Nailor 35S User manual

Nailor Industries, Inc. reserves the right to change any information concerning product or specification without notice or obligation.
DISCHARGE
DUCT PRIMARY
INLET
PRIMARY
AIRFLOW
INDUCED
AIR
ELECTRIC
HEATER
SECTION
INDUCED AIR
INDUCTION PORT
(DO NOT OBSTRUCT)
STEALTH
ATTENUATOR
DISCHARGE
DUCT PRIMARY
INLET
PRIMARY
AIRFLOW
HOT WATER
SECTION
General
Receiving Inspection Checklist
Visually inspect unit for shipping damage before unwrapping
any packaging material. Report any damage immediately to the
delivering carrier.
After unpacking the unit, check it again for shipping damage. If any
shipping damage is found, report it immediately to the delivering
carrier.
Notify your local Nailor representative of damage and arrange for
repair or replacement.
Check that the unit is labeled as intended and deliver to appropriate
site location.
Store units in a clean, dry location.
Caution: Do not use the inlet collar, damper shaft, airow
sensor, electrical conduit, water coil extremities, drip pan,
or tubing as a handle to lift or move assembly. Damage to
the unit, unit accessories or controls may result.
Safety Precautions
a. All person(s) involved in installation process shall be qualied
according to all relevant local codes and standards.
b. Beware of other building utilities and electrical wiring during
installation process.
c. The unit installed shall be used only as intended. Any unintended
use shall therein result in immediate forfeiture of manufacturer
assumed warranty, responsibility and liability of product and
associated components. Contact your local Nailor representative
for questions.
d. Warning: Make sure all electrical power to the unit has
been disconnected and any capacitors fully discharged
before servicing. Failure to do so could result in injury or
death.
e. During brazing process, make sure to protect any surrounding
ammable materials, using barriers where applicable and always
have a re extinguisher accessible.
Caution: Any improper product handling, installation,
servicing, or operation resulting in personal injury and
property damage shall void any manufacturer assumed
legal responsibility.
Installation
Supporting the Assembly
Suspend the unit from the building structure in the horizontal plane
and ensure the unit is level to guarantee proper performance. Hanger
rods or straps (by others) should be securely attached to joists or to
mounting anchors which are properly secured to slab construction with
lugs or poured in place anchors. Be careful not to obstruct the bottom
access panel in order to maintain clearance for blower service. When
requested, the unit is supplied with optional hanger brackets (shipped
loose for eld mounting) for use with hanger rod up to 3/8" (9.5) dia.
Hanger brackets or straps should be screwed to the top corner posts
(35S only) or unit casing sides (other models) or alternatively onto the
inlet and outlet ends of the unit. See Figures 1 and 2.
Caution: Nailor Fan Powered Terminal units are too
heavy to suspend with the ductwork and must be
independently supported.
Duct Connections
All ducts should be installed in accordance with SMACNA guidelines.
Slip each inlet duct over the inlet collar of the terminal. Fasten and
seal the connection by the method prescribed in the job specication.
The diameter of the inlet duct in inches must be equal to the nominal
size of the terminal inlet. The inlet collar of the terminal is 1/8" (3)
smaller than the nominal duct size to allow it to t inside the duct.
Important: Do not insert ductwork inside the inlet collar
of the assembly.
Installation and Operation Manual (IOM)
Fan Powered Terminal Units
Model Series: 35S(ST), 35SXC, 35N,
37S(ST) and 37N
7-6-23 IOM-FPTU Page 1 of 10
Figure 1: Fan Powered Terminal Unit Support Using Hanger Straps
(Model 35SE illustrated).
Figure 2: Fan Powered Terminal Unit Support Using Hanger Brackets
and Rods (Models 35SWST and 35SW illustrated).
USE "Z" BRACKET
WITH
ELECTRIC OR
HOT WATER HEAT

Nailor Industries, Inc. reserves the right to change any information concerning product or specification without notice or obligation.
For optimum performance, 2 to 3 equivalent diameters of straight
duct should be installed prior to the inlet of the unit. Rectangular
discharge opening is designed for a anged duct connection. A clear
area around the opening has been left for screw penetration. Fasten
and seal all connections by method prescribed in the job specication.
Minimum Access
Make appropriate accommodations for access panel removal. If unit
is to be installed in hard ceiling/wall application, refer to Nailor
fan powered terminal unit submittals for specic dimensions before
installing to assure there is access to the unit and components after
installation is complete. Nailor 35S fan powered VAV terminal units
have access panels on the top, bottom and side. Nailor 35N units
have only bottom panels. Model 37S and 37N have top and bottom
panels. Removable top and bottom access panels are secured as
standard with screws. However, if the ¼ turn fastener access panel
option is supplied, the bottom panel screws are replaced with two
quick-connect latches.
Units with a removable top access panel are secured with two
additional screws in the middle for shipping and handling. These
additional screws can be removed after the unit is hung for quicker
service if needed.
For low voltage control enclosure access, a minimum of 18" (457) is
recommended. Specic control enclosure location is indicated on
product submittals. Low voltage control enclosures have removable
covers that are attached with sheet metal screws. High voltage
controls enclosures have access panels that are equipped with
hinges. For clearances for full opening of hinged access doors, refer
to project specications, submittal sheets and NEC.
Important: These recommendations do not preclude
NEC or local codes that may be in effect, which are the
responsibility of the installing contractor.
Field Wiring
All eld wiring must comply with NEC and local codes. Disconnect
switches are optional. Wiring diagrams can be found on labels
afxed to the exterior/interior of the control box enclosure. Unless
specically requested by customer, all units are wired for a single
point connection to the fan and electric heater (if present). All electric
heaters will be staged per specication. Motors rated for 277 or 120
VAC on units with 480 or 208 VAC ratings respectively are always
connected between the neutral and L1 terminals. The installing
electrician should rotate the incoming electric service by phase to
help balance the building electric load.
Fuse size designates the size of the internal fuse if it is supplied.
Maximum Overcurrent Protection (MOP) designates the largest
breaker or fuse in the electrical service panel that can be used to
protect the unit. See Table 1 for calculation details.
Electrical Suggestions and Requirements
1. Provide a safety disconnect per NEC 424-19, 20, 21.
2. Disconnect the power supply before wiring or servicing unit. If+ a
disconnect switch is present, it should be in the OFF position while
making power connections or repairs.
3. All units with electric heat should have copper wires sized for minimum
circuit ampacity (MCA). See Table 1 for calculation details.
4. Follow wiring diagrams and instructions mounted on the unit.
480V/3 phase heaters, for example, require a neutral wire in
addition to the full sized ground wire. NEC 424-15 and 250 also
require that all units be grounded.
Water Pipe Connections
Exercise extreme caution during "sweating" or brazing process of coil
piping to avoid applying excessive heat to components associated
with valve package. This could cause irreversible damage, requiring
immediate replacement of parts. Make sure valves are in full open
position during brazing process. Heat can be dissipated more
effectively by wrapping a wet towel around the valve body during the
brazing process.
