Nibe SMO S40 User guide

IHB EN 2016-1
431901
INSTALLER MANUAL
Control module
NIBE SMO S40

Quick guide
NAVIGATION
Browse
Scroll
Select The dots at the bot-
tom edge show
that there are more
pages.
If the menu has
several sub-menus,
you can see more
information by
dragging up or
down with your fin-
ger.
Most options and
functions are activ-
ated by lightly
pressing on the dis-
play with your fin-
ger.
Drag to the right or
left with your finger
to browse between
the pages.
Setting the indoor temperature.
Bottom floor
Temperature
HEAT
13.45 3 October
Smartguide
Yes please, take me to Smartguide.
Hi!
Your system is working properly. Do you want help making
changes?
13.45 3 October
Here, you can set the temperature in the installation's
zones.
Smartguide helps you both to view information about the
current status and to make the most common settings
easily. The information that you see depends on the
product you have and the accessories that are connected
to the product.
Product overview
PRODUCT OVERVIEW
Update
Product name
Serial number
Software
Service
13.45 3 October
Company AB
Phone number
SMOS40
01234567890123
1.0.0
Increasing hot water temperature
HOT WATER
More hot water
13.45 3 October
Here, you can find information about product name, the
product's serial number, the version of the software and
service. When there is new software to download, you
can do it here (provided that SMO S40 is connected to
myUplink).
Here, you can start or stop a temporary increase in the
hot water temperature.
This function page is only visible in installations with a
water heater.

51 Important information
5Symbols
5Serial number
6Inspection of the installation
7System solutions
82 Delivery and handling
8Mounting
9Supplied components
9Open front hatch
10Open USB cover
113 The Control Module Design
11Component positions
12List of components
134 Installing the installation
13General
14Symbol key
14Temperature sensor installation on pipe
14Fixed condensing
15Connecting air/water heat pump
15Connecting the climate system
16Cold and hot water
16Installation alternative
185 Electrical connections
18General
19Connections
27Selectable in/outputs
29Settings
306 Commissioning and adjusting
30Preparations
30Commissioning
30Commissioning with additional heating only
30Check the reversing valve
30Check selectable outputs
30Cooling mode
31Start guide
31Setting the cooling/heating curve
337 myUplink
33Specification
33Connection
33Range of services
33Mobile apps for myUplink
348 Control - Introduction
34Display unit
35Navigation
35Menu types
389 Control – Menus
38Menu 1 – Indoor climate
42Menu 2 – Hot water
44Menu 3 - Info
45Menu 4 - My system
49Menu 5 - Connection
50Menu 6 - Scheduling
51Menu 7 - Installer settings
6010 Service
60Service actions
6311 Disturbances in comfort
63Info-menu
63Manage alarm
63Troubleshooting
65Add. heat only
6612 Accessories
6813 Technical data
68Dimensions
69Technical specifications
70Energy labelling
71Electrical circuit diagram
3Table of ContentsNIBE SMO S40
Table of Contents

Symbols
NOTE
This symbol indicates danger to person or ma-
chine .
Caution
This symbol indicates important information
about what you should consider when installing
or servicing the installation.
TIP
This symbol indicates tips on how to facilitate
using the product.
Serial number
The serial number can be found on the left-hand side of
the control module and on the "Product overview" home
screen.
UN
Serial number
Caution
You need the product's ((14 digit) serial number
for servicing and support.
5Chapter 1 | Important informationNIBE SMO S40
1 Important information

Inspection of the installation
Current regulations require the heating installation to be inspected before it is commissioned. The inspection must
be carried out by a suitably qualified person.
In addition, fill in the page for the installation data in the User Manual.
DateSigna-
ture
NotesDescription
✔
Electrical connections
Communication, heat pump
Connected supply 230 V
Outside sensor
Room sensor
Temperature sensor, hot water char-
ging
Temperature sensor, hot water top
Temperature sensor, external flow
line
Temperature sensor, external return
line
Charge pump
Shuttle valve
AUX1
AUX2
AUX3
AUX4
AUX5
AUX6
AUX10
AUX11
Miscellaneous
Checking additional heater
Checking the function of the revers-
ing valve
Checking charge pump function
Completed installation check of heat
pump and associated equipment
NIBE SMO S40Chapter 1 | Important information6

