NHP TemBreak PRO User manual

Version
1.1.0
NHP Electrical Engineering Products
AU 1300 NHP NHP
NZ 0800 NHP NHP
nhp.com.au
nhp-nz.com
B Model Moulded Case CircuitBreaker
Basic Electronic Trip Unit from 250A up to1600A
USER MANUAL

2
TemBreak PRO B_BE-UM-001-EN V1.1.0
Using this manual
Safety Precautions
Authorised Personnel Only
The product or system described in this documentation must be installed, operated and maintained by qualified personnel only. NHP or Terasaki accept no
responsibility for the consequences of the use of this equipment by unqualified personnel.
A qualified person is one with the necessary skills and knowledge of the construction and operation of the installation of electrical equipment and has been
trained to identify and avoid risks.
Appropriate use of NHP / Terasaki products
NHP / Terasaki products are intended to be used only for the applications described in the catalogue and technical documentation, which is dedicated to
them. If products and components from other manufacturers are used, they must be recommended or approved by NHP or Terasaki.
Appropriate use of NHP / Terasaki products during transport, storage, installation, assembly, commissioning, operation and maintenance is necessary to
ensure safe operation and without any problems.
The permissible ambient conditions must be met. The information contained in the technical documentation must be observed.
Publication of responsibility
The contents of this document have been reviewed to ensure that the reliability of the information is correct at time of publication.
NHP or Terasaki are not responsible for printing or damage resulting from errors. NHP or Terasaki reserve the right to make corrections and changes
needed in subsequent edition.
Warnings and notes
This documentation contains safety instructions that you must follow for your personal safety and to prevent damage to property.
Safety instructions, referring to your personal safety are reported in the literature by a safety alert symbol.
Safety warning symbols and the words below are classified according to the degree of risk.
WARNING: Indicates an imminently hazardous situation which, if it cannot be avoided, will result in death or
serious injury.
WARNING: Indicates a potentially hazardous situation which, if it cannot be avoided, can result serious injury or
death.
WARNING: Indicates a potentially hazardous situation which, if it cannot be avoided, may cause minor or
moderate injury.
Notice: Indicates a warning of property damage and can also indicate important operating and especially useful
information on the product, that it should pay particular attention to efficient and safe operation.

3
TemBreak PRO B_BE-UM-001-EN V1.1.0
Summary of Changes
This section highlights the details of changes made since the previous issue of this document.
The versioning convention used to track changes in this document follows the structure Vx.y.z where:
x: Major revision, where extensive changes are made which is generally incompatible with the previous version. Such changes may include new
products and/or features, or removal of information which is no longer relevant or applicable to the previous version
y: Minor revision, where changes made do not change the overall scope of the previous version, but may include additional information which
complements or corrects the previous version, or provides additional clarity on an existing topic.
z: Patch version, where small changes are made to correct minor errors or adjust existing text, charts, figures and/or images, and which do not
add or remove information from the previous version. Example changes may include spelling corrections, image re-sizing and adjustments,
updated images, etc.
Version
Publication date
Changes
By
V 1.0.0
3-May-2021
Initial release
D.NAT
V 1.1.0
28-May-2021
Correction to Product Information tables, rewording to Watts Loss tables, Label Identification section
added, typo in Temperature Rating tables removed and aligned headings with TD-001-EN,
added references and links to,
TD-001-EN, TD-002-EN, TD-003-EN, & Type2_TBpro_MotorStartTables-TD-001-EN
N.ALEX

4
TemBreak PRO B_BE-UM-001-EN V1.1.0
Table of Contents
Using this manual 2
Safety Precautions 2
Summary of Changes 3
Table of Contents 4
Introduction 5
Who Should Use This Manual? 5
Additional resources 5
Terminology and Abbreviations 6
Product Information 7
Part Number Break Down 8
Available MCCBs in the TemBreak PRO range 9
Label Identification 10
B250_BE & B400_BE Information 11
B800_BE Information 12
B1000_BE & B1250_BE Information 13
B1600_BE Information 14
Internal Accessories 15
Auxiliary & Alarm Switches 15
Auxiliary Contact 15
Alarm Contact 15
Shunt Trip 16
Under Voltage Trips 16
Plugs and Ports 17
Installation 18
Precautions 18
Mounting Angles 18
Direction of Power Supply 18
Clearances 19
Internal Accessory Mounting Locations 21
B250 internal accessories combination 21
B400 internal accessories combination 22
B800 & B1000 internal accessories combination 23
B1250 & B1600 internal accessories combination 24
Alarm, Shunt & UVT Installation 25
Alarm & Auxiliary installation 25
Shunt & UVT installation 26
Protection Settings 27
Trip Curve 27
Pre-Defined Curves 28
Long Time Delay Protection (LTD) 29
Adjusting Ir(Current) 29
Adjusting tr(Time Delay) 30
Short Time Delay Protection (STD) 31
Adjustment Isd (Current) 31
Adjusting tsd (Time Delay) 32
Instantaneous Protection (INST) 33
Adjusting Ii(Current) 33
Ground/Earth Fault Protection (GF) 34
Neutral Protection (NP) 35
Alarms & Indication 36
PTA (Pre-Trip Alarm) 37
Power supply requirement 37
Connections and contact specification 38
Commissioning 39
LTD Adjustments (Ir) 39
Pre-Defined Curve Selection 40
INST Protection Only Setting 41
LSIG 3P –GF Protection Adjustments (Ig) 42
LSIG 4P –NP and GF Protection Adjustments (IN) 43
Troubleshooting 44
Annex A –Dimensions 45
B250P 45
B400P / R 47
B800N / H / G 49
B800P / R 51
B1000N / H 53
B1250N / H / HL 55
B1600N / HL 57
Annex B - Time Current Curves 59
B250_BE –In40 A 59
B250_BE –In125 A 62
B250_BE –In250 A 65
B400_BE –In250 A 68
B400_BE –In400A 71
B800_BE –In630 A 74
B800_BE –In800 A 77
B1000_BE –In1000 A 80
B1250_BE –In1250 A 83
B1600_BE –In1600 A 86
Annex C - I2t Let-Through Curves 89
B250P 89
B400P / R 90
B800N / H / G 91
B800P / R 92
B1000N / H 93
B1250N / H / HL 94
B1600N / HL 95
Annex D - Peak Let-through Curves 96
B250P 96
B400P / R 97
B800N / H / G 98
B800P / R 99
B1000N / H 100
B1250N / H / HL 101
B1600N / HL 102
Annex E –Watts Loss 103
Impedance Watts Loss 103
Annex F –Temperature Ratings Tables 104