Control Start-up and Operation
Your local Nailor Representative can provide detailed information
about start-up and operating procedures for Nailor’s digital, analog,
and pneumatic controls. For specic information on controls provided
by other manufacturers contact the control manufacturer’s local or
national ofce. This applies whether the controls were factory or eld
installed.
NOTE
Note: Digital controllers may use specic communication
addresses based on Building Management Systems,
Architecture and original engineering drawings.
Installing the terminal in a location other than that noted
on the label may result in excessive start-up labor.
Primary Air Damper and Fan Adjustment
Before starting the fan motor:
a. If lters are required, make sure they are installed as intended.
b. Make sure duct system is clear of all debris and foreign objects.
c. Ensure unit enclosure, blower housing and blower wheel are free
of any debris and foreign objects.
Starting the fan motor:
1. Start motor and let it run-in at least 15 minutes. During run-in,
check ductwork connections for leaks and repair if necessary.
2. All Nailor fan powered VAV terminal units incorporating PSC
motors use a solid state SCR speed controller to adjust motor
speed and consequently air volume. Speed controllers have built-in
maximum and minimum stops as detailed on the fan performance
pages in the Nailor VAV Terminal Unit catalog. Turning the manual
fan speed control counterclockwise will increase the fan speed;
clockwise will decrease speed. The fan speed control is located
on the side of the motor controls enclosure.
3. For series units, set the unit to full cooling. Adjust and set primary
maximum cfm by measuring the airow with a manometer
attached between the gauge ports in the pneumatic tube leading
to the high and low sides of the inlet air pick-up. A chart is attached
to the side of the unit showing airow vs. pressure for different inlet
sizes. Adjust and set remote balancing dampers, if present. Do not
worry about airow at this time; just proportion the outlets with the
dampers. Be sure to leave the dampers in the most possible open
position. This will generate the minimum noise level. Adjust the fan
speed control until the required CFM is obtained (by measuring
the air quantity at the room outlets or by zeroing the induction air if
primary and fan match). Fan should be adjusted with primary air
at maximum set point to ensure that no supply air is discharged at
the induction port. Recheck the fan and primary airows when the
damper is reset to the minimum set point.
4. For parallel units, turn the fan off, and set the primary air in the
same manner as described for series units. Proportion the diffusers
as above. Reset the primary airow to the design fan turn-on point.
Measure the airow again to verify proper airow. Turn the fan
on. Allow the primary air damper to come under control after the
fan is started, and then adjust the fan until the prescribed airow
is achieved by measuring the air quantity at the room outlets. Be
sure to allow the primary air damper to stabilize after each fan
adjustment and prior to measuring the airow. Turn the fan off and
verify the minimum airow point on the damper.
5. For units equipped with ECM motors, set the primary air dampers
as described in (3). Set the fan as described on the ECM MOTORS
IOM, page 1. Proportion the dampers after the fan is set. Remember
to adjust the dampers so that they are in the most open condition
after proportioning. This will generate the minimum noise.
Page 2 of 10 7-6-23 IOM-FPTU

Nailor Industries, Inc. reserves the right to change any information concerning product or specification without notice or obligation.
7-6-23 IOM-FPTU Page 3 of 10
Label Example
Maintenance Procedures
Warning: Electrical Hazard!
Before Servicing, disconnect all sources of electrical power,
including the complete discharge of any electric current stored
in capacitors included in the wiring structure. Practice good
lockout/tagout procedures to prevent energizing of the unit
during servicing. Failure to comply with previous statements
could yield personal injury or even result in death.
Fan and Motor
Nailor fan powered terminal units are equipped with permanently
lubricated motors. Inspect fan and motor assembly for dust and dirt as
often as dictated by operating environment. Clean assembly if necessary.
If fan motor does not run, do the following:
a. Check for free rotation of blower wheel. Make sure no foreign
objects are in fan. Look for signs of freight or job site damage.
b. Check power supply. Disconnects should be in the "ON" position.
Optional fusing should also be inspected. Check transformer for
proper output.
c. Check for proper control signals and PE switch setting (if provided)
and relay function.
Fan motor runs but emits excessive noise
a. Maximum airow may be too high, or discharge static pressure
may be incorrect.
b. Blower may have clearance problems. Make sure all components
are securely attached.
c. Verify integrity of ductwork. Leaks or loose connections could
cause noise. Check for rattling diffusers or rattling or incorrectly
adjusted balancing dampers.
Fan motor runs, but airflow too low:
a. May be due to ductwork restrictions, dirty air lters or clogged
water coils.
b. Readjust fan speed control on control card.
c.
Discharge static pressure may be incorrect. Check balancing dampers.
d. Conrm signal from the motor card to the motor by measuring the
plug at the motor.
If repair or replacement is required
Disconnect all power before servicing. Motor and fan should be
removed as an assembly. Remove the four hex nuts from mounting
lugs holding the fan assembly to the discharge panel, and remove
the assembly through any convenient access panel. Do not allow
assembly to hang from wiring. If removing motor from blower, rst
loosen the set screw holding the blower wheel to the motor shaft.
Remove the three screws holding the motor to the fan housing, and
slide motor and fan housing apart.
To put the assembly back together, reverse the procedure. Be sure
to align the blower set screw with the at section of motor shaft.
NOTE
Note: Over-tightening motor mounting screws may
crush isolation bushing, causing excessive fan noise.
Primary Air Damper Replacement
Nailor’s primary air valve assembly is not repairable. The entire
assembly should be replaced if it is damaged.
Labels
Each fan powered terminal unit is shipped with a nameplate label
afxed to the control casing. Principle nameplate data on the label
typically include Order-Serial number, Model number, Unit Size,
Motor horsepower, Amperage, MOP, Heater (if present) data, Supply
voltage and Airows. Also provided are calibration, airow, as well as
other labels as necessary. We suggest that you read all labels before
beginning installation. If you have any questions, please contact your
local Nailor Representative. Their phone numbers can be found on
our website at nailor.com.
Fan Powered
Terminal Unit
(Unite Terminale @
Ventilateur Intégré)
Date (Date)
Model (Modèle)
Unit Size-Inlet Size
(Diamètre D'Entrée)
Control Voltage
(Voltage De Contrôle)
Control Sequence
(Séquence De Contrôle)
Volt Amp (Volt-Ampère)
:
:
:
:
:
:
5-Jul-2023 Serial No. (No. De Série)
Tag No. (No. D'étiquette)
Voltage (Voltage)
Phase (Phase)
Stages (Étapes)
HZ (HZ)
Motor HP (Moteur HP)
Motor Voltage
(Voltage Du Moteur)
Motor Amp
(Ampérage Du Moteur)
:
:
:
:
:
:
:
:
:
Hot Water Coil Rows
(Nombre De Rangées Serpentin Eau Chaud)
Chilled Water Coil Rows
(Nombre De Rangées Serpentin Eau Froid)
:
:
KW/HP
Heater (Chauffage)
Motor (Moteur)
Total (Totale)
Amps (Ampères) Ampacity (Ampacitée)
Max. Overcurrent Protection
(Resistance Des Fusible Max.)