System solutions
COMPATIBLE PRODUCTS
The following combinations of products are recommended for control by SMO S40.
LEK
LEK
LEK
LEK
LEK
LEK
LEK
Volume ves-
sel
Addition
Water heater
Circ. pumpAccumulator
with hot wa-
ter heater
HW control
Air/water
heat pump
Control mod-
ule
UKV 40
ELK 15
VPB 200
CPD 11-25/65
VPA 200/70
VST 05
AMS 10-6 /
HBS 05-6
SMO S40
UKV 100
UKV 200ELK 26
ELK 42
VPB 300
VPBS 300
CPD 11-25/75
VPA 300/200
VPA 450/300
AMS 10-8 /
HBS 05-12
UKV 300
VPB 500
VPAS
300/450
F2040 – 6
UKV 500
VPB 750-2
F2040 – 8
VPB 1000
F2120 – 8
VST 11
AMS 10-12 /
HBS 05-12
F2040 – 12
F2120 – 12
F2120 – 16
VPB 500
VST 20
AMS 10-16 /
HBS 05-16 VPB 750-2
VPB 1000
F2040 – 16
F2120 – 20
COMPATIBLE AIR/WATER HEAT PUMPS
In some air/water heat pumps, manufactured before or
during 2019, the circuit board must be updated in order
to be compatible with SMO S40.
Lowest compatible soft-
ware version
Air/water heat pump
v37 (AA23 communication
board)
NIBE SPLIT HBS 05
(AMS 10, HBS 05)
v129F2030
v37 (AA23 communication
board)
F2040
v561F2120
v129F2300
7Chapter 1 | Important informationNIBE SMO S40

Mounting
NOTE
For wall mounting, use screws (and any plugs)
suitable for the surface.
Use all mounting points and install SMO S40 upright flat
against the wall without any part of the control module
protruding beyond the edge of the wall.
Leave at least 100 mm free space around the control
module to facilitate access and cable routing on installa-
tion and service.
Caution
Screws for removing the front cover are
reached from underneath.
SMO S40
1. Remove the hatch, by unscrewing the screws in the
bottom edge. Angle out at the bottom edge and unhook
the cover at the upper edge.
SMO S40
2x
2. Remove the display by moving it to the left. Detach the
cable from the lower edge.
3. Mark the position of the two upper screws using a pen.
Screw in the upper two screws.
4. Hook onto SMO S40 the screws in the wall.
2x
NIBE SMO S40Chapter 2 | Delivery and handling8
2 Delivery and handling

5. Reassemble the display. Screw SMO S40 into place on
the lower edge with the two remaining screws. Supplied components
Room sensor
1 x
Outdoor temperature
sensor
1 x
LEK
Aluminium tape
LEK
Insulation tape
Temperature sensor
Cable ties
Heating pipe paste
LEK
LEK
LEK
Current sensor
Open front hatch
9Chapter 2 | Delivery and handlingNIBE SMO S40

Open USB cover
NIBE SMO S40Chapter 2 | Delivery and handling10

Component positions
UN
AA4 SF1XF3
XF8
PZ3
AA2
UB2UB1 X9 X10 X11
X2
X5
X1
X6 X8
X13 X14
X7
X12
AA100
X4X3
AA100-F2 AA2-F1AA100-F1
11Chapter 3 | The Control Module DesignNIBE SMO S40
3 The Control Module Design

List of components
ELECTRICAL COMPONENTS
Base cardAA2
Fine wire fuse, 4ATF1
Display unitAA4
USB socketXF3
Network socketXF8
Joint cardAA100
Fine wire fuse, 6.3ATF1
Fine wire fuse, 6.3ATF2
Terminal block, power supplyX1
Terminal block, earthX2
Terminal block (N)X3
Terminal block (L)X4
Terminal block (QN10, GP10,
GP12.1-EB101, GP12.2-EB102)
X5
Terminal block AUX outputs
(AUX10)
X6
Terminal block AUX outputs
(AUX11)
X7
Terminal block, additional heatX8
Terminal block, external connection
options
X9
Terminal block AUX inputs, external
connection options (selectable AUX
1–6)
X10
Terminal block (GND)X11
Terminal block, external connectionsX12
Terminal block (GND)X13
Terminal block, external connectionsX14
On/off buttonSF1
Network connection for myUplinkXF8
Cable grommet, incoming supply electricity,
power for accessories
UB1
Cable gland, signalUB2
OTHER COMPONENTS
Serial number platePZ3
Designations according to standard EN 81346-2.
NIBE SMO S40Chapter 3 | The Control Module Design12