5
TemBreak PRO B_BE-UM-001-EN V1.1.0
Introduction
This user manual describes the TemBreak PRO B Model Basic Electronic (B_BE) MCCB’s MCCB features and instructions for use, and provides
information for commissioning and configuring.
Some additional features may require the use of additional products and accessories to achieve full utilization of that feature. Refer the respective User
Manual in the TemBreak PRO series for additional information on the respective product.
Who Should Use This Manual?
This manual aims to provide users, electricians, panel builders and maintenance personnel, with the technical information required for commissioning and
operation of the NHP / Terasaki TemBreak PROB_BE MCCB.
Users of this document must have at minimum a basic understanding of electrical circuit protection topics including (but not limited to):
-
Power distribution and reticulation
-
Circuit protection devices
-
Fault currents
-
Arc faults
-
Temperature rise and thermal derating of switchgear
Additional resources
The following resources contain additional information which should be read in conjunction with this document.
Resource
Description
NHP/Terasaki TemBreak PRO B_BE Installation
Instructions
B250_3_BE-IN-001-EN
B250_4_BE-IN-001-EN
B400_3_BE-IN-001-EN
B400_4_BE-IN-001-EN
B800_3_BE-IN-001-EN
B800_4_BE-IN-001-EN
B1000_3_BE-IN-001-EN
B1000_4_BE-IN-001-EN
B1250_3_BE-IN-001-EN
B1250_4_BE-IN-001-EN
B1600_3_BE-IN-001-EN
B1600_4_BE-IN-001-EN
Information on installing, mounting, and wiring the TemBreak PRO B Model Basic
Electronic MCCB.
COMING SOON
Technical Data –Temperature and Watts Loss
TBP-TD-001-EN
Temperature and Watts Loss tables for TemBreak PRO Moulded Case Circuit Breakers.
Technical Data –Cascading and Selectivity
TBP-TD-002-EN
Cascading and Selectivity tables for TemBreak PRO Moulded Case Circuit Breakers with
Din-T, Din-Safe, & MOD6 MCBs/RCBOs
Technical Data –Coordination
TBP-TD-003-EN
Socomec Backup Tables with TemBreak PRO Moulded Case Circuit Breakers
Technical Data –Type 2 Coordination
Type2_TBpro_MotorStartTables-TD-001-EN
Type 2 Coordination for Premium Efficiency Motor Starters with TemBreak PRO Moulded
Case Circuit Breakers
Notice: Not all MCCBs in the TemBreak PRO series are identical. This document specifically covers the B_BE
series MCCB only. Refer to the respective TemBreak PRO User Manual (e.g. B_SE, P_SE, etc.) for information
and instructions on other models in the TemBreak PRO range.

