nilan Combi 302 Polar Top User manual

Version: 10.00, 28-11-2016
Combi 302 Polar
Installation instruction
CTS 602 by Nilan

Table of contents
Table of contents ............................................................................................................................2
Figure table ....................................................................................................................................2
Introduction..................................................................................................................................... 3
Power supply..................................................................................................................................4
Assembly of Combi 302 Polar......................................................................................................... 5
Condensation drain / water seal ..................................................................................................... 6
Ducting...........................................................................................................................................7
Starting and set up of the CTS 602 control..................................................................................... 8
Starting.......................................................................................................................................8
Set up of the CTS 602 control..................................................................................................... 8
Activating the SERVICE menu.................................................................................................... 9
Inlet heating.............................................................................................................................. 10
Heating surface......................................................................................................................... 11
Air quality.................................................................................................................................. 12
Air exchange............................................................................................................................. 13
Defrost......................................................................................................................................14
Temp. control............................................................................................................................ 15
Inlet control............................................................................................................................... 16
Room control ............................................................................................................................ 17
Restart......................................................................................................................................18
Preset....................................................................................................................................... 19
Manual......................................................................................................................................20
Modbus.....................................................................................................................................21
Datalog .....................................................................................................................................22
System dimension........................................................................................................................ 23
Accessories / spare parts ............................................................................................................. 24
Figure table
Figure 1: CTS 602 control............................................................................................................... 4
Figure 2: Mounting the Combi 302 Polar ........................................................................................ 5
Figure 3: Condensation drain / water seal....................................................................................... 6
Figure 4: Insulation of ducting.........................................................................................................7
Figure 5: CTS 602 control............................................................................................................... 8
Figure 6: Headlines in the service menu......................................................................................... 9
Figure 7: The "Inlet heating" Menu................................................................................................ 10
Figure 8: The “Central heating” menu........................................................................................... 11
Figure 9: The "Air quality" Menu................................................................................................... 12
Figure 10: The "Air exchange" Menu............................................................................................ 13
Figure 11: The "Defrost" Menu ..................................................................................................... 14
Figure 12: The "Temp. control" Menu ........................................................................................... 15
Figure 13: The "Inlet control" Menu............................................................................................... 16
Figure 14: The "Room control" Menu............................................................................................ 17
Figure 15: The "Restart" Menu ..................................................................................................... 18
Figure 16: The "Preset" Menu....................................................................................................... 19
Figure 17: The "Manual" Menu..................................................................................................... 20
Figure 18: The "Modbus" Menu .................................................................................................... 21
Figure 19: The "Datalog" Menu..................................................................................................... 22
Figure 20: System dimension ....................................................................................................... 23

This document may be subject to change Side 3 of 24
Introduction
Please control that the following documents have been delivered together with the unit:
- Directions for assembly & use (this document)
- CTS 602 directions
- Electrical chart
Should you have any questions on how to operate the system, contact your nearest Nilan dealer,
who you can find at www.nilan.dk/dealers
Combi 302 Polar is a combined passive and active heat recovery plant with a cooling function.
The standard delivery of the Combi 302 Polar is with filter classes F5 (EU5) in the exhaust device
and F7 (EU7) in the injection.
The unit can be equipped with different accessories e.g. hygrostat and filter box with pollen filter.
Operating the unit is done with the CTS 602 control. The control has many functions such as menu
based attendance, week programme, time controlled filter guard and adjustment of the velocity of
the ventilator. (Directions for the CTS 602 control is described in another document delivered with
the unit.)
For accessories see page 23.
We recommend that the system as well as the installation is adjusted/checked to ensure
a healthy indoor climate and optimal operation.