General
Pipe installation must be carried out in accordance with
applicable regulations. See manual for compatible NIBE
air/water heat pump for installation of the heat pump.
The pipe dimension should not be less than the recom-
mended pipe diameter according to the table. However,
each system must be dimensioned individually to man-
age the recommended system flows.
MINIMUM SYSTEM FLOWS
The installation must be dimensioned at least to manage
the minimum defrosting flow at 100% pump operation,
see table.
Minimum re-
commended
pipe dimen-
sion (mm)
Minimum re-
commended
pipe dimen-
sion (DN)
Minimum
flow during
defrosting
(100% pump
speed (l/s)
Air/water
heat pump
22200.27F2120-8
(1x230V)
22200.27F2120-8
28250.35F2120-12
(1x230V)
28250.35F2120-12
28250.38F2120-16
35320.48F2120-20
Minimum re-
commended
pipe dimen-
sion (mm)
Minimum re-
commended
pipe dimen-
sion (DN)
Minimum
flow during
defrosting
(100% pump
speed (l/s)
Air/water
heat pump
22200.19F2040-6
22200.19F2040-8
22200.29F2040-12
28250.39F2040-16
Minimum re-
commended
pipe dimen-
sion (mm)
Minimum re-
commended
pipe dimen-
sion (DN)
Minimum
flow during
defrosting
(100% pump
speed (l/s)
Air/water
heat pump
22200.19HBS 05-6/
AMS 10-6
22200.19HBS 05-12/
AMS 10-8
22200.29HBS 05-12/
AMS 10-12
28250.39HBS 05-16/
AMS 10-16
NOTE
An undersized system can result in damage to
the machine and lead to malfunctions.
13Chapter 4 | Installing the installationNIBE SMO S40
4 Installing the installation

Symbol key
MeaningSymbol
Unit box
Shut-off valve
Tapping valve
Non-return valve
Mixing valve
Circulation pump
Expansion vessel
Filterball
Pressure gauge
Particle filter
Safety valve
Temperature sensor
Reversing valve/shunt
Heat exchanger
Overflow valve
Under floor heating systems
Control module
Cooling system
Air/water heat pump
Pool
Radiator system
Domestic hot water
Addition
Water heater
Temperature sensor
installation on pipe
LEK
LEK
The temperature sensors are mounted with heat con-
ducting paste, cable ties (the first cable tie is secured
to the pipe in the middle of the sensor and the other
cable tie is mounted approx. 5 cm beyond the sensor)
and aluminium tape. Then insulate with supplied insula-
tion tape.
NOTE
Sensor and communication cables must not
be placed near power cables.
Fixed condensing
If SMO S40 is only to work towards a water heater with
fixed condensing, you must connect external supply
temperature sensor (BT25) according to the description
in section "Temperature sensor, external flow line". In
addition, you must make the following menu settings.
Menu setting (local vari-
ations may be required)
Menu
Desired temperature in the
tank.
1.30.4 – Lowest supply,
heating
Desired temperature in the
tank.
1.30.6 – Highest supply,
heating
Manual4.1 – Operating mode
NIBE SMO S40Chapter 4 | Installing the installation14

Connecting air/water
heat pump
You can find a list of compatible air/water heat pumps
in section "System solutions".
• Install the necessary safety equipment, non-return
valve, shut-off valve, circulation pump and expansion
vessel. Also, consult the Installer Manual for your
air/water heat pump.
• Install the enclosed filterball.
• If the system is to work towards both a climate sys-
tem and hot water heater, a reversing valve must be
installed.
P
XL1
XL2
Connecting the
climate system
A climate system is a system that regulates indoor
comfort with the help of the control system in SMO S40
and for example radiators, underfloor heating/cooling,
fan convectors etc.
• Install external supply temperature sensor (BT25) It
says when the air/water heat pump must start to
produce heating/cooling for the climate system.
• Install external return temperature sensor (BT71). It
is used to check that the climate system is correctly
adjusted.
• When connecting to systems with thermostats on all
radiators/underfloor heating coils, some of the thermo-
stats must be removed to ensure there is sufficient
flow.
• For an even flow to the radiators during hot water
charging or similar, a circulation pump and reversing
valve for the climate system are installed.
XL1
XL2
15Chapter 4 | Installing the installationNIBE SMO S40