Introduction
6
TemBreak PRO B_BE-UM-001-EN V1.1.0
Terminology and Abbreviations
Abbreviation
Description
Abbreviation
Description
ACP
Auxiliary Communications port: Plug for Smart auxiliary /
alarm contact block
MIP
Maintenance Interface Port: Plug for temporary
connection to OCR testing, servicing, and maintenance
tools
AL
Alarm: An auxiliary contact indicating trip status
N
Neutral
ASCII
American Standard Code for Information Interchange
NP
Neutral Protection
AX or AUX
Auxiliary: Auxiliary contact indicating open / closed
OAC
Optional Alarm Contact: Connection connector optional
alarm output contact
BE
Basic Electronic Trip Unit (dial type, LSI and LSIG)
OCR
Over Current Relay
CCW
Connected Components Workbench software
P or PTA
Pre-trip Alarm
CIP 1 2
1Communication Interface Port: Plug for control power
and data for use with the TPED remote display and
TPCM communication module
2Common Industrial Protocol
PDU
Protocol Data Unit
CRC
Cyclic Redundancy Check –error-detecting code used at
the end of each Modbus message
PELV
Protected Extra Low Voltage (earthed system)
dec
Decimal (base-10) numbering system
PTA
Pre-Trip Alarm: is a programmable output contact to
advise when a trip may be imminent.
DINT
Signed Double Integer datatype (4 bytes or 32 bits in
length)
RTU
Remote Terminal Unit
EIPM
TemBreak PRO Ethernet/IP Module
S or STD
Short Time Delay Protection
FF
Fixed Thermal and Fixed Magnetic
SE
Smart Energy Trip Unit
FM
Fixed Thermal and Adjustable Magnetic
SELV
Separated Extra Low Voltage
G or GF
Ground Fault Protection
SN
Solid Neutral
hex
Hexadecimal (base-16) numbering system
SSID
Service Set Identifier (name of the Wi-Fi wireless
network)
I or INST
Instantaneous Protection
STR
String datatype
IEC
International Electrotechnical Commission
TCP
Transmission Control Protocol
IEEE
Institute of Electrical and Electronics Engineers
TF
Adjustable Thermal and Fixed Magnetic
Ig
Ground Fault Protection Current
THD
Total Harmonic Distortion
Ii
Instantaneous Protection Current
TM
Adjustable Thermal Magnetic
In
Rated Current
TPCM
TemCom PRO Communication Module
IN
Neutral Protection Current
TPED
TemView PRO External Display
INT
Signed Integer datatype (2 bytes or 16 bits in length)
tr/ tR
LTD Time delay
IP
International Protection (Ingress Protection)
tsd
STD Time delay
Ir/ IR
LTD Protection Current
ttsp
Thermal Self-Protection Time delay
Isd
STD Protection Current
UDINT
Unsigned Integer (2 bytes or 16-bits in length)
Itsp
Thermal Self-Protection Current
UINT
Unsigned Integer (2 bytes or 16 bits in length)
L or LTD
Long Time Delay Protection
ULINT
Unsigned Long Integer datatype (8 bytes or 64 bits in
length)
LCD
Liquid Crystal Display (LCD)
URLs
Uniform Resource Locator (address of an Internet
website)
LED
Light Emitting Diode
WORD
2 bytes or 16-bits of data
LINT
Signed Long Integer datatype (8 bytes or 64 bits in
length)
ZSI
Zone Selective Interlocking (zone selectivity)
LSI
Long Time, Short Time and Instantaneous Protection
θ
Thermal imaging value
LSIG
Long Time, Short Time, Instantaneous and Ground Fault
Protection
θC
Cold start mode thermal imaging value
MCCB
Moulded Case Circuit Breaker
θH
Hot start mode thermal imaging value
microSD
Micro Secure Digital
θtrip
Thermal imaging value tripping threshold

7
TemBreak PRO B_BE-UM-001-EN V1.1.0
Product Information
Features
-Electronic overcurrent protection, for general & selectivity applications
-3 & 4 Pole
-Adjustable Long Time (Ir)
-Base current Iris adjustable from 40% - 100% of the nominal rated current In.
-Predefined LSI curves
250A: 8 characteristic curves
400A to 1600A: 10 characteristic curves,
-Instantaneous only
-Optional Adjustable Neutral Pole protection (OFF, 50%, 100%)
-Optional Ground Fault Trip on 400A to 1600A models (0.2 x In)
-Optional Pre-Trip Alarm
Ampere Frame Sizes
-B250
-B400
-B800
-B1000
-B1250
-B1600
Protection Functions
-Long Time Delay
-Short Time Delay (Predefined curves)
-Instantaneous (Predefined curves)
-Ground/Earth Fault (LSIG model)
-Neutral Protection (LSIG 4P model)
B_BE MCCB optional protection features
Rated (In)
Poles
Catalogue
number suffix
Ground/Earth Fault Protection
(GF)
Neutral Protection
(NP)
Pre-Trip Alarm
(PTA)
250 A
3P
*P
─
─
✓
4P
*P
─
─
✓
*N
─
✓
─
*PN
─
✓
✓
400…1600 A
3P
*P
─
─
✓
*G
✓
─
─
*PG
✓
─
✓
4P
*P
─
─
✓
*N
─
✓
─
*G
✓
✓
─
Additional Certificates

Product Information
8
TemBreak PRO B_BE-UM-001-EN V1.1.0
Part Number Break Down
P
160
F
2
4
160
BE
G
a)
b)
c)
d)
e)
f)
g)
h)
a) Model Type
A
Basic applications
(160…250 A)
P
Mid to advanced applications
(160…630 A)
B
High current, high kA applications
(160…1600 A)
ZS
Earth Leakage applications
(125…800 A)
XS
Highest current applications
(2000…3200 A)
b) Ampere Frame
125
A
160
A
250
A
400
A
630
A
800
A
1000
A
1250
A
1600
A
2000
A
2500
A
3200
A
c) Short Circuit Break Capacity Icu (kA)
R
200 kA
L
150 kA
P
125 kA
S
110 kA
G
100 kA
HL
85 kA
H
70 kA
M
65 kA
N
50 kA
F
36 kA
E
25 kA
D
Switch
d) Pole Pitch Size (mm) 1)
1
25
2
30
3
35
e) No. of Poles
1
6)
2
7)
3
4
f) Trip Unit Rating (In)
In
x A
g) Trip Unit Type
TF
Adj Thermal Fix Magnetic 3)
FF
Fix Thermal Fix Magnetic 3)
FM
Fix Thermal Adj Magnetic 8)
TM
Adj Thermal Adj Magnetic
SX
Smart Ammeter 4) 5)
BE
Basic Electronic 5)
SE
Smart Energy 5)
NN
Non-Auto Switch
h) Trip Unit Option
G
Ground Fault 2)
N
Neutral 2)
P
Pre-Trip Alarm 2)
SN
Solid Neutral 8)
1. 160AF only
2. For P_SE versions these features are standard and therefore are not added to the end of the part number.
3. Only available in A & ZS models
4. Only available in B models
5. Not available in A models
6. Only available in A and B models (FF Only Trip Unit)
7. Not available in A and B models (FF Only Trip Unit)
8. ZS Models
Notice: Not all combinations are possible. Confirm part number combination with NHP for availability.