Internal Fuse Size
(If Supplied)
Total
(Totale)
Each Cir.
(Chaque
Circuit)
Each Stg.
(Chaque
Étape)
Total
(Totale)
Each Cir.
(Chaque
Circuit)
Each Stg.
(Chaque
Étape)
Total
(Totale)
Each Cir.
(Chaque
Circuit)
Each Stg.
(Chaque
Étape)
Total
(Totale)
Each Cir.
(Chaque Circuit)
Each Element Rated @
(Chaque Element Classifier A)
KW
@
VAC.
AWG. Min Wire Size (Min Diamètre De Fil) :
Min. Heating CFM (Min. PCM) :
Use wire suitable for at least 75 °C,
L1 is color coded black, L2 is blue, L3 is red,
Control wires coded as marked,
Use copper conductors only.
Utiliser un fil métallique qui convient au moin 75 °C,
L1 est colore noire, L2 est blue, L3 est rouge,
Les fils de contrôle son identifiée comme marque,
Utilise des conducteurs de cuivre seulement.
Primary CFM (Max/Min) :
Fan CFM :
Primary L/S (Max/Min) :
Fan L/S :
D35SE
3-8
24
DF
50
155258-10
0
42
208
1
2
60
0
208
62.5
80
6.50
13.00
62.5
31.25
78.13
39.07
39.07
80
0
0.00
0
62.50
78.13
15
N/A
3.25
890 / 360
890
420 / 170
420
40
208
910.00
4
13.00
Primaire PCM (Max.Min):
Ventilateur PCM:
Primaire L/S (Max.Min):
Ventilateur L/S:
Fan Powered
Terminal Unit (Unite Terminale @
Ventilateur Intégré)
Date
(Date)
Model
(Modèle)
(Diamètre D'Entrée)
Control Voltage
(Voltage De Contrôle)
Control Sequence
(Séquence De Contrôle)
Volt Amp (Volt-Ampère)
:
:
:
:
:
:
5-Jul-2023
Serial No.
(No. De Série)
Tag No. (No. D'étiquette)
Voltage (Voltage)
Phase
(Phase)
Stages (Étapes)
HZ (HZ)
Watts (Watts)
Motor Voltage
(Voltage Du Moteur)
Motor Amp
(Ampérage Du Moteur)
:
:
:
:
:
:
:
:
Hot Water Coil Rows
(Nombre De Rangées Serpentin Eau Chaud)
Chilled Water Coil Rows
(Nombre De Rangées Serpentin Eau Froid)
:
:
KW/Watts
Heater (Chauffage)
Motor (Moteur)
Total (Totale)
Amps
(Ampères)
Ampacity
(Ampacitée)
Max. Overcurrent Protection
(Resistance Des Fusible Max.)
Internal Fuse Size
(If Supplied)
Total
(Totale)
Each Cir.
(Chaque
Circuit)
Each Stg.
(Chaque
Étape)
Total
(Totale)
Each Cir.
(Chaque
Circuit)
Each Stg.
(Chaque
Étape)
Total
(Totale)
Each Cir.
(Chaque
Circuit)
Each Stg.
(Chaque
Étape)
Total
(Totale)
Each Cir.
(Chaque Circuit)
Each Element Rated @
(Chaque Element Classifier A)
KW
@
VAC.
AWG. Min Wire Size (Min Diamètre De Fil) :
Min. Heating CFM (Min. PCM) :
Use wire suitable for at least 75 °C,
L1 is color coded black, L2 is blue, L3 is red,
Control wires coded as marked,
Use copper conductors only.
Primary CFM (Max/Min) :
Fan CFM
Primary L/S (Max/Min) :
Fan L/S
D35SE
3-8
24
DF
50
155258-10
0
42
208
1
2
60
208
0
62.5
80
62.5
0
0
13.00
13.00
6.50
62.50
31.25
78.13
0.00
78.13
39.07
39.07
80
40
15
N/A
3.25
208
890 / 360
890
420 / 170
420
4
910.00
(Ventilateur PCM) (Ventilateur L/S)
Primaire PCM (Max.Min) Primaire L/S (Max.Min)
Unit Size-Inlet Size
:
Utiliser un fil métallique qui convient au moin 75 °C,
L1 est colore noire, L2 est blue, L3 est rouge,
Les fils de contrôle son identifiée comme marque,
Utilise des conducteurs de cuivre seulement.

Nailor Industries, Inc. reserves the right to change any information concerning product or specification without notice or obligation.
Minimum Circuit Ampacity
MCA = 1.25 x (Load 1 + Load 2 + Load 3 + Load 4)
Maximum Overcurrent Protection
MOP = (2.25 x load 1) + load 2 + load 3 + load 4
If the calculated MOP does not equal the standard current rating of an Overcurrent protective device (typically even multiples of 5),
then the marked MOP is the next lower standard rating.
Exceptions:
1. The marked MOP will be the next higher standard rating than the computed value, if the next lower standard rating is less than 125
percent of the current rating of an electric heater load when such heater is involved.
2. If the computed value for MOP is less than the MCA, then the marked MOP is increased to the largest MOP appropriate for the
MCA.
3. If the MCA does not correspond to a standard protective device rating, the next higher standard rating of the protective device will
be marked if this rating does not exceed 800 A.
For Nailor Fan Powered Terminal Units and Fan Powered Terminal Units, Load 1 is the largest motor current, Load 2 is the sum
of all other motor currents, and Load 3 is the heater current. Load 4 is used for other loads greater than 1.0 ampere and can be
considered zero for most standard products.
For Nailor Variable Air Volume Units, Load 1 and Load 2 are considered zero.
Load 3 is the heater current Load 4 is used for other loads greater than 1.0 ampere and can be considered zero for most standard
products.
(Motor currents are determined by product application test in accordance with UL 1995 and may not be the same as the motor
manufacture’s FLA marking.)
All formulae, denitions, and exceptions are cited from Underwriters Laboratories Inc. Standard for Safety for Heating and Cooling Equipment, UL
1995 Fifth Edition (Sec. 44.14.44.15) CAN/CSA-C22.2 No. 236 Fifth Edition
Page 4 of 10 7-6-23 IOM-FPTU
MCA and MOP Calculations
.40
.02
.03
.04
.05
.06
.07
.08
.09
.20
.50
.60
.70
.80
.90
1.0
.30
.10
.15
30 300 400 700 1000 1500 50003000200080605040 200100 150 500
CFM
DIAMOND FLOW SENSOR
FIELD CALIBRATION CHART
MODEL SERIES:
3100, 3230, 3240, 33SZ, 35N, 35S,
35SST, 36VRR, 37N, 37S & 37SST
DFSCC-2
11-2022
SENSOR ∆P (INCHES W.G.)
