SAR IAQ Room Sensors
Specification and Installation Instructions
SAR-170524-ESA.docx Page | 1
Models
SAR24GH
with humidity and CO2sensor
SAR24GV
with CO2and VOC sensor
Features
CO2sensor feedback output (AO1)
CO2warning and alarm level outputs (BO1 and BO2)
Humidity or VOC sensor feedback output (AO2)
Input voltage 24Vac or 24Vdc
SAR24GH/SAR24GV
Technical Specifications
Description SAR24GH/SAR24GV
Humidity Sensor (SAR24GH)
Sensor range 5 to 95% RH
Display resolution 0.1% RH
CO2Sensor (SAR24GH and SAR24GV)
Operating principle Self-calibrating, Non-Dispersive Infrared (NDIR)
Sensor range 400 to 2000 ppm
Accuracy ±30 ppm ±3% of reading (Accuracy is defined after minimum 3 weeks of continuous operation)
Response time 2 minutes by 90%
VOC Sensor (SAR24GV)
Operating principle Self-calibrating, Non-Dispersive Infrared (NDIR)
Sensor range 0-1000 ppb isobutylene equivalent tVOCs
Response time < 5 seconds for tVOC
Start up time 15 minutes
Other
Outputs 2 Binary outputs (BO1 and BO2), dry contracts 24Vac, 1A max 3A in-rush
2 Analog outputs (0 to 10Vdc)
Electrical connection 0.8 mm
[18 AWG] minimum
Operating temperature 0ºC to 50ºC [32ºF to 122ºF]
Storage temperature -30ºC to 50ºC [-22ºF to 122ºF]
Relative humidity 5 to 95 % non-condensing
Enclosure protection IP 30 (EN 60529)
Weight 80 g. [0.2 lb]
Dimensions
A = 2.85” | 73mm
B = 4.85” | 123mm
C = 1.00” | 24mm
D = 2.36” | 60mm
E = 3.27” | 83mm
B
C
D
E