Product Information
9
TemBreak PRO B_BE-UM-001-EN V1.1.0
Available MCCBs in the TemBreak PRO range
Rating
Short Circuit Break Capacity
(kA)
Frame Size
160
250
400
630
800
1000
1250
1600
2000
2500
3200
E
25
A160E –TF
A160E –FF
B160E –FF
A250E –TM
P400E-TM
P630E –TM
F
36
A160F –TF
P160F –FF
P160F –TM
P160F –BE
P160F –BEG
P160F –SE
A250F –TM
P250F –TM
P250F –BE
P250F –BEG
P250F –SE
P400F –TM
P400F –BE
P400F –BEG
P400F –SE
P630F –TM
P630F –BE
P630F –BEG
P630F –SE
B800F –TM
N
50
P160N –TM
P160N –BE
P160N –BEG
P160N –SE
P250N –TM
P250N –BE
P250N –BEG
P250N –SE
P400N –TM
P400N –BE
P400N –BEG
P400N –SE
P630N –TM
P630N –BE
P630N –BEG
P630N –SE
B800N –TM
B800N –BE
B800N –SX
B800N –SE
B1000N –BE
B1000N –SX
B1000N –SE
B1250N –BE
B1600N –BE
H
70
P160H –TM
P160H –BE
P160H –BEG
P160H –SE
P250H –TM
P250H –BE
P250H –BEG
P250H –SE
P400H –TM
P400H –BE
P400H –BEG
P400H –SE
P630H –TM
P630H –BE
P630H –BEG
P630H –SE
B800H –TM
B800H –BE
B800H –SX
B800H –SE
B1000H –BE
B1000H –SX
B1000H –SE
B1250H –BE
HL
85
B1250HL –BE
B1600HL –BE
XS2000HL –BE
XS2500HL –BE
XS3200HL –BE
G
100
B800G –TM
B800G –BE
B800G –SX
B800G –SE
S
110
P400S –TM
P400S –BE
P400S –BEG
P400S –SE
P630S –TM
P630S –BE
P630S –BEG
P630S –SE
P
125
B160P –TM
B250P –TM
B250P –BE
B250P –SE
B400P –BE
B800P –BE
B800P –SX
B800P –SE
R
200
B160R –TM
B250R –TM
B400R –BE
B800R –BE
B800R –SX
B800R –SE
D
Switch
A160D –NN
P160D –NN
A250D –NN
P250D –NN
P400D –NN
P630D –NN
B800D –NN
B1000D –NN
B1250D –NN
B1600D –NN
XS2000D –NN
XS2500D –NN
XS3200D –NN

Product Information
10
TemBreak PRO B_BE-UM-001-EN V1.1.0
Label Identification
The label on the MCCB features information to aid in product identification.
Description
Notes
1
Circuit Break Identifier
Identifies the model type, ampere frame, and Icu rating.
2
Trip unit type
The trip unit type is indicated by the colour of the label.
White label –Thermal-magnetic type trip unit
Trip Units
FF, TF, FM, TM
Models
A, P, B, ZS
Ampere Frame
125 –800
Grey label –electronic or non-auto type trip unit. To distinguish between the two, electronic trip units
will have the “Icu” letter and non-auto will use the letter “D”, Switch.
Trip Units
BE, BEG, BEGN , NN
Models
A, P, B, XS
Ampere Frame
160 –3200
Blue Label –SMART electronic type trip unit
Trip Units
SX, SE
Models
P, B
Ampere Frame
160 –1000
3
Certifications
Identifies the additional localised certifications of the product, in addition to the international product standard, IEC 60947-2 /
AS/NZS IEC 60947-2.
For additional certifications please contact NHP.