This document may be subject to change Side 4 of 24
Power supply
Power supply including safety switch must be installed by an authorized electrician.
The Combi 302 Polar unit must be connected according to the attached electrical chart.
The unit is delivered with 1m test cable for the CTS 602 panel. The panel should be connected to
the CTS 602 control in the unit with cable type 2x2x0.25mm2twisted in pairs. (Maximum length
50m).
The CTS 602 panel must be placed dry and frost-proof. The panels’ integrated feeler prevents fur-
ther cooling of the building if the primary heat-supply stops by stopping the ventilation if the panel
feeler gets below a specific value. (Factory setting is 10°C; the value can be set from 1°C to 20°C.)
Use of t he CTS 600 panel :
- pr ess ESC t o go one st ep back i n t he menu
- press pt o move up or down i n a menu or t o
adj ust an act i vat ed menu
- press ENTER t o act i vat e a menu
- pr ess ENTER t o conf i r m a menu
- pr ess OFF t o t ur n of f t he uni t
- pr ess ON t o t ur n t he uni t on
Figure 1: CTS 602 control
If a water post-heating element is installed, the control valve and circulation pump must be elec-
tronically connected as described in the provided wiring diagrams.

This document may be subject to change Side 5 of 24
Assembly of Combi 302 Polar
When mounting the Combi 302 Polar future service and maintenance should be consid-
ered.
It is recommended to have minimum 60 and 30 cm free space in front of-
and at the end
of the plant.
The system must be level due to the condense outlet. The condense outlet requires a clearance
height of minimum 11.5 cm under the outlet connection piece.
It is not necessary to re-insulate the system as it is delivered with a 20 mm standard insulation.
The system is low-noise and low-vibration. However, potential vibrations spreading from the sys-
tem to the individual building parts must be taken into account. We recommend a minimum
distance of 30 mm from building parts and other fixtures. It is recommended to place the plant on
vibration absorbers to separate the plant and the base
Figure 2: Mounting the Combi 302 Polar

This document may be subject to change Side 6 of 24
Condensation drain / water seal
The Combi 302 Polar unit is delivered with a 20mm condensation drain. (PVC, GF-fittings). The
drain is placed under the discharge.
The condensation drain should be carried with an even inclination of at least 1 cm per
meter, frost-proof to the nearest outlet. The overflow from the safety valve should also be
carried to the nearest outlet.
To avoid frost problems it can be necessary to supply the condensation drain with a
heating cable. It is the plumbers’ responsibility to secure the drain.
When the system is running, there can be a vacuum of up to 500Pa (corresponding to 50mm water
column) in the outlet. For this reason, the difference in height in the water seal must be minimum
50mm. This means that the first bend of the water seal must be at least twice as long in order for
the system to be able to dispose of the condense water (see figure 3).
The condensation drain must be airproof from the unit to the water seal in order for the condensa-
tion water to be let away from the unit. If the condensation drain is not airproof false air will be
sucked in to the unit and the water will stay inside the unit.
The water seal can dry out and avoid the water from running out of the unit. Therefore the water
seal should be tested regularly and refilled with water if necessary. An elevated height of the water
seal will reduce the need for refilling with water.
min. 112 mm
min. 50mm.
min. 50mm.
Ø20 mm drain
Unit
Figure 3: Condensation drain / water seal
The water seal should be tested as described below. (the unit must be connected to the
ducting and the front door should be closed):
The condensation tray is filled with water and the unit is started at the highest ventilation
step. The unit should run for a couple of minutes. Check that the condensation tray is
empty when the test is finished.