SIZE 4 ROUND
SIZE 5 ROUND
SIZE 6 ROUND
SIZE 7 ROUND
SIZE 8 ROUND
SIZE 9 ROUND
SIZE 10 ROUND
SIZE 14 x 10 RECT.
SIZE 14 ROUND
SIZE 16 ROUND
SIZE 18 OVAL
Inlet K-Factor
Size
4 Round 182
5 Round 325
6 Round 455
7 Round 657
8 Round 899
9 Round 1158
10 Round 1497
12 Round 2048
14 Round 2742
16 Round 3683
14 x 8 Rect. 2035
14 x 10 Rect. 2417
18 Oval 4323
CFM = K x ∆P
ALLOWABLE PNEUMATIC LO
SETTING MIN. ∆P = O.O3" W.G.
SIZE 12 ROUND (14x8 RECT.)
Sample Diamond Flow Sensor Calibration Label
ECM MOTOR FAN CALIBRATION TABLE
FAN POWERED TERMINAL UNIT
MODEL SERIES: 35S & 35SST • UNIT SIZE 3 • 120/208/230/277 VAC 2/26/23
0-10 0-10 0-10 0-10
V
DC
V
DC
V
DC
V
DC
REF. REF. REF. REF.
138 0.50 429 2.89 747 5.29 1023 7.68
146 0.57 438 2.96 756 5.36 1030 7.75
155 0.64 448 3.03 765 5.43 1037 7.82
163 0.71 457 3.10 774 5.50 1044 7.89
171 0.78 466 3.17 783 5.57 1051 7.96
179 0.85 475 3.24 791 5.64 1058 8.03
188 0.92 485 3.31 800 5.71 1065 8.10
196 0.99 494 3.39 809 5.78 1072 8.17
204 1.06 503 3.46 818 5.85 1079 8.24
213 1.13 513 3.53 826 5.92 1086 8.31
221 1.20 522 3.60 835 5.99 1093 8.38
229 1.27 531 3.67 843 6.06 1100 8.45
238 1.34 541 3.74 852 6.13 1108 8.52
246 1.41 550 3.81 860 6.20 1115 8.59
254 1.49 560 3.88 869 6.27 1122 8.66
263 1.56 569 3.95 877 6.34 1129 8.73
271 1.63 579 4.02 885 6.41 1136 8.80
280 1.70 588 4.09 893 6.48 1143 8.87
288 1.77 598 4.16 901 6.55 1151 8.94
297 1.84 607 4.23 909 6.62 1158 9.01
305 1.91 616 4.30 917 6.69 1166 9.09
314 1.98 626 4.37 925 6.76 1173 9.16
322 2.05 635 4.44 933 6.83 1181 9.23
331 2.12 645 4.51 941 6.90 1189 9.30
340 2.19 654 4.58 949 6.97 1197 9.37
349 2.26 663 4.65 956 7.04 1205 9.44
357 2.33 673 4.72 964 7.11 1213 9.51
366 2.40 682 4.79 971 7.19 1222 9.58
375 2.47 691 4.86 979 7.26 1230 9.65
384 2.54 701 4.93 986 7.33 1239 9.72
393 2.61 710 5.00 994 7.40 1248 9.79
402 2.68 719 5.07 1001 7.47 1257 9.86
411 2.75 728 5.14 1008 7.54 1266 9.93
420 2.82 737 5.21 1016 7.61 1276 10.00
THIS UNIT HAS BEEN FACTORY SET AT ____________ CFM.
www.nailor.com SUBJECT TO CHANGE WITHOUT NOTICE
Digital Control Algorithm:
CFM=0.027717307(VDC)5‐0.61146699(VDC)4+4.155391639(VDC)3‐8.60626115(VDC)2+124.7107364(VDC)+77.19940471
VDC=‐1.2214E‐14(CFM)5+3.95345E‐11(CFM)4‐4.43622E‐08(CFM)3+2.07462E‐05(CFM)2+4.104313E‐03(CFM)‐0.340841705E+0
0
RE-CALIBRATION IS NOT REQUIRED UNLESS THE ZONE DESIGN AIRFLOW REQUIRMENT HAS CHANGED. THE BOLD LINES INDICATE MIN AND
MAX CFM FOR THE UNIT. VARIATIONS IN FLOW IS IN +/- 5% or +/- 30 CFM WHICHEVER IS GREATER EXCEPT IN GRAY AREA. DATA
REPRESENTED IN THIS CHART IS AT STANDARD CONDITIONS OF TEMPERATURE, PRESSURE AND HUMIDITY I.E. SCFM. FAN TURNS OFF
BELOW 0.50Vdc.
CFM vs VDC
(
Im
p
erial Units
)
CFM CFM CFM CFM
Application Charts for ECM Motors
Airflow Direction (affixed to inlet collar)
AIR FLOW (ECOULEMENT DE L'AIR)
AIR FLOW (ECOULEMENT DE L'AIR)
LOW (BAS) HIGH (HAUT)
HIGH (HAUT) LOW
Table 1.

Nailor Industries, Inc. reserves the right to change any information concerning product or specification without notice or obligation.
7-6-23 IOM-FPTU Page 5 of 10
Model Series Fan Powered Terminal Units Replacement Parts
NAILOR EZVAV DIGITAL CONTROLS
Code Description
Controller/Actuators:
BAC-8001-36 EZVAV Digital Controller (SD Clg only)
BAC-8005-36 EZVAV Digital Controller (SDRH, FP)
BAC-8007-36 EZVAV Digital Controller (DD master)
TSP-8001-36 EZVAV Digital Controller (DD slave)
Room Temperature Sensors:
STE-8001W36 EZVAV Room Temp Sensor – Digital display
STE-8201W36 EZVAV Room Temp Sensor – Digital display w/
motion sensor
STE-6014W36 EZVAV Room Temp Sensor – Rotary dial
ECRJ45-25 Ethernet cable RJ-45, 25 ft.
ECRJ45-35 Ethernet cable RJ-45, 35 ft.
ECRJ45-50 Ethernet cable RJ-45, 50 ft.
ECRJ45-75 Ethernet cable RJ-45, 75 ft.