Product Information
11
TemBreak PRO B_BE-UM-001-EN V1.1.0
B250_BE & B400_BE Information
Frame / Model
Quantity
Unit
Condition
B250P
B400P
B400R
Number of Poles
3, 4
3, 4
3, 4
Nominal current ratings
ICT
(A)
45°C
40, 100,
─
─
Trip unit ratings
160, 250
─
─
50°C
─
400
400
55°C
─
250
250
Electrical characteristics
Rated maximum operational voltage
Ue
(V)
AC 50/60 Hz
690
690
690
(V)
DC
250
─
─
Rated insulation voltage
Ui
(V)
800
800
800
Rated impulse withstand voltage
Uimp
(kV)
8
8
8
Selectivity category
A
B
B
Rated short time withstand current
Icw
(kA)
0.4 sec
─
5 / 0.3 sec
5 / 0.3 sec
Ultimate breaking capacity
Icu
(kA)
690 Vac
20
35
50
(IEC, JIS, AS/NZS)
400 /415 Vac
125
125
200
240 Vac
150
150
200
Service breaking capacity
Ics
(kA)
690 Vac
15
35
50
(IEC, JIS, AS/NZS)
400 /415 Vac
85
85
150
220 /240 Vac
150
150
150
Protection - Over Current Release types
Std Standard
Opt Optional
─Not Available
BE 2 dial 10 pre-set characteristic curves
Std
Std
Std
BE 2 dial Instantaneous only setting
Std
Std
Std
BE Instantaneous only setting (ICB)
Std
Std
Std
LT Adjustable 40% to 100% in 1% increments
─
─
─
LT Adjustable 40% to 100% in 1A increments
─
Std
increments
Std
Installation (Std / Opt / ─ )
Std Standard
Opt Optional
─Not Available
Front connection (FC)
Std
Std
Std
Extension bar (FB)
Opt
Opt
Opt
Cable tunnel clamp (FW)
Opt
Opt
Opt
Rear Connection (RC)
Opt
Opt
Opt
DIN rail adaptor
─
─
─
Withdrawable mechanism
─
─
─
Plug-in
Opt
Opt
Opt
Reverse supply connection possible to 440V
Yes
Yes
Yes
Dimensions
H
(mm)
165
260
260
W
(mm)
3 pole
105
140
140
4 pole
140
185
185
D
(mm)
103
140
140
T
(mm)
127
182
182
Weight
W
(kg)
3 pole
2.4
4.3
4.3
4 pole
3.2
5.7
5.7
Operation options (Std / Opt / ─ )
Std Standard
Opt Optional
─Not Available
Toggle operation
Std
Std
Std
Extension handle TP-HS/HP or Direct mount T2HB
Opt
Opt
Opt
Motor operation TP-MC
Opt
Opt
Opt
Endurance
Electrical
Cycles
415 Vac
10000
6000
6000
Mechanical
Cycles
20000
15000
15000

Product Information
12
TemBreak PRO B_BE-UM-001-EN V1.1.0
B800_BE Information
Frame / Model
Quantity
Unit
Condition
B800N
B800H
B800G
B800P
B800R
Number of Poles
3, 4
3, 4
3, 4
3, 4
3 ,4
Nominal current ratings
ICT
(A)
45°C
630, 800
630, 800
800
800
800
Trip unit ratings
50°C
─
─
630
630
630
Electrical characteristics
Rated maximum operational voltage
Ue
(V)
AC 50/60 Hz
690
690
690
690
690
(V)
DC
─
─
─
─
─
Rated insulation voltage
Ui
(V)
800
800
800
800
800
Rated impulse withstand voltage
Uimp
(kV)
8
8
8
8
8
Selectivity category
B
B
B
B
B
Rated short time withstand current
Icw
(kA)
0.4 sec
10
10
10
10
10
Ultimate breaking capacity
Icu
(kA)
690 Vac
25
25
25
25
25
(IEC, JIS, AS/NZS)
400 /415 Vac
50
70
100
125
200
240 Vac
85
100
125
150
200
Service breaking capacity
Ics
(kA)
690 Vac
20
20
20
20
20
(IEC, JIS, AS/NZS)
400 /415 Vac
50
50
50
94
150
220 /240 Vac
85
75
125
150
150
Protection - Over Current Release types
Std Standard
Opt Optional
─Not Available
BE 2 dials 10 pre-set characteristic curves
Std
Std
Std
Std
Std
BE Ground Fault
─
Opt
Opt
Opt
─
BE Instantaneous only setting (ICB)
Std
Std
Std
Std
Std
Installation (Std / Opt / ─ )
Std Standard
Opt Optional
─Not Available
Front connection (FC)
Std
Std
Std
Std
Std
Extension bar (FB)
Std
Std
Std
Std
Std
Cable tunnel clamp (FW)
─
─
─
─
─
Rear connection (RC)
Opt
Opt
Opt
Opt
Opt
DIN rail adaptor
─
─
─
─
─
Withdrawable mechanism
Opt
Opt
Opt
─
─
Plug-in
Opt
Opt
Opt
Opt
Opt
Reverse supply connection possible to 440V
Yes
Yes
Yes
Yes
Yes
Dimensions
H
(mm)
273
273
273
273
273
W
(mm)
3 pole
210
210
210
210
210
4 pole
280
280
280
280
280
D
(mm)
145
145
145
182
182
T
(mm)
103
103
103
140
140
Weight
W
(kg)
3 pole
9.1
9.1
9.1
14.8
14.8
4 pole
12.3
12.3
12.3
18.8
18.8
3 pole (630A)
7.0
8.7
8.7
13.3
13.3
4 pole (630A)
10.5
11.9
11.9
16.8
16.8
Operation options (Std / Opt / ─ )
Std Standard
Opt Optional
─Not Available
Toggle operation
Std
Std
Std
Std
Std
Extension handle TP-HS/HP or Direct mount T2HB
Opt
Opt
Opt
Opt
Opt
Motor operation TP-MC
Opt
Opt
Opt
Opt
Opt
Endurance
Electrical
Cycles
415 Vac
4000
4000
4000
4000
4000
Mechanical
Cycles
10000
10000
10000
10000
10000