Cold and hot water
CONNECTING THE HOT WATER HEATER
• Controlling hot water sensor (BT6) and display hot
water sensor (BT7) are placed in the water heater.
• Fit shut-off valve, non-return valve and safety valve as
illustrated.
• The safety valve must have max. 1.0 MPa (10.0 bar)
opening pressure, and be installed on the incoming
domestic water line as shown.
• A mixer valve must also be installed, if the factory
setting for hot water is changed. National regulations
must be observed.
• Hot water production is activated in the start guide or
in menu 7.1.1.
XL1
XL2
Installation alternative
SMO S40 can be connected in several different ways,
some of which are shown below.
More information about the alternatives is available at
nibe.eu/ODM and in the relevant assembly instructions
for the accessories used. See section "Accessories" for
a list of the accessories that can be used with SMO S40.
BUFFER VESSEL UKV
UKV is an accumulator tank that is suitable for connec-
tion to a heat pump or another external heat source, and
can have several different applications. It can also be
used during external control of the heating system.
The image shows UKV flow equalisation.
ADDITION
On cold days of the year, when the availability of energy
from the air is lower, the additional heating can com-
pensate and help to produce heat. The additional heating
is also good to have as assistance, if the heat pump
ends up outside its working range or if it has been
blocked for any reason.
In the principle diagram below, the additional heat is
located after the reversing valve. (Additional heat can
also be connected before the reversing valve.)
COOLING
Cooling (in 2-pipe system)
Cooling and heating are distributed via the same climate
system.
NIBE SMO S40Chapter 4 | Installing the installation16

Cooling (in 4-pipe system)
With the accessory NIBE AXC 30, separate cooling and
heating systems can be connected via a reversing valve.
It is also possible to connect cooling (in 4 pipe systems)
on AUX10 (relay K8) or AUX11 (relay K9).
-EP45-GP10
-EP45
-EQ1-BT64
EXTRA CLIMATE SYSTEM
In buildings with several climate systems that require
different supply temperatures, the accessory
ECS 40/ECS 41 can be connected. A shunt valve then
lowers the temperature to the underfloor heating sys-
tem, for example.
-EP21-RM1
-EP21-GP10-EP21-BT2
-EP21-AA25
-EP21-BT3
-EP21-QN25
-EP21
POOL
POOL 40 is an accessory that enables pool heating using
one or more compressors in your installation.
-CL11-HQ4-CL11-BT51-CL11-GP9
-CL11-EP5
-CL11-AA25
-CL11
17Chapter 4 | Installing the installationNIBE SMO S40

General
• Disconnect SMO S40 before insulation testing the
house wiring.
• When the building is equipped with an earth-fault
breaker the heat pump should be equipped with a
separate one.
• SMO S40 must be installed via an isolator switch. The
cable area has to be dimensioned based on the fuse
rating used.
•Use a screened cable for communication with the heat
pump.
• To prevent interference, sensor cables to external
connections must not be laid close to high voltage
cables.
• The minimum area of communication and sensor
cables to external connections must be 0.5 mm² up
to 50 m, for example EKKX, LiYY or equivalent.
• When cable routing in SMO S40, the cable grommets
(UB1 and UB2) must be used.
•For an electrical wiring diagram for the control module,
see section "Technical Specifications"
UB1 UB2
NOTE
Do not start the system before filling up with
water. Components in the system could be
damaged.
NOTE
Electrical installation and any servicing must
be carried out under the supervision of a quali-
fied electrician. Disconnect the current using
the circuit breaker before carrying out any ser-
vicing.
Electrical installation and wiring must be carried out in
accordance with the stipulations in force.
ACCESSIBILITY, ELECTRICAL CONNECTION
Removing the cover
Loosen the screws slightly. Lift the bottom edge of the
front cover of the control module and unhook the cover
on the upper edge.
SMO S40
2x
Removing the covers
The cover is opened using a screwdriver.
NIBE SMO S40Chapter 5 | Electrical connections18
5 Electrical connections