STE-1401 Air temp. sensor (HCCO, DAT)
ELECTRICAL COMPONENTS
RAPP Code
Description Part
Number
Disconnect Switches
EC-DISTG251P Toggle Disconnect Switch
1P,600V,25A H1-0212A
EC-DISTG403P Toggle Disconnect Switch
3P,600V,40A H1-0220Z
EC-DISTG603P Toggle Disconnect Switch
3P,600V,60A H1-0221Z
EC-DISINT25A Interlocking Disconnect
Switch3P,600V,25A H1-0215Z
EC-DISINT40A Interlocking Disconnect
Switch3P,600V,40A H1-0216Z
EC-DISINT60A Interlocking Disconnect
Switch3P,600V,60A H1-0217Z
EC-DISINTHDL Interlocking Disconnect Handle H1-0215C
EC-DISINTSFT Interlocking Disconnect Shaft H1-0215D
Contactors
EC-CONM50A1P Contactor MAG 1P,600V,40Amp H1-0635
EC-CONM40A1P Contactor MAG 1P,600V,40Amp H1-0636
EC-CONM30A1P Contactor MAG 1P,600V,20Amp H1-0654
EC-CONM50A2P Contactor MAG 2P,600V,40Amp H1-0658
EC-CONM40A2P Contactor MAG 2P,600V,30Amp H1-0655
EC-CONM30A2P Contactor MAG 2P,600V,20Amp H1-0652
EC-CONM50A3P Contactor MAG 3P,600V,40Amp H1-0640
EC-CONM40A3P Contactor MAG 3P,600V,30Amp H1-0639
EC-CONM30A3P Contactor MAG 3P,600V,20Amp H1-0653
SCR/SSR
EC-SCR
SCR Elect. Heat controller, 600V, 1ph, 45A
H1-2064
EC-SSR
SSR Elect. Heat controller, 600V, 1ph, 45A
H1-2082
ECM Motor Wiring harness
EC-HARNESS1 Wiring Harness, Card to ECM. 16 Pin H1-1104
EC-HARNESS2 Wiring Harness Power to Motor. 5 Pin H1-1101
EC-HARNESS3 0-10 VDC wiring harness, 2 Pin H1-1921
EC-HARNESS4 0-10 VDC wiring harness, 4 Pin, 2W H1-1921A
0-10 VDC wiring harness, 4 Pin, 4W H1-1921H
Transformers
EC-TRANS120A Transformer 120V,24V,50VA H1-0692
EC-TRANS208A Transformer 208-240V,24V,50VA H1-0685
EC-TRANS277A Transformer 277V,24V,50VA H1-0674
EC-TRANS480A Transformer 480V,24V,50VA H1-0686
EC-TRANS2424 Isolation Transformer 24V,24V,50VA H1-0673
EC-TRANSB Transformer 120V/208/240/480 to
24V,75VA H1-0689
EC-TRANS277B Transformer 277V,24V,75VA H1-0677
MISC
EC-AFSW Airflow Switch H1-0236A
EC-AFSWPB Airflow Switch Probe 4" H1-0242
EC-AFSWPBL Airflow Switch Probe 6" H1-1924
EC-AUTOLMTSW Auto Temp. LMT Switch H1-0006
EC-MANLMTSW Manual Temp. LMT Switch H1-0805
EC-FANRELAY Fan Relay 24V H1-0666
ELECTRIC CONTROLS - Transformers
Code Description Part Number
V2072
V2073
V2074
V2075
V2076
120 to 24 v. 40VA - foot mount
- 4" x 4" elec. box
208/240 to 24 v. 40VA - foot mount
277 to 24 v. 40VA - foot mount
24 to 24 v. 50VA - foot mount
H1-0669
H1-0671
H1-0675
H1-0673
RAPP Code Description Part Number
BLW10x10R Blower 10x10R H1-0904X
BLW10x10T Blower 10x10T H1-0903X
BLW10x4R Blower 10x4R H1-0906X
BLW10x6R Blower 10x6R H1-0905AX
BLW11x4R Blower 11x4R H1-2427X
BLW9x4T Blower 9x4T H1-1809
BLW9x7R Blower 9x7R H1-0900X
BLW9x7T Blower 9x7T H1-0902AX
BLW9x9R Blower 9x9R H1-1983X
BLW35S1E Blower for 35S(ST) Size 1
ECM Mtr
H1-2361,
H1-2361A,
& H1-2361B
BLW35S3P Blower for 35S(ST) Size 3
PSC Mtr
H1-0900ZX
BLW37S1 Wheel-Housing for 3S(ST)
Size 1 ECM
H1-2361B
BLW37S2E Blower for 37S(ST) Size 2
ECM Mtr
H1-2902AX
BLW35N3 Blower for 35N Size 3
ECM-PSC Mtr
H1-0900ZX
BLW33S10A Blower for 33SZ Size 10
ECM LH-CW
H1-2119
BLW33S10B Blower for 33SZ Size 10
ECM RH-CCW
H1-2120
BLW38S-38F1A Blower for 38S Size 1 ECM
Mtr OL
H1-2134
BLW38S-38F1B Blower for 38S Size 1 ECM
Mtr OR
H1-2135
BLOWERS AND WHEELS

Nailor Industries, Inc. reserves the right to change any information concerning product or specification without notice or obligation.