Product Information
13
TemBreak PRO B_BE-UM-001-EN V1.1.0
B1000_BE & B1250_BE Information
Frame / Model
Quantity
Unit
Condition
B1000N
B1000H
B1250N
B1250H
B1250HL
Number of Poles
3, 4
3, 4
3, 4
3, 4
3, 4
Nominal current ratings
ICT
(A)
45°C
1000
1000
─
─
─
Trip unit ratings
50°C
─
─
1250
1250
1250
Electrical characteristics
Rated maximum operational voltage
Ue
(V)
AC 50/60 Hz
690
690
690
690
690
(V)
DC
─
─
─
─
─
Rated insulation voltage
Ui
(V)
800
800
800
800
800
Rated impulse withstand voltage
Uimp
(kV)
8
8
8
8
8
Selectivity category
A
A
B
B
B
Rated short time withstand current
Icw
(kA)
0.4 sec
─
─
15
15
15
Ultimate breaking capacity
Icu
(kA)
690 Vac
20
25
20
25
45
(IEC, JIS, AS/NZS)
400 /415 Vac
50
70
50
70
85
240 Vac
85
100
85
100
125
Service breaking capacity
Ics
(kA)
690 Vac
15
20
15
20
34
(IEC, JIS, AS/NZS)
400 /415 Vac
38
50
38
50
65
220 /240 Vac
65
75
65
75
94
Protection - Over Current Release types
Std Standard
Opt Optional
─Not Available
BE 2 dials 10 pre-set characteristic curves
Std
Std
Std
Std
Std
BE-G Ground Fault
─
Std
Std
Std
Std
BE Instantaneous only setting (ICB) 1)
Std
Std
Std
Std
Std
Installation (standard / optional / - )
Installation
Std Standard
Opt Optional
─Not Available
Front connection (FC)
Std
Std
Std
Std
Std
Extension bar (FB)
Std
Std
Std
Std
Std
Cable tunnel clamp (FW)
─
─
─
─
─
Rear connection (RC)
Opt
Opt
Opt
Opt
Opt
DIN rail adaptor
─
─
─
─
─
Withdrawable mechanism
─
─
─
─
─
Plug-in
─
─
Opt
Opt
Opt
Reverse supply connection possible to 440V
Yes
Yes
Yes
Yes
Yes
Dimensions
H
(mm)
273
273
370
370
370
W
(mm)
3 pole
210
210
210
210
210
4 pole
280
280
280
280
280
D
(mm)
145
145
171
171
171
T
(mm)
103
103
120
120
120
Weight
W
(kg)
3 pole
11.0
11.0
19.8
19.8
19.8
4 pole
14.8
14.8
25
25
25
Operation options (std / opt / - )
Std Standard
Opt Optional
─Not Available
Toggle operation
Std
Std
Std
Std
Std
Extension handle TP-HS/HP or Direct mount T2HB
Opt
Opt
Opt
Opt
Opt
Motor operation TP-MC
Opt
Opt
Opt
Opt
Opt
Endurance
Electrical
Cycles
415 Vac
4000
4000
4000
4000
4000
Mechanical
Cycles
10000
10000
5000
5000
5000

Product Information
14
TemBreak PRO B_BE-UM-001-EN V1.1.0
B1600_BE Information
Frame / Model
Quantity
Unit
Condition
B1600N
B1600HL
Number of Poles
3, 4
3, 4
Nominal current ratings
ICT
(A)
50°C
1600
1600
Trip unit ratings
Electrical characteristics
Rated maximum operational voltage
Ue
(V)
AC 50/60 Hz
690
690
(V)
DC
─
─
Rated insulation voltage
Ui
(V)
800
800
Rated impulse withstand voltage
Uimp
(kV)
8
8
Selectivity category
B
B
Rated short time withstand current
Icw
(kA)
0.4 sec
20
20
Ultimate breaking capacity
Icu
(kA)
690 Vac
20
45
(IEC, JIS, AS/NZS)
400 /415 Vac
50
85
240 Vac
85
125
Service breaking capacity
Ics
(kA)
690 Vac
15
34
(IEC, JIS, AS/NZS)
400 /415 Vac
38
65
220 /240 Vac
65
94
Protection - Over Current Release types
Std Standard
Opt Optional
─Not Available
BE 2 dials 10 pre-set characteristic curves
Std
Std
BE-G Ground Fault
Std
Std
BE Instantaneous only setting (ICB)
Std
Std
Installation (Std / Opt / ─ )
Std Standard
Opt Optional
─Not Available
Front connection (FC)
Std
Std
Extension bar (FB)
Std
Std
Cable tunnel clamp (FW)
─
─
Rear connection (RC)
Opt
Opt
DIN rail adaptor
─
─
Withdrawable mechanism
─
─
Plug-in
─
─
Reverse supply connection possible to 440V
Dimensions
H
(mm)
370
370
W
(mm)
3 pole
210
210
4 pole
280
280
D
(mm)
191
191
T
(mm)
140
140
Weight
W
(kg)
3 pole
27
27
4 pole
35
35
Operation options (std / opt / - )
Std Standard
Opt Optional
─Not Available
Toggle operation
Std
Std
Extension handle TP-HS/HP or Direct mount T2HB
Opt
Opt
Motor operation TP-MC
Opt
Opt
Endurance
Electrical
Cycles
415 Vac
4000
4000
Mechanical
Cycles
5000
5000