This document may be subject to change Side 7 of 24
Ducting
We recommend that there are used ducts and fittings with rubber packing that meet sealing class
B and that the connections between the unit and the ducting are made with 1 metre sound absorb-
ing flexible transitions as regards sound reduction.
The ducts should be shortened with a hacksaw or an angle grinder and laid out according to the
working drawing. The ducts are typically laid out on the main beam of the truss frame and are se-
cured with hole belts or they are being hanged in assembly belts. Please avoid any unnecessary
area reductions and breaks of the ducting.
The ducts should be insulated – in some cases with the ordinary attic-insulation. All ducts should
be insulated with 100mm mineral wool to avoid heat loss and condensation. This also applies for
flexible transitions. It is recommended that the insulation is carried out with 2 layers of 50mm. If the
ducts are laid out in an unheated room it will cause condensation problems if the unit are turned off
for a longer period of time as the hot air from the heated room will rise to the ducts and cause con-
densation which can cause damp problems.
Figure 4: Insulation of ducting
The discharge duct is leading the exhaust air away either above the roof or through the outer wall.
It is important that the roof cowl has at least the same open space as the duct leading to the roof
cowl. A reduction at this place will cause an unnecessary pressure drop which can lead to a re-
duced ventilation output.
The holes for the inlet- and exhaust valves should be cut according to the mounting-frame for the
prescribed valve. The frame for the valve must be secured with screws before placing the valve in
the frame. The valves are placed in accordance with the size, construction and use of the room. As
an example we would not recommend placing an inlet valve just above people with sedentary work
because the inlet air in some cases would be experienced as a draught.
Granulate
Duct
Loft insulationmaterial

This document may be subject to change Side 8 of 24
Starting and set up of the CTS 602 control
Starting
Before starting the Combi 302 Polar please check all functions as cooling, heating and heating
surface if installed.
Set up of the CTS 602 control
In this passage we will go through the service menu of the CTS 602 control. For daily use of the
CTS 602 control please see the CTS 602 directions. (delivered together with the Combi 302 Polar).
Use of t he CTS 600 panel :
- pr ess ESC t o go one st ep back i n t he menu
- press pt o move up or down i n a menu or t o
adj ust an act i vat ed menu
- press ENTER t o act i vat e a menu
- pr ess ENTER t o conf i r m a menu
- pr ess OFF t o t ur n of f t he uni t
- pr ess ON t o t ur n t he uni t on
Figure 5: CTS 602 control

This document may be subject to change Side 9 of 24
Activating the SERVICE menu
Press and hold and ENTER simultaneously for 10 seconds. The SERVICE menu can then be
accessed. Press repeatedly until SERVICE appears on the display. Press ENTER to activate
the SERVICE menu. It is then possible to scroll through the SERVICE menu options using the p
buttons. The options available on the SERVICE menu are shown in the figure below.
HEAT
DEFROST
ENTER
SERVICE
AIR
QUALITY
AIR
EXCHANGE
TEMP.
CONTROL
INLET
CONTROL
ROOM
CONTROL
RESTART
OFF
PRESET
OFF
MANUAL
OFF
INLET
HEATING
MODBUS
ADR 30
DATALOG
INTV 10
SURFACE
Figure 6: Headlines in the service menu

This document may be subject to change Side 10 of 24
Inlet heating
In the ”Inlet heating” menu it is possible to activate and de-activate the heating surface in the inlet
air and to set the regulation time.
On the CTS602 control panel, press:
- ESC to return to the previous menu
- p to scroll upwards or downwards through the menus or to
adjust the setting of an activated menu option
- ENTER to activate a menu option
- ENTER to confirm a menu option setting
- OFF switch off the controls
- ON to switch on the controls
DEFROST
SELECT
ON ENTER
ENTER
SELECT
”OFF”
INTEGRAL
TIME 10
AIR
EXCHANGE
INLET
CONTROL
SERVICE ENTER
TEMP.
CONTROL
RESTART
OFF
MANUAL
OFF
PRESET
OFF
ROOM
CONTROL
AIR
QUALITY
INLET
HEATING
Regulation time
in minutes.
SELECT
”ON”
INTEGRAL
TIME ”10"
MODBUS
ADR 30
DATALOG
INTV 10
HEAT
SURFACE
Figure 7: The "Inlet heating" Menu