FILTERS
Page 6 of 10 7-6-23 IOM-FPTU
Model Series Fan Powered Terminal Units Replacement Parts
Model 35S Basic Unit Top Inlet
Unit
Size RAPP Code Description Part Number
1, 2 VH1-0196 Filter 1" 14x16 H1-0196
VH1-0196A Filter 1" MERV8 14x16 H1-0196A
3VH1-0199 Filter 1" 16x16 H1-0199
VH1-1810 Filter 1" MERV8 16x16 H1-1810
4,5 VH1-0979 Filter 1" 16x25 H1-0979
Filter 1" MERV8 16x25 H1-3108
6VH1-0200 Filter 1" 18x28 H1-0200
Filter 1" MERV8 18x28 H1-0200A
7 (2) VH1-0979 Filter 1" 16x25 H1-0979
Filter 1" MERV8 16x25 H1-3108
Model 35SST Stealth
Unit
Size RAPP Code Description Part Number
1, 2 VH1-0974 Filter 1" 10x14 H1-0974
VH1-2055 Filter 1" MERV8 10x14 H1-2055
3VH1-0977 Filter 1" 12x18 H1-0977
VH1-1966A Filter 1" MERV8 12x18 H1-1966A
4VH1-0196 Filter 1" 14x16 H1-0196
VH1-0196A Filter 1" MERV8 14x16 H1-0196A
5VH1-0975 Filter 1" 14x18 H1-0975
VH1-1434A Filter 1" MERV8 14x18 H1-1434A
6VH1-0197 Filter 1" 18x19 H1-0197
VH1-0197A Filter 1" MERV8 18x19 H1-0197A
7 (2) VH1-0928 Filter 1" 14x14 H1-0928
Filter 1" MERV7 14x14 H1-1996
Model 35S Basic Unit Side Inlet & Q Boot option
Unit
Size RAPP Code Description Part Number
1, 2 VH1-0998 Filter 1" 10x12 H1-0998
VH1-0998A Filter 1" MERV8 10x12 H1-0998A
3VH1-0196 Filter 1" 14x16 H1-0196
VH1-0196A Filter 1" MERV8 14x16 H1-0196A
4,5 VH1-0199 Filter 1" 16x16 H1-0199
VH1-1810 Filter 1" MERV8 16x16 H1-1810
6VH1-1529 Filter 1" 17x18 H1-1529
VH1-1529A Filter 1" MERV8 17x18 H1-1529A
7
(2)
VH1-0196 Filter 1" 14x16 H1-0196
VH1-0196A Filter 1" MERV8 14x16 H1-0196A
Model 37S Basic Unit
Unit
Size RAPP Code Description Part Number
1VH1-0997 Filter 1" 8x10 H1-0997
VH1-0997A Filter 1" MERV8 8x10 H1-0997A
2,3 VH1-0203 Filter 1" 10x18 H1-0203
VH1-2056 Filter 1" MERV8 10x18 H1-2056
4 (2) VH1-0974 Filter 1" 10x14 H1-0974
VH1-2055 Filter 1" MERV8 10x14 H1-2055
Model 37SST Stealth
Unit
Size RAPP Code Description Part Number
1VH1-0201 Filter 1" 9x11 H1-0201
VH1-0201A Filter 1" MERV8 9x11 H1-0201A
2,3 VH1-0202 Filter 1" 11x12 H1-0202
VH1-2020 Filter 1" MERV8 11x12 H1-2020
4 (2) VH1-0974 Filter 1" 10x14 H1-0974
VH1-2055 Filter 1" MERV8 10x14 H1-2055
Model 35N Basic Unit & Q Boot Option
Unit
Size RAPP Code Description Part Number
2VH1-1282 Filter 1" 13x26 H1-1282
VH1-1282A Filter 1" MERV8 13x26 H1-1282A
3VH1-1283 Filter 1" 17x27 H1-1283
VH1-1283A Filter 1" MERV8 17x27 H1-1283A
5VH1-1284 Filter 1" 17x33 H1-1284
VH1-1284A Filter 1" MERV8 17x33 H1-1284A
6VH1-1285 Filter 1" 19x35 H1-1285
VH1-1285A Filter 1" MERV8 19x35 H1-1285A
Model 37N
Unit
Size RAPP Code Description Part Number
2VH1-2254A Filter 1" 11x14 H1-2254A
VH1-2255A Filter 1" MERV8 11x14 H1-2255A
3VH1-2254B Filter 1" 11x18 H1-2254B
VH1-2255B Filter 1" MERV8 11x18 H1-2255B
4VH1-2254C Filter 1" 11x21 H1-2254C
VH1-2255C Filter 1" MERV8 11x21 H1-2255C
Model Series 35SXC
Unit
Size RAPP Code Description Part Number
1Filter 1" 6x14 H1-3457
Filter 1" MERV8 6x14
3Filter 1" 6x18 H1-2901
Filter 1" MERV8 6x18
5Filter 1" 12x20 H1-2902
Filter 1" MERV8 10x20

Nailor Industries, Inc. reserves the right to change any information concerning product or specification without notice or obligation.
7-6-23 IOM-FPTU Page 7 of 10
Model 35S(ST)
Unit
Size RAPP Code Description Part Number Program
1 MTR35SECMS1 ECM Motor 35S(ST), Size 1, 120-277V H1-2267A 35S_Size1_ALL_R3
2 MTR35SECMS2 ECM Motor 35S(ST), Size 2, 120-277V H1-2267A 35S_Size2_ALL
3 MTR35SECMS3 ECM Motor 35S(ST), Size 3, 120-277V H1-2269A 35S_3ADSR
4 MTR35SECMS4 ECM Motor 35S(ST), Size 4, 120-277V H1-2269A 35S_4ADSR
5 MTR35SECMS5 ECM Motor 35S(ST), Size 5, 120-277V H1-2270A 35S_5ADSR
6 MTR35SECMS6 ECM Motor 35S(ST), Size 6, 120-277V H1-2271A 35S_6ADSR
7 MTR35SECMS7 ECM Motor 35S(ST), Size 7, 120-277V H1-2270A 35S_7ADSR
Model 35N
Unit
Size RAPP Code Description Part Number Program
2 MTR35NECMS2 ECM Motor 35N, Size 2, 120-277V H1-2267A 35N_Size2_ALL_E
3 MTR35NECMS3 ECM Motor 35N, Size 3, 120-277V H1-2267A 35N_Size3_ALL_E
5 MTR35NECMS5 ECM Motor 35N, Size 5, 120-277V H1-2270A 35N_Size5_ALL_E
6 MTR35NECMS6 ECM Motor 35N, Size 6, 120-277V H1-2270A 35N_Size6_ALL_E
Model Series 35SXC
Unit
Size RAPP Code Description Part Number Program
1 MTR35XECMS1A V4 H1-3146 35S(ST_XC)_1_120V.ECM
1 MTR35XECMS1B V5A,V5B,V6 H1-3145 35S(ST_XC)_1_277V.ECM
3 MTR35XECMS3 V4,V5A,V5B,V6 H1-3098 35SXC-3 HEB.ECM_Application
5 MTR35XECMS5 V4,V5A,V5B,V6 H1-3099 35SXC-3 HEB.ECM_Application
Model 37S(ST)
Unit
Size RAPP Code Description Part Number Program
1 MTR37SECMS1A ECM Motor 37S(ST), Size 1, 120-277V H1-2706 37S_Size1_All_R2
2 MTR37SECMS2A ECM Motor 37S(ST), Size 2, 120V H1-2706 37S_Size2_120
2 MTR37SECMS2B ECM Motor 37S(ST), Size 2, 208-277V H1-2705 37S_Size2_277
3 MTR37SECMS3 ECM Motor 37S(ST), Size 3, 120-277V H1-2269U 37S_Size3_All_R2
4 MTR37SECMS4 ECM Motor 37S(ST), Size 4, 120-277V H1-2267A 37S_Size4_All_R2
Model 37N
Unit
Size RAPP Code Description Part Number Program
2 MTR37NECMS2 ECM Motor 37N, Size 2, 120-277V H1-2267A 37N_2ADS2
3 MTR37NECMS3 ECM Motor 37N, Size 3, 120-277V H1-2267A 37N_3ADSR
4 MTR37NECMS4 ECM Motor 37N, Size 4, 120-277V H1-2269U 37N_Size4_ALL_R2
EPIC ECM MOTORS
Model Series Fan Powered Terminal Units Replacement Parts

Nailor Industries, Inc. reserves the right to change any information concerning product or specification without notice or obligation.