15
TemBreak PRO B_BE-UM-001-EN V1.1.0
Internal Accessories
Internal accessories include Auxiliary and Alarm contacts, Shunt Trip and Undervoltage Trip (UVT) modules, which may be installed under the front cover of
the MCCB in various combinations to provide additional functionality and connection with external control circuits.
Auxiliary & Alarm Switches
Auxiliary Contact
An auxiliary contact can be installed to indicate whether an MCCB is Open (both OFF and
Tripped positions) or Closed (ON). Auxiliary contacts come in either general purpose, heavy
duty or micro-switch type, with some combinations pre-wired or with terminals. Each contact
type is provided as a single change-over switching arrangement (1x C/O), or normally-open
(1x N/O) for option in heavy-duty.
Alarm Contact
An alarm contact can be installed to indicate whether an MCCB is in the Tripped or Not
Tripped position (ON, OFF). Alarm contacts come in either general purpose, heavy duty or
micro-switch type, with some combinations pre-wired or with terminals. Each contact type is
provided as a single change-over switching arrangement (1x C/O), or normally-open (1x
N/O) for option in heavy-duty.
Part Number
Description
Contact Type
Contact Arrangement
Connection Type
T2AX00M3STA
Auxiliary
General purpose
C/O
Terminal
T2AX00M3SWA
Auxiliary
General purpose
C/O
Pre-wired
T2AX00B1STA
Auxiliary
Heavy duty
N/O
Terminal
T2AX00B2STA
Auxiliary
Heavy duty
C/O
Terminal
T2AX00M3RTA
Auxiliary
Micro-switch
C/O
Terminal
T2AL00M3STA
Alarm
General purpose
C/O
Pre-wired
T2AL00M3SWA
Alarm
General purpose
C/O
Pre-wired
T2AL00B1STA
Alarm
Heavy duty
N/O
Pre-wired
T2AL00B2STA
Alarm
Heavy duty
C/O
Pre-wired
T2AL00M3RTA
Alarm; left side only
Micro-switch
C/O
Pre-wired
General purpose contact
AC (V)
DC (V)
Minimum Load
Volts (V)
Amperes (A)
Volts (V)
Amperes (A)
Resistive Load
Inductive Load
Resistive Load
Inductive Load
480
─
─
250
─
─
100 mA @ 15 Vdc
250
3
2
125
0.4
0.05
125
3
2
30
3
2
Heavy duty contact
AC (V)
DC (V)
Minimum Load
Volts (V)
Amperes (A)
Volts (V)
Amperes (A)
Resistive Load
Inductive Load
Resistive Load
Inductive Load
500
1
1
─
─
─
─
440
3
3
250
0.5
0.5
240
4
4
125
1
1
110
5
5
48
3
2.5
48
6
6
24
6
2.5
Micro-switch contact
DC (V)
Minimum Load
Volts (V)
Amperes (A)
Resistive Load
Inductive Load
30
0.1
─
1 mA @ 5 Vdc

Internal Accessories
16
TemBreak PRO B_BE-UM-001-EN V1.1.0
Shunt Trip
A shunt (normally de-energized) can be installed to trip the MCCB by applying voltage to the shunt coil.
Part Number
Rated voltage
Connection type
AC (V)
DC (V)
T2SH00A10TA
110
─
Terminal
T2SH00A20TA
230…240
─
Terminal
T2SH00A40TA
400…415
─
Terminal
T2SH00D01TA
─
12
Terminal
T2SH00D02TA
*
24
Terminal
T2SH00D04TA
─
48
Terminal
T2SH00D10TA
─
110
Terminal
T2SH00D20TA
─
230
Terminal
* Whilst not a rated voltage, T2SH00D02TA will operate at 24V ac
Rated voltage
AC (V)
DC (V)
100…120
200…240
380…450
12
24
48
100…120
200…240
Excitation Current (mA)
14.0
14.0
6.5
30.0
30.0
30.0
11.0
11.0
Under Voltage Trips
A UVT (normally energized) can be installed to trip the MCCB removing voltage from the UVT coil.
Part Number
Rated voltage
Compatible MCCB
Connection
Type
Notes
AC (V)
DC (V)
T2UV00A10NTA
110
─
B 250 / 400
Terminal
Instantaneous
T2UV00A20NTA
200…240
─
B 250 / 400
Terminal
Instantaneous
T2UV00A40NTA
380…450
─
B 250 / 400
Terminal
Instantaneous
T2UV00D02NTA
─
24
B 250 / 400
Terminal
Instantaneous
T2UV00D04NTA
─
48
B 250 / 400
Terminal
Instantaneous
T2UV00D10NTA
─
110
B 250 / 400
Terminal
Instantaneous
T2UV00D20NTA
─
230
B 250 / 400
Terminal
Instantaneous
T2UV00A10DS
110
─
B 250 / 400
Terminal
Time Delay 500ms
T2UV00A24DS
230…240
─
B 250 / 400
Terminal
Time Delay 500ms
T2UV00A40DS
440..450
─
B 250 / 400
Terminal
Time Delay 500ms
T2UV00D02DS
─
24
B 250 / 400
Terminal
Time Delay 500ms
T2UV00D10DS
─
110
B 250 / 400
Terminal
Time Delay 500ms
T2UV00D24DS
─
230
B 250 / 400
Terminal
Time Delay 500ms
T2UV80A10NTA
110
─
B 800 / 1000 / 1250 / 1600
Terminal
Instantaneous
T2UV80A20NTA
200…240
─
B 800 / 1000 / 1250 / 1600
Terminal
Instantaneous
T2UV80A40NTA
380…450
─
B 800 / 1000 / 1250 / 1600
Terminal
Instantaneous
T2UV80D02NTA
─
24
B 800 / 1000 / 1250 / 1600
Terminal
Instantaneous
T2UV80D04NTA
─
48
B 800 / 1000 / 1250 / 1600
Terminal
Instantaneous
T2UV80D10NTA
─
110
B 800 / 1000 / 1250 / 1600
Terminal
Instantaneous
T2UV80D20NTA
─
230
B 800 / 1000 / 1250 / 1600
Terminal
Instantaneous
T2UV80A10DS
110
─
B 800 / 1000 / 1250 / 1600
Terminal
Time Delay 500ms
T2UV80A24DS
230…240
─
B 800 / 1000 / 1250 / 1600
Terminal
Time Delay 500ms
T2UV80A40DS
440…450
─
B 800 / 1000 / 1250 / 1600
Terminal
Time Delay 500ms
T2UV80D02DS
─
24
B 800 / 1000 / 1250 / 1600
Terminal
Time Delay 500ms
T2UV80D10DS
─
110
B 800 / 1000 / 1250 / 1600
Terminal
Time Delay 500ms
T2UV80D24DS
─
230
B 800 / 1000 / 1250 / 1600
Terminal
Time Delay 500ms
Rated Voltage
Power supply capacity (VA)
Excitation current (mA)
AC (V)
DC (V)
100…110
115…120
200…220
230…240
380…415
440…450
24
100…120
200…240
B 250 / 400
1.4
1.4
2.8
2.8
2.3
2.3
23
10
10
B 800 / 1000 / 1250 / 1600
1.5
1.6
2.4
2.9
2.1
2.3
29
13
11

