancewith “Installation&RegulationGuidefor
TargetFlowController”(Figure4.3~4.4).Thewiresofthetarget
flowcontrollershouldbeledtotheelectriccabinetthrough
shieldedcable(seeElectricControllingSchematicDiagramfor
details).Theworking pressureofthetargetflowcontrolleris
1.0MPa,and itsinterfaceis1inchindiameter.Afterthe
pipelinesareinstalled,the targetflowcontrollerwillbe set
properlyaccordingtotheratedwaterflowoftheunit.
d.Thepumpinstalledinthewaterpipelinesystemshould be
equippedwithstarter.Thepumpwill directlypress waterinto
theheatexchangerofthewatersystem.
e.Thepipesandtheirportsmustbeindependentlysupported
butshouldnotbesupportedon theunit.
f.Thepipesandtheirportsoftheheatexchangershouldbe
easytodisassemble foroperationand cleaning,aswellas
inspectionof port pipesof theevaporator.
g.Theevaporatorshouldbeprovidedwithafilterwithmore
than40meshesperinchatsite.Thefiltershouldbeinstalled
neartotheinletportasmuchaspossible,andbeunderheat
preservation.
h.The by-pass pipesandby-passvalvesasshowninFig.4-1
mustbemountedfortheheatexchanger,tofacilitatecleaning
oftheoutsidesystemofwaterpassagebeforethe unitis
adjusted.Duringmaintenance,thewaterpassage oftheheat
exchangercan be cutoffwithoutdisturbing otherheat
exchangers.
i.Theflexibleportsshouldbeadoptedbetweentheinterfaceof
theheatexchangerandon-sitepipeline,toreducetransferof
vibrationtothebuilding.
j. Tofacilitatemaintenance,theinletand outletpipesshouldbe
providedwiththermometerormanometer.Theunitisnot
equippedwithpressureandtemperatureinstruments,sothey
needtobe purchasedbytheuser.
k.Alllowpositionsofthewatersystemshouldbeprovidedwith
drainageports,todrainwaterintheevaporatorandthe system
completely;andallhigh positionsshouldbesupplied with
discharge valves,tofacilitateexpellingairfromthepipeline. The
discharge valvesanddrainageportsshouldnotbeunderheat
preservationtofacilitatemaintenance.
CAUTION
NOTE
Installation & owner's manual
5
Modular Chiller MUEN-H6
Anchor bolt (M10X300)