Model 35S(ST)
Unit Size RAPP Code Description Part Number Capacitor
1,2 MTR35SPSCS1A PSC 35S, Size 1&2, 1/10 HP, 120V+Cap H1-2584 H1-0875
1,2 MTR35SPSCS1B PSC 35S, Size 1&2, 1/10 HP, 208V+Cap H1-2585 H1-0875
1,2 MTR35SPSCS1C PSC 35S, Size 1&2, 1/10 HP, 277V+Cap H1-2586 H1-0875
3 MTR35SPSCS3A PSC 35S, Size 3, 1/4 HP, 120V+Cap H1-2590S H1-0878
3 MTR35SPSCS3B PSC 35S, Size 3, 1/4 HP, 208V+Cap H1-2591S H1-0878
3 MTR35SPSCS3C PSC 35S, Size 3, 1/4 HP, 277V+Cap H1-2592S H1-0878
4 MTR35SPSCS4A PSC 35S, Size 4, 1/3 HP, 120V+Cap H1-2593 H1-0877
4 MTR35SPSCS4B PSC 35S, Size 4, 1/3 HP, 208V+Cap H1-2594 H1-0876
4 MTR35SPSCS4C PSC 35S, Size 4, 1/3 HP, 277V+Cap H1-2595 H1-0876
5,7 MTR35SPSCS5A PSC 35S, Size 5&7, 1/2 HP, 120V+Cap H1-2596S H1-0877
5,7 MTR35SPSCS5B PSC 35S, Size 5&7, 1/2 HP, 208V+Cap H1-2597S H1-0876
57 MTR35SPSCS5C PSC 35S, Size 5&7, 1/2 HP, 277V+Cap H1-2598S H1-0876
6 MTR35SPSCS6A PSC 35S, Size 6, 3/4 HP, 120V+Cap H1-2599 H1-0877
6 MTR35SPSCS6B PSC 35S, Size 6, 3/4 HP, 208V+Cap H1-2600 H1-0877
6 MTR35SPSCS6C PSC 35S, Size 6, 3/4 HP, 277V+Cap H1-2601 H1-0877
Model 35N
Unit Size RAPP Code Description Part Number Capacitor
2 MTR35NPSCS2A PSC 35N, Size 2, 1/10 HP, 120V+Cap H1-2584 H1-0875
2 MTR35NPSCS2B PSC 35N, Size 2, 1/10 HP, 208V+Cap H1-2585 H1-0875
2 MTR35NPSCS2C PSC 35N, Size 2, 1/10 HP, 277V+Cap H1-2586 H1-0875
3 MTR35NPSCS3A PSC 35N, Size 3, 1/4 HP, 120V+Cap H1-2590S H1-0878
3 MTR35NPSCS3B PSC 35N, Size 3, 1/4 HP, 208V+Cap H1-2591S H1-0878
3 MTR35NPSCS3C PSC 35N, Size 3, 1/4 HP, 277V+Cap H1-2592S H1-0878
5 MTR35NPSCS5A PSC 35N, Size 5, 1/2 HP, 120V+Cap H1-2596S H1-0877
5 MTR35NPSCS5B PSC 35N, Size 5, 1/2 HP, 208V+Cap H1-2597S H1-0876
5 MTR35NPSCS5C PSC 35N, Size 5, 1/2 HP, 277V+Cap H1-2598S H1-0876
6 MTR35NPSCS6A PSC 35N, Size 6, 3/4 HP, 120V+Cap H1-2599 H1-0877
6 MTR35NPSCS6B PSC 35N, Size 6, 3/4 HP, 208V+Cap H1-2600 H1-0877
6 MTR35NPSCS6C PSC 35N, Size 6, 3/4 HP, 277V+Cap H1-2601 H1-0877
Model 37S(ST)
Unit Size RAPP Code Description Part Number Capacitor
2 MTR37SPSCS2A PSC 37S, Size 2, 1/6 HP, 120V+Cap H1-2589S H1-0875
2 MTR37SPSCS2B PSC 37S, Size 2, 1/6 HP, 208V+Cap H1-2588 H1-0875
2 MTR37SPSCS2C PSC 37S, Size 2, 1/6 HP, 277V+Cap H1-2587 H1-0875
3&4 MTR37SPSCS3A PSC 37S, Size 3&4, 1/4 HP, 120V+Cap H1-2590S H1-0878
3&4 MTR37SPSCS3B PSC 37S, Size 3&4, 1/4 HP, 208V+Cap H1-2591S H1-0878
3&4 MTR37SPSCS3C PSC 37S, Size 3&4, 1/4 HP, 277V+Cap H1-2592S H1-0878
Model 37N
Unit Size RAPP Code Description Part Number Capacitor
2 MTR37NPSCS2A PSC 37N, Size 2, 1/6 HP, 120V+Cap H1-2589S H1-0875
2 MTR37NPSCS2B PSC 37N, Size 2, 1/6 HP, 208V+Cap H1-2588 H1-0875
2 MTR37NPSCS2C PSC 37N, Size 2, 1/6 HP, 277V+Cap H1-2587 H1-0875
3 MTR37NPSCS3A PSC 37N, Size 3, 1/4 HP, 120V+Cap H1-2590S H1-0878
3 MTR37NPSCS3B PSC 37N, Size 3, 1/4 HP, 208V+Cap H1-2591S H1-0878
3 MTR37NPSCS3C PSC 37N, Size 3, 1/4 HP, 277V+Cap H1-2592S H1-0878
4 MTR37NPSCS4A PSC 35N, Size 4, 1/2 HP, 120V+Cap H1-2596S H1-0877
4 MTR37NPSCS4B PSC 35N, Size 4, 1/2 HP, 208V+Cap H1-2597S H1-0876
4 MTR37NPSCS4C PSC 35N, Size 4, 1/2 HP, 277V+Cap H1-2598S H1-0876
TERMINAL UNIT PARTS
FAN POWERED TERMINAL UNIT EPIC ECM MOTORS
PSC MOTORS
Model Series Fan Powered Terminal Units Replacement Parts
Page 8 of 10 7-6-23 IOM-FPTU

Nailor Industries, Inc. reserves the right to change any information concerning product or specification without notice or obligation.