17
TemBreak PRO B_BE-UM-001-EN V1.1.0
Plugs and Ports
The B_BE circuit breaker is equipped with specific connectors for factory use only.
Port
Description
B 250
B 400 / 800 / 1000 / 1600
Test
Factory Use Only
✓
─
Test
Factory Use Only
─
✓

18
TemBreak PRO B_BE-UM-001-EN V1.1.0
Installation
Precautions
Mounting Angles
TemBreak PRO MCCBs may be mounted at any angle without affecting performance.
Direction of Power Supply
Power supply may be fed in either direction with respect to the MCCB without affecting performance.
WARNING: To prevent electrical shock and damage to equipment, disconnect and isolate power source
upstream of the MCCB before installing or servicing the MCCB including its connected accessories.
Notice: To ensure correct performance, and integrity of equipment, the installation instructions and
recommendations provided herein shall be respected. Refer to the respective user manual and installation
instructions provided with the MCCB and associated accessories.
Positive (+)
Forward/Normal
Supply
Negative (−)
Reverse Supply

Installation
19
TemBreak PRO B_BE-UM-001-EN V1.1.0
Clearances
Phase to Phase and Earth
Interruption of large currents during fault or normal switching operation produces ionised gases and arcing materials which expelled from the vents at the top
of the MCCB. These ionised gases are highly conductive, concentrated, and at an elevated temperature when it exits the MCCB via the arc vents. Care
must be taken to avoid an arcing fault from occurring due to the presence of concentrated ionised gases creating a conductive path between exposed
conductors. Incoming conductors must therefore be insulated the full length up to the terminal opening of the MCCB, ensuring bare conductors are not
exposed directly to concentrated ionised gases. This also applies to the attached busbars supplied as part of the MCCB.
Interpole barriers or terminal covers may be used to achieve creepage and clearance requirements. Conductors must not impede the flow of ionised gas
and allow it to clear and disperse safety. Interpole barriers are supplied as standard with Terasaki MCCBs for the line side only. 2 barriers with 3P MCCBs
and 3 with 4P MCCBs. In cases where two different MCCB types are installed one above the other, the insulation distance between the two models should
be as for the lower model.
WARNING: Exposed conductors including terminals at attached busbars must be insulated to avoid possible
short-circuit or earth faults due any foreign matter coming into contact with the conductors.

Installation
20
TemBreak PRO B_BE-UM-001-EN V1.1.0
Insulating Distance
When earth metal is installed within proximity of the breakers, the correct insulating distance must be maintained, (refer to Minimum Clearance).
This distance is necessary to allow the exhausted arc gases to disperse. This could include the mounting plate or side panel within a switchboard.
Minimum Clearance
Below illustrates the minimum clearance that must be maintained.
Dim.
Description
MCCB Cat. No.
Distances (mm)
A
B1
B2
C
D
E
A
Distance from lower breaker to open charging part of terminal on
upper breaker (front connection) or the distance from lower
breaker to upper breaker end (rear connection and plug-in type)
B250 P / R
100
80
60
0
50
^
B400 P / R
120
120
80
0
80
^
B800 F / N / D
120
70
40
0
30
^
B1
Distance from breaker end to ceiling (earthed metal)
B800 H / G
150
80
50
0
40
^
B2
Distance from breaker end to insulator
B800 P / R
150
70
40
0
30
^
C
Clearance between breakers
B1000 N / H / D
150
70
40
0
30
^
D
Distance from breaker side to side plate (earthed metal)
B1250 N / H / HL / D
150
70
40
0
30
^
E
Length of insulation over exposed conductors.
B1600 N / HL / D
150
150
100
0
100
^
^ Insulate the exposed conductor until it overlaps the moulded case at the terminal, or the terminal cover.
Table of contents
Other NHP Circuit Breaker manuals
Popular Circuit Breaker manuals by other brands

Stahl
Stahl 8562 Series operating instructions

Allen-Bradley
Allen-Bradley 140G-BML Installation instruction

Siemens
Siemens Speedfax HMM3M800 installation instructions

Siemens
Siemens SIRIUS operating instructions

Rockwell Automation
Rockwell Automation Allen-Bradley 140G-G manual

Cutler-Hammer
Cutler-Hammer VCP-TR Series Instructions for the Use, Operation and Maintenance