This document may be subject to change Side 11 of 24
Heating surface
The unit can be equipped with a heating surface.
It is possible to retrofit a heating surface. The surface must be activated in the CTS 602 control in
order to function together with the unit and for the frost-protection to be active.
When installing a heating surface T7 is the temperature sensor in the inlet.
Use of the CTS600 panel:
- press ESC to go one step back in the menu
- press pto move up or down in a menu or to adjust an
activated menu
- press ENTER to activate a menu
- press ENTER to confirm a menu
- press OFF to turn off the unit
- press ON to turn the unit on
SERVICE ENTER
DEFROST
INLET
CONTROL
TEMP.
CONTROL
PRESET
OFF
RESTART
OFF
ROOM
CONTROL
AIR
EXCHANGE
INLET
HEATING
AIR
QUALITY
MANUAL
OFF
MODBUS
ADR 30
DATALOG
INTV 10
Forsinkelse fra
opstart af blæsere
og varmekrav til
eftervarmefladen
frigives (0 – 60
min.)
”OFF”
0 MIN
”EL SUP”
ENTER
SELECT
VANDSUP
0–10 V
”PERIOD”
”0–10 V”
”0/5/10 V”
VALG
OFF ENTER
ENTER
FORSINK
0 MIN
0–10 V
”EL SUP”
Pulserende med
1 min. periode
Trinløs analog
10 V ON/OFF
1 min. periode
HEAT
SURFACE
Should be chosen
when installing a
heating surface for
water.
Controlled via 0 -10
V signal
Should be chosen
when installing an
electrical heating
surface, controlled
via 0-10 V signal DELAY
SELECT
SELECT
SELECT
The setting ”OFF”
is chosen for
systems without
heating element
SELECT
”WATERSUP”
SELECT
SELECT
SELECT
SELECT
SELECT
”PERIOD”
”0–10 V”
”0/5/10 V”
Pulserende med
1 min. periode
Trinløs analog
10 V ON/OFF
1 min. periode
SELECT
SELECT
SELECT
Figure 8: The “Central heating” menu

This document may be subject to change Side 12 of 24
Air quality
In the ”Air quality” menu it is possible to choose between 3 types of regulation: Humidity, Humidity
+ CO2or OFF.
On the CTS602 control panel, press:
- ESC to return to the previous menu
- p to scroll upwards or downwards through the menus or to
adjust the setting of an activated menu option
- ENTER to activate a menu option
- ENTER to confirm a menu option setting
- OFF switch off the controls
- ON to switch on the controls
DEFROST
FUNCTION
OFF ENTER
ENTER FUNCTION
”OFF”
AIR
EXCHANGE
INLET
CONTROL
SERVICE ENTER
TEMP.
CONTROL
RESTART
OFF
MANUAL
OFF
PRESET
OFF
ROOM
CONTROL
AIR
QUALITY
INLET
HEATING
Can be set to:
OFF, HUMIDITY or
HUM+CO2, when is
mounted.
MODBUS
ADR 30
DATALOG
INTV 10
HEAT
SURFACE
Figure 9: The "Air quality" Menu

This document may be subject to change Side 13 of 24
Air exchange
The AIR EXCHANGE menu allows four ventilation steps (air quantities) to be set. Individual values
for inlet and exhaust can be set for each ventilation step.
A minimum ventilation step for inlet air and minimum and maximum steps for exhaust air can also
be set.
On the CTS602 control panel, press:
-ESC to return to the previous menu
-p to scroll upwards or downwards through the menus or to
adjust the setting of an activated menu option
- ENTER to activate a menu option
- ENTER to confirm a menu option setting
- OFF switch off the controls
-ON to switch on the controls
Each ventilation step can be set
as a percentage of maximum fan
INLET
HEATING
AIR
EXCHANGE ENTER
SERVICE ENTER
DEFROST
INLET
CONTROL
TEMP.
CONTROL
PRESET
OFF
RESTART
OFF
ROOM
CONTROL
AIR
QUALITY
The lowest permissible
ventilation step for fresh air/inlet
(0-2)
The lowest permissible
ventilation step for outlet/exhaust
(1-2)
INLET
MIN 0
EXHAUST
MIN 1
EXHAUST
MAX 4
The highest permissible
ventilation step for outlet/exhaust
(3-4)
INLET23%
INLET
>2< 40%
INLET
>3< 65%
EXHAUST
>1< 25%
EXHAUST
>3< 70%
EXHAUST
>4< 100%
INLET
>4< 100%
EXHAUST
>2< 45%
speed.
MANUAL
OFF
>1<
MODBUS
ADR 30
DATALOG
INTV 10
HEAT
SURFACE
Figure 10: The "Air exchange" Menu

This document may be subject to change Side 14 of 24
Defrost
The DEFROST menu determines the mode of system operation while the evaporator surface and
the counter flow heat exchanger in the exhaust air flow is being defrosted.
Options that flash are indicated by ” ”
On the CTS602 control panel, press:
-ESC to return to the previous menu
- p to scroll upwards or downwards through the menus or to
adjust the setting of an activated menu option
- ENTER to activate a menu option
- ENTER to confirm a menu option setting
- OFF switch off the controls
- ON to switch on the controls
INLET
HEATING
DEFROST ENTER
AIR
EXCHANGE
INLET
CONTROL
SERVICE ENTER
TEMP.
CONTROL
RESTART
OFF
MANUAL
OFF
PRESET
OFF
ROOM
CONTROL
AIR
QUALITY
MODBUS
ADR 30
DATALOG
INTV 10
HEAT
SURFACE
Lockout between 2
defrost periods. Can
be set from 15 –
720 minuttes.
PERIOD
30 MIN
Max. defrosting
time of heat
exchanger.
TERMINAT
T4 5°C
COMP MAX
5 MIN
EXCH MAX
25 MIN
Max. defrosting
time of
compressor.
Adjustable temperature,
which terminates
defrosting of heat
exchanger. Temperature
measured at sensor T4.
Adjustable temperature to stop
antifreeze on passive exchanger
measured on T4 (1-5). ”- - ”
5eactivate antifreeze function
FROSTSIK
T4 3 °C
START
T6 -2 °C
Adjustable temperature to
start evaporator defrost on
T6 [-10…0]
NO-FROST
STANDARD
Select "EXTRA" for maximum
power of preheating at
evaporator defrost
Figure 11: The "Defrost" Menu

This document may be subject to change Side 15 of 24
Temp. control
The temperature sensor to be used to control the system is selected in the TEMP. CONTROL
menu. It is also possible to stipulate a minimum temperature at which the system is to be stopped
to prevent further cooling of the building if the primary heating system has cut out for some reason.
Options that flash are indicated by ” ”
On the CTS602 control panel, press:
-ESC to return to the previous menu
- p to scroll upwards or downwards through the menus or to
adjust the setting of an activated menu option
- ENTER to activate a menu option
- ENTER to confirm a menu option setting
- OFF switch off the controls
- ON to switch on the controls
DATALOG
INTV 10
HEAT
SURFACE
INLET
HEATING
TEMP.
CONTROL ENTER
AIR
EXCHANGE
DEFROST
INLET
CONTROL
SERVICE ENTER
RESTART
OFF
MANUAL
OFF
PRESET
OFF
ROOM
CONTROL
EXTERNAL
-1°C
AIR
QUALITY
Option for an extra heating
element via relay output,
R8. R8 is an accessory and
the option is only possible
via accessory pcb.
The temperature is added
or subtracted to/from the
set point shown in the main
menu.
Determines the sensor to be
used for control purposes:
PANEL: T15 (in control panel)
EXTERNAL: T10 (Duct sensor
If T15 is chosen as the
controlling sensor the sensor
follows ROOM LOW this
temperature.
SENSOR
PANEL SENSOR
”PANEL”
PRIORITY
”HP”
PRIOR.
”OFF”
ENTER
ENTER
ROOM
LOW 10°C
PRIORITY
HP
Stops the system at this
room temperature (20-
1°C, -- indicates that the
function is inactive). The
”--” setting should be
used if the control panel
is installed in a cold
location.
OFF:
ventilation
without heat
pump.
VP:
ventilation
with only
heat pump
active.
MODBUS
ADR 30
SENSOR
”EXTERNAL”
Figure 12: The "Temp. control" Menu

This document may be subject to change Side 16 of 24
Inlet control
The inlet control menu makes it possible to set the time in which the compressor has to be shut off
before restart.
Parameters in the INLET CONTROL menu should
only be set by experienced control
technicians.
On the CTS602 control panel, press:
- ESC to return to the previous menu
- p to scroll upwards or downwards through the menus or to
adjust the setting of an activated menu option
- ENTER to activate a menu option
- ENTER to confirm a menu option setting
- OFF switch off the controls
- ON to switch on the controls
INLET
HEATING
TEMP.
CONTROL
AIR
EXCHANGE
DEFROST
SERVICE ENTER
RESTART
OFF
MANUAL
OFF
PRESET
OFF
ROOM
CONTROL
INLET
CONTROL
HEATPUMP
RST 6m
ENTER
ENTER
Minimum time in
minutes for compressor
to be shut off before
restart
AIR
QUALITY
MODBUS
ADR 30
DATALOG
INTV 10
HEAT
SURFACE
GAIN 7.0%/°
INTEGRAL
120 s
N-ZONE
0.5°C
TMP-RAMP
0.10°/s
CAP-RAMP
0.5%/s
Figure 13: The "Inlet control" Menu

This document may be subject to change Side 17 of 24
Room control
The ROOM CONTROL menu allows the room temperature controller to be set.
Options that flash are indicated by ” ”
Parameters in the ROOM CONTROL menu should only be set by experienced control
technicians.
On the CTS602 control panel, press:
- ESC to return to the previous menu
- p to scroll upwards or downwards through the menus or to
adjust the setting of an activated menu option
- ENTER to activate a menu option
- ENTER to confirm a menu option setting
- OFF switch off the controls
- ON to switch on the controls
INLET
HEATING
ROOM
CONTROL
TEMP.
CONTROL
AIR
EXCHANGE
DEFROST
INLET
CONTROL
SERVICE ENTER
RESTART
OFF
MANUAL
OFF
PRESET
OFF
AIR
QUALITY
MODBUS
ADR 30
DATALOG
INTV 10
HEAT
SURFACE
ENTER RESPONSE
NORMAL
RESPONSE
”USER”
RESPONSE
”FAST”
RESPONSE
”NORMAL”
GAIN 6.0°/°
INTERGRAL
6m
RESPONSE
”SLOW”
ENTER
N-ZONE
2.0°C
ENTER RESPONSE
USER
N-ZONE
2.0°C
The RESPONSE
menu is only
accessible when the
CTScontrol is
set up to heating
surface
Rum control parametres:
Response Gain Integral
Slow 4.0 12
Normal 6.0 6
Fast 8.0 4
User 6.0 6
Figure 14: The "Room control" Menu

This document may be subject to change Side 18 of 24
Restart
The RESTART menu allows the system to be set to restart automatically in connection with high or
low pressure faults.
Fire alarms can be acknowledged automatically in connection with fire drills/testing. A condition for
acknowledgement is that the fire thermostat input has returned to normal state.
Options that flash are indicated by ” ”
The ”HP/LP” setting in the RESTART menu must not be used during normal operation.
On the CTS602 control panel, press:
- ESC to return to the previous menu
- p to scroll upwards or downwards through the menus or to
adjust the setting of an activated menu option
- ENTER to activate a menu option
- ENTER to confirm a menu option setting
- OFF switch off the controls
- ON to switch on the controls
AIR
QUALITY
AIR
EXCHANGE
DEFROST
INLET
CONTROL
SERVICE ENTER
TEMP.
CONTROL
MANUAL
OFF
PRESET
OFF
ROOM
CONTROL
RESTART
OFF
INLET
HEATING
MODBUS
ADR 30
DATALOG
INTV 10
HEAT
SURFACE
This setting must never be
used during normal
operation. Indicates that
the system is to be
restarted automatically in
connection with high or
low pressure alarms.
ENTER
RESTART
”HP/LP”
RESTART
”OFF” Indicates that the system
will not be restarted
automatically in
connection with high or
low pressure alarms.
RESTART
”FIRE”
FIRE:Even Receipt
when fire input is back
to normal
Figure 15: The "Restart" Menu

This document may be subject to change Side 19 of 24
Preset
The PRESET menu allows default factory settings to be stored.
RESTORE menu allows you to reload a copy of the installation setup.
By keeping the ESC + key pressed for 5 seconds a new menu item RESTORE appear, this is
then acceptable / activated by pressing the ENTER
Options that flash are indicated by ” ”
On the CTS602 control panel, press:
-ESC to return to the previous menu
- p to scroll upwards or downwards through the menus or to
adjust the setting of an activated menu option
- ENTER to activate a menu option
- ENTER to confirm a menu option setting
- OFF switch off the controls
-ON to switch on the controls
INLET
HEATING
AIR
EXCHANGE
DEFROST
INLET
CONTROL
SERVICE ENTER
TEMP.
CONTROL
MANUAL
OFF
ROOM
CONTROL
RESTART
OFF
PRESET
OFF ENTER PRESET
OFF
PRESET
STANDARD
When ”standard” is
chosen all factory
settings are reset. An
eventual supplementary
heating surface must be
re-activated.
frost-protected until it is
correctly installed and
activated in the service
menu.
AIR
QUALITY
”BACKUP”
”RESTORE”
PRESET
PRESET The backup will be
saved.
The backup is restored.
Subsequently, the
system must be
restarted.
MODBUS
ADR 30
DATALOG
INTV 10
HEAT
SURFACE
Figure 16: The "Preset" Menu

This document may be subject to change Side 20 of 24
Manual
The MANUAL menu allows system functions to be tested manually.
Options that flash are indicated by ” ”
On the CTS602 control panel, press:
- ESC to return to the previous menu
- p to scroll upwards or downwards through the menus or to
adjust the setting of an activated menu option
- ENTER to activate a menu option
- ENTER to confirm a menu option setting
- OFF switch off the controls
- ON to switch on the controls
AIR
QUALITY
AIR
EXCHANGE
DEFROST
INLET
CONTROL
SERVICE ENTER
TEMP.
CONTROL
PRESET
OFF
ROOM
KONTROL
RESTART
OFF
MANUAL
OFF MANUAL
”OFF”
ENTER
MANUAL
”DEFROST”
MANUAL
”INLET”
MANUAL
”EXHAUST”
MANUAL
”VENT+CPR”
MANUEL
”VEN+HEAT”
MANUEL
”WTR HEAT”
Manual test of hot water
production – 1000W
Manual test of ventilation
and heating
Manual test of ventilation
and compressor
Manual test of exhaust
Manual test of inlet
Manual test of defrost
function
Manual test inactive
(during normal
operation)
INLET
HEATING
MODBUS
ADR 30
DATALOG
INTV 10
HEAT
SURFACE
Figure 17: The "Manual" Menu
Other manuals for Combi 302 Polar Top
1
Table of contents
Other nilan Heating System manuals
Popular Heating System manuals by other brands

Energotech
Energotech EnergoStrip EE-3 Series Mounting and installation

REVENTON
REVENTON INSPIRO Technical documentation

Alnor
Alnor HRU-WALL user manual

Vallox
Vallox DIGIT2 SE VKL Instructions for use and maintenance

Baxi
Baxi Valor Fires 540 quick guide

Myson
Myson SLIM-LINE RC Installation & maintenance manual