CABLE LOCK
Use a suitable tool to release/lock cables in the heat
pump terminal blocks.
Terminal block
1.
2.
MAKING HOLES FOR CABLE ROUTING
Press out the hole using a suitable tool.
Connections
NOTE
To prevent interference, sensor cables to ex-
ternal connections must not be laid close to
high voltage cables.
POWER CONNECTION
Supply voltage
The incoming cable must be connected to terminal block
AA100-X1. Tightening torque: 0.5 – 0.6 Nm.
AA100
AA2
X1
L N
X1
Tariff control
If the voltage to the compressor in the air/water pump
is lost for a certain period, this must be blocked simul-
taneously via the selectable inputs, see section "Select-
able in/outputs – Possible selections for AUX inputs".
Compressor blocking must be performed either on the
control module or on the air/water heat pump, not on
both at the same time.
19Chapter 5 | Electrical connectionsNIBE SMO S40

CHARGE PUMP FOR HEAT PUMP 1 AND 2
Connect circulation pump (AA35-GP12.1-EB101) to the
terminal block AA100-X2 (PE), AA100-X3 (N) and AA100-
X5:3 (230 V).
Control signal for AA35-GP12.1-EB101 is connected to
terminal block AA100-X12:1 (Pulse/0–10V) (PWM1) and
GND on any block X13.
If two heat pumps are connected to SMO S40 the circu-
lation pump (AA35-GP12.2-EB102) must be connected
to the terminal block AA100-X2 (PE), AA100-X3 (N) and
AA100-X5:4 (230 V). Control signal for (AA35-GP12.2-
EB102) is connected to terminal block AA100-X12:3
(Pulse/0–10V) (PWM0) and GND on any block X13.
TIP
Two charge pumps can be connected to and
controlled by SMO S40. Several charge pumps
can be connected, if accessory boards (AXC)
are used, two pumps per board.
1 2 3 4
Styrmodul
N L
AA100-X3
AA100-X5
PE
AA100-X2
NNN
PEPEPE
AA100:X12
PWM1
2
3
4
1
6
5
AA100:X13
GND
GND
GND
Externt
AA35-GP12.1-EB101
SMOS40
External
Styrmodul
N L
AA100-X3
AA100-X5
PE
AA100-X2
NNN
PEPEPE
AA100:X12
PWM0
2
3
4
1
6
5
AA100:X13
GND
GND
GND
41 2 3
Externt
AA35-GP12.2-EB102
SMOS40
External
SENSORS
External connections are connected on terminal block
X10 and X11 on the joint board (AA100).
X3
X2
X5
X12
X6 X7 X9 X11 X13
X14X10
AA100
AA2
Outside sensor
The outdoor sensor (BT1) is placed in the shade on a
wall facing north or north-west, so it is unaffected e.g.
by the morning sun.
The outdoor sensor is connected to terminal block
AA100-X10:1 and to any input on terminal block AA100-
X11.
If a conduit is used it must be sealed to prevent condens-
ation in the sensor capsule.
AA100-X11
2
3
4
5
6
1
BT7
BT25
BT71
BT1
BT50
BT6
AA100-X10
BT1
Temperature sensor, hot water charging
The temperature sensor, hot water charging (BT6) is
placed in the submerged tube on the water heater.
Connect the sensor to terminal block AA100-X10:3 and
to any input on terminal block AA100-X11.
Settings for hot water are made in menu 2 "Hot water".
BT7
BT25
BT1
BT50
BT6
BT6
AA100-X11
AA100-X10
2
3
4
5
1
NIBE SMO S40Chapter 5 | Electrical connections20
Other manuals for SMO S40
3
Table of contents
Other Nibe Control System manuals
Popular Control System manuals by other brands

Carrier
Carrier i-Vu CCN Pro 4.2 installation guide

See Water
See Water Oil Smart installation manual

Honeywell
Honeywell VR8205 installation instructions

Emerson
Emerson PACSystems user guide

Tridonic
Tridonic modularDIM BASIC installation instructions

Böhnke + Partner
Böhnke + Partner Schmersal bp408 operating instructions