7-6-23 IOM-FPTU Page 9 of 10
Model 37SW(ST)
Unit
Size RAPP Code Description Part
Number
1 V37SHWC11 HW Coil 37S 1 Row, Size 1 H1-0091
2,3 V37SHWC13 HW Coil 37S 1 Row, Size 2,3 H1-0094
4 V37SHWC14 HW Coil 37S 1 Row, Size 4 H1-0097
1 V37SHWC21 HW Coil 37S 2 Row, Size 1 H1-0092
2,3 V37SHWC23 HW Coil 37S 2 Row, Size 2,3 H1-0095
4 V37SHWC24 HW Coil 37S 2 Row, Size 4 H1-0098
1 V37SHWC31 HW Coil 37S 3 Row, Size 1 H1-0093
2, 3 V37SHWC33 HW Coil 37S 3 Row, Size 2,3 H1-0096
4 V37SHWC34 HW Coil 37S 3 Row, Size 4 H1-0099
Model 35SXCW
Model 37NW
Unit
Size RAPP Code Description Part
Number
2 V37NHWC12 HW Coil 37N 1 Row, Size 2 H1-2163
3 V37NHWC13 HW Coil 37N 1 Row, Size 3 H1-2165
4 V37NHWC14 HW Coil 37N 1 Row, Size 4 H1-2167
2 V37NHWC22 HW Coil 37N 2 Row, Size 2 H1-2164
3 V37NHWC23 HW Coil 37N 2 Row, Size 3 H1-2166
4 V37NHWC24 HW Coil 37N 2 Row, Size 4 H1-2168
Model 35SW(ST)
Unit
size RAPP code Description Part
Number
1,2 V35SHWC12 HW Coil 35S 1 Row, Size 1,2 H1-0986
3 V35SHWC13 HW Coil 35S 1 Row, Size 3 H1-0987
4,5 V35SHWC15 HW Coil 35S 1 Row, Size 4,5 H1-0988
6 V35SHWC16 HW Coil 35S 1 Row, Size 6 H1-0989
7 V35SHWC17 HW Coil 35S 1 Row, Size 7 H1-0055
1,2 V35SHWC22 HW Coil 35S 2 Row, Size 1,2 H1-0925
3 V35SHWC23 HW Coil 35S 2 Row, Size 3 H1-0926
4,5 V35SHWC25 HW Coil 35S 2 Row, Size 4,5 H1-0927
6 V35SHWC26 HW Coil 35S 2 Row, Size 6 H1-0990
7 V35SHWC27 HW Coil 35S 2 Row, Size 7 H1-0056
1,2 V35SHWC32 HW Coil 35S 3 Row, Size 1,2 H1-0942
3 V35SHWC33 HW Coil 35S 3 Row, Size 3 H1-0943
4,5 V35SHWC35 HW Coil 35S 3 Row, Size 4,5 H1-0944
6 V35SHWC36 HW Coil 35S 3 Row, Size 6 H1-0945
7 V35SHWC37 HW Coil 35S 3 Row, Size 7 H1-1038
WATER COILS
Model Series Fan Powered Terminal Units Replacement Parts
Model 35NW
Unit
Size RAPP Code Description Part
Number
2 V35NHWC12 HW Coil 35N 1 Row, Size 2 H1-1251
3 V35NHWC13 HW Coil 35N 1 Row, Size 3 H1-1254
5 V35NHWC15 HW Coil 35N 1 Row, Size 5 H1-1257A
6 V35NHWC16 HW Coil 35N 1 Row, Size 6 H1-1260
2 V35NHWC22 HW Coil 35N 2 Row, Size 2 H1-1252
3 V35NHWC23 HW Coil 35N 2 Row, Size 3 H1-1255
5 V35NHWC25 HW Coil 35N 2 Row, Size 5 H1-1258
6 V35NHWC26 HW Coil 35N 2 Row, Size 6 H1-1261
2 V35NHWC32 HW Coil 35N 3 Row, Size 2 H1-1253
3 V35NHWC33 HW Coil 35N 3 Row, Size 3 H1-1256
5 V35NHWC35 HW Coil 35N 3 Row, Size 5 H1-1259
6 V35NHWC36 HW Coil 35N 3 Row, Size 6 H1-1262
Unit
size RAPP code Description Part
Number
1 V35SHWC12 HW Coil 35S 1 Row, Size 1 H1-0986
3 V35SHWC13 HW Coil 35S 1 Row, Size 3 H1-0987
5 V35SHWC15 HW Coil 35S 1 Row, Size 5 H1-0988
1 V35SHWC22 HW Coil 35S 2 Row, Size 1 H1-0925
3 V35SHWC23 HW Coil 35S 2 Row, Size 3 H1-0926
5 V35SHWC25 HW Coil 35S 2 Row, Size 5 H1-0927
1 V35SHWC32 HW Coil 35S 3 Row, Size 1 H1-0942
3 V35SHWC33 HW Coil 35S 3 Row, Size 3 H1-0943
5 V35SHWC35 HW Coil 35S 3 Row, Size 5 H1-0944
RAPP
Code Description Part
Number
EC-FSBLK1PA Fuseblock, 1P, 250V, 30A H1-0016
EC-FSBLK1PB Fuseblock, 1P, 250V, 60A H1-0263
EC-FSBLK1PC Fuseblock, 1P, 600V, 30A H1-0973
EC-FSBLK1PD Fuseblock, 1P, 600V, 60A H1-0269A
EC-FSBLK2PA Fuseblock, 2P, 250V, 30A H1-0920
EC-FSBLK2PC Fuseblock, 2P, 600V, 30A H1-0264
EC-FSBLK2PD Fuseblock, 2P, 600V, 60A H1-0269B
EC-FSBLK3PA Fuseblock, 3P, 250V, 30A H1-0265
EC-FSBLK3PB Fuseblock, 3P, 250V, 60A H1-0266
EC-FSBLK3PC Fuseblock, 3P, 600V, 30A H1-0268
EC-FSBLK3PD Fuseblock, 3P, 600V, 60A H1-0269
EC-FUS250V15 Fuse, 250V, 15A H1-0320A
EC-FUS250V20 Fuse, 250V, 20A H1-0321A
EC-FUS250V25 Fuse, 250V, 25A H1-0322A
EC-FUS250V30 Fuse, 250V, 30A H1-0323A
EC-FUS250V35 Fuse, 250V, 35A H1-0324A
EC-FUS250V40 Fuse, 250V, 40A H1-0325A
EC-FUS250V45 Fuse, 250V, 45A H1-0326A
EC-FUS250V50 Fuse, 250V, 50A H1-0327A
EC-FUS250V60 Fuse, 250V, 60A H1-0328A
EC-FUS600V15 Fuse, 600V, 15A H1-0329A
EC-FUS600V20 Fuse, 600V, 20A H1-0330A
EC-FUS600V25 Fuse, 600V, 25A H1-0331A
EC-FUS600V30 Fuse, 600V, 30A H1-0332A
EC-FUS600V35 Fuse, 600V, 35A H1-0333A
EC-FUS600V40 Fuse, 600V, 40A H1-0334A
EC-FUS600V45 Fuse, 600V, 45A H1-0335A
EC-FUS600V50 Fuse, 600V, 50A H1-0336A
EC-FUS600V60 Fuse, 600V, 60A H1-0337A
FUSE/FUSE BLOCKS

www.nailor.com
"Complete Air Control and Distribution Solutions."
Houston, Texas
Tel: 281-590-1172
Fax: 281-590-3086
Las Vegas, Nevada
Tel: 702-648-5400
Fax: 702-638-0400
Toronto, Canada
Tel: 416-744-3300
Fax: 416-744-3360
Calgary, Canada
Tel: 403-279-8619
Fax: 403-279-5035
Page 10 of 10 7-6-23 IOM